| 2019-07-11 12:59:57 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. FBC B 107.2.1. PLEASE PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION ON SUBMITTED DRAWINGS: WINDOW |
| | SIZES; DESIGNATE BUILDING TO RECEIVE NEW WINDOWS AND |
| | STORM SHUTTERS. |
| | 2. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT |
| | APPROVAL, PROVIDE THE FOLLOWING FOR EACH PRODUCT: COVER |
| | SHEET (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE |
| | CODE VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT) EVALUATION REPORT; |
| | INSTALLATION INSTRUCTIONS |
| | 3. PROVIDE TWO SETS OF PRODUCT APPROVALS/NOA'S FOR THE |
| | REQUIRED MULLION BARS TO BE USED. AS PER FAC9N-3 |
| | 4. FBC B 107.2.1. PLEASE CLARIFY; ?SEALING UP |
| | OPENINGS?. LEVEL 2 ALTERATIONS INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. |
| | 5. FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS |
| | DESCRIBED IN SECTION 504 SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 8. IN ADDITION TO THE |
| | REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY |
| | WITH THE REQUIREMENTS OF CHAPTER 7. |
| | |