| 2019-07-18 09:18:57 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19061299 |
| | 7/18/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.1: THE O/A CALCULATIONS ARE BASED ON RATES |
| | FOR OFFICES HOWEVER THE PLANS ARE INDICATING THE TENANT |
| | SPACES ARE "STUDIOS". PLEASE CLARIFY WHAT TYPES OF |
| | STUDIOS THESE ARE.TABLE 403.3.1.1 DOES NOT PROVIDE A |
| | VENTILATION IN GENERAL FOR STUDIOS, HOWEVER THERE ARE |
| | RATES LISTED FOR PHOTO STUDIOS, THEATER STUDIOS, AND |
| | ART CLASSROOMS. PLEASE SEE SECTION 403.3.1.1 AND |
| | PROVIDE THE RATES THAT ARE MOST SIMILAR TO WHAT THE USE |
| | AND FUNCTIONS OF THESE SPACES WILL BE. |
| | |
| | 2) M1.1 & M1.2: PROVIDE EITHER NOTES OR MEASUREMENTS ON |
| | THE PLAN TO INDICATE THE LOCATIONS OF THE O/A INLETS |
| | ARE IN COMPLIANCE WITH SECTION 401.4 FOR REQUIRED |
| | CLEARANCES. |
| | |
| | 3) M2.1 & M2.2: PROVIDE A DETAIL FOR ATTACHING THE NEW |
| | CU'S TO THE EXISTING STANDS- SECTION 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |