| 2019-07-11 06:50:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN IS A PRINTED COPY OF A DIGITALLY SIGNED PLAN |
| | AND IS NOT CONSIDERED TO BE SIGNED AND SEALED PER |
| | FLORIDA STATUTES AND THE F.A.C. PLEASE SEE REQUIREMENTS |
| | BELOW FOR SIGNATURES AND SEALS. |
| | |
| | PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE |
| | LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S |
| | SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED |
| | ON PHYSICALLY TRANSMITTED DOCUMENTS. |
| | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON |
| | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED. |
| | |
| | AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED |
| | DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A |
| | WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART |
| | OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO |
| | PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT |
| | THE SIGNATURE IS NOT MADE ILLEGIBLE. |
| | CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN |
| | USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN |
| | EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE |
| | SIGNATURE ILLEGIBLE. |
| | |
| | 2. "NEW" SERVICE SHOWN ON PAGE E4 OF PLAN HAS ALREADY |
| | BEEN INSTALLED UNDER THE MAIN ELECTRICAL SUB PERMIT FOR |
| | THIS ADDRESS. PLEASE REMOVE SERVICE FROM PLAN. FBC |
| | 107.2.1 |
| | |
| | 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF LIGHT |
| | FIXTURES SHOWING UL OR ANOTHER NRTL LISTING. FBC |
| | 107.2.1 NEC 90.7, 110.2, 110.3B |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |