Plan Review Details - Permit 19061262
Plan Review Stops For Permit 19061262
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-10 Cont ID  
Sent By pvalenti Date 2019-07-10 Time 08:15 Rev Time 0.00
Received By pvalenti Date 2019-07-10 Time 08:14 Sent To  
Notes
2019-07-10 08:33:35 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING PLAN REVIEW PASSED WITH NOTES:
  
 THE FLOORING MATERIAL IS DIRECT TO CONCRETE SLAB WITH
 AN APPROVED INCORPORATED INSULATION.
 THE CONTRACTOR IS REQUIRED TO SCHEDULE A FINAL
 INSPECTION WITH PHOTOS OF THE INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 16:05 Rev Time 0.00
Received By pvalenti Date 2019-07-03 Time 16:05 Sent To  
Notes
2019-07-03 16:15:26***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLAN REVIEW DENIED:
  
 FBC B 107. PROVIDE THE TEST REPORTS TO VERIFY RESULTS
 PERTHE FOLLOWING CODE SECTIONS:
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-10 Cont ID  
Sent By pvalenti Date 2019-07-10 Time 08:16 Rev Time 0.00
Received By pvalenti Date 2019-07-10 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 16:15 Rev Time 0.00
Received By pvalenti Date 2019-06-26 Time 15:12 Sent To  
Notes
2019-06-27 15:12:27BLDG <5K