Plan Review Details - Permit 19061208
Plan Review Stops For Permit 19061208
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-31 Cont ID  
Sent By fgiaquin Date 2019-07-31 Time 07:00 Rev Time 0.00
Received By fgiaquin Date 2019-07-31 Time 07:00 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-26 Cont ID  
Sent By fgiaquin Date 2019-07-26 Time 06:03 Rev Time 0.00
Received By fgiaquin Date 2019-07-26 Time 05:59 Sent To I
Notes
2019-07-26 06:08:15SEE LAST PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By fgiaquin Date 2019-07-12 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2019-07-12 Time 06:06 Sent To I
Notes
2019-07-12 06:41:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE UL OR OTHER NRTL LISTING OF ALL MATERIALS
 AND EQUIPMENT TO BE INSTALLED. NO PRODUCT APPROVAL
 PROVIDED FOR CARD READER, DOOR CONTACT, ELECTRIC
 STRIKE. FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
 2. FIXED TRANSMITTERS AND PENDANT TRANSMITTERS ARE NOT
 LISTED, ONLY SHOW FCC "COMPLIANCE. NEC 90.7, 110.2,
 110.3B
  
 3. NO LOCATION SHOWN FOR FIXED TRANSMITTERS ON PLAN.
 FBC 107.2.1
  
 4. NO LOCATION SHOWN FOR POWER SUPPLY ON PLAN, ONLY
 LOCATION SHOWN IS FOR CONTROLLER. FBC 107.2.1
  
 5. POWER SUPPLY AND CONTROLLER ARE SHOWN TO BE
 "EXISTING" ON RISER DIAGRAM PAGE, PLEASE CLARIFY
 WHETHER A NEW POWER SUPPLY AND CONTROLLER ARE TO BE
 INSTALLED. IF SO PROVIDE CUT SHEETS FOR PRODUCT
 APPROVAL. ONLY CUT SHEET SUPPLIED WAS FOR CONTROLLER.
 FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By pleduc Date 2019-07-19 Time   Rev Time 0.00
Received By pleduc Date 2019-07-19 Time 13:55 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-28 Cont ID  
Sent By pleduc Date 2019-06-28 Time   Rev Time 0.00
Received By pleduc Date 2019-06-28 Time 11:19 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-26 Cont ID  
Sent By fgiaquin Date 2019-07-26 Time 06:08 Rev Time 0.00
Received By fgiaquin Date 2019-07-17 Time 15:27 Sent To  
Notes
2019-07-18 15:27:23RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-12 Cont ID  
Sent By fgiaquin Date 2019-07-12 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2019-06-25 Time 11:29 Sent To  
Notes
2019-06-27 11:29:51ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved