Plan Review Details - Permit 19061173
Plan Review Stops For Permit 19061173
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 14:37 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 06:48 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 06:48 Sent To  
Notes
2019-09-24 06:48:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481 (NO ELECTRICAL PLAN
 WAS PROVIDED. THERE IS A SUBMITTAL THAT HAS DRAWINGS
 WITHIN. THESE DRAWINGS SHOULD BE SUBMITTED AS PLAN
 SHEETS, WITH EACH SHEET SIGNED/SEALED PER FLORIDA
 STATUTES. PROVIDE CORRECTIONS.)
 2. FOR INSTRUCTIONS ON HOW TO UPLOAD PLANS, CONTACT
 [email protected] . WPB FBC 107.1 (INFORMATIONAL
 ONLY.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jpearson Date 2019-07-18 Time 09:26 Rev Time 0.00
Received By jpearson Date 2019-07-18 Time 09:26 Sent To  
Notes
2019-07-18 09:26:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 2. FOR INSTRUCTIONS ON HOW TO UPLOAD PLANS, CONTACT
 [email protected] . WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-24 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-16 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-25 Time 08:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 14:37 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 14:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 06:46 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 06:46 Sent To  
Notes
2019-09-24 06:46:17PER THE PREVIOUS COMMENT, EACH SHEET OF PLAN MUST BE
 SIGNED BY THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FLORIDA STATUTES, FOR ELECTRICAL WORK, THIS PERSON MUST
 BE A DESIGN PROFESSIONAL WITH A DIGITAL SIGNATURE AND
 SEAL, OR THE ELECTRICAL CONTRACTOR QUALIFIER WITH
 DIGITAL SIGNATURE. PROVIDE CORRECTIONS. WPB FBC 107.1;
 FS 471/481
  
 PREVIOUS COMMENT:
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE MUST
 INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jpearson Date 2019-07-18 Time 09:24 Rev Time 0.00
Received By jpearson Date 2019-07-18 Time 09:23 Sent To  
Notes
2019-07-18 09:23:55PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. ADDITIONALLY, THE DIGITAL SIGNATURE MUST
 INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481