Plan Review Details - Permit 19061141
Plan Review Stops For Permit 19061141
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-06 Cont ID  
Sent By dbattles Date 2019-08-06 Time 13:12 Rev Time 0.00
Received By dbattles Date 2019-08-06 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-24 Cont ID  
Sent By dbattles Date 2019-07-24 Time 15:19 Rev Time 0.00
Received By dbattles Date 2019-07-24 Time 15:18 Sent To  
Notes
2019-07-24 15:29:14BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19061141
 2ND REVIEW: JULY 24, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.2(2) TABLE FBC[R]
 PLEASE PROVIDE WIND DESIGN DATA FOR NEW WINDOWS.
 PROJECT DATA:
 TYPE OF WALL CONSTRUCTION = _________(WOOD, MASONRY?)
 RISK CATEGORY = ___(II)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO ROOF DECK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 COMPONANT & CLADDING:
 FBC TABLE 301.2(2) FBC[R]
 DESIGN PRESSURE = +___ & -___
 301.2(3) FBC[R] CHECK EXPOSURE AND M.R.H. TO DETERMINE
 IF ADJUSTMENT FACTOR NEEDED.
 MULTIPLE DESIGN PRESUURES BY THE ADJUSTMENT FACTOR IF <
 OR > 1.00
  
 PROVIDE PRESSURE ON EACH WINDOW/DOOR AND INDICATE IF
 THE OPENING IS IN THE INTERIOR OR EXTERIOR ZONE.
  
 1A) 2ND REVIEW ADDITIONAL COMMENT:
 THE DRAWING SHEET PROVIDED IS THE SAME SHEET PROVIDED
 WITH THE INITIAL PERMIT.
 IT STATES THAT WINDOWS ARE EXISTING AND DOES NOT SHOW
 THE NEW WORK.
 PLEASE PROVIDE A SHEET TO SHOW NEW WORK, WINDOW
 SCHEDULE AND PREVIOUSLY REQUESTED DESIGN DATA.
 I REVIEWED INITIAL PERMIT SHEETS AND THIS DESIGN DATA
 WAS NOT ALREADY PROVIDED SINCE ORIGINALLY THERE WAS NO
 WINDOW/DOOR REPLACEMENT.
  
 2) OK - PRODUCT APPROVALS SUBMITTED AND STAMPED FOR
 APPROVAL.
  
 NOTES:
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By dbattles Date 2019-07-10 Time 09:55 Rev Time 0.00
Received By dbattles Date 2019-07-10 Time 09:55 Sent To  
Notes
2019-07-10 09:59:47BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19061141
 REVIEWED: JULY 10, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.2(2) TABLE FBC[R]
 PLEASE PROVIDE WIND DESIGN DATA FOR NEW WINDOWS.
 PROJECT DATA:
 TYPE OF WALL CONSTRUCTION = _________(WOOD, MASONRY?)
 RISK CATEGORY = ___(II)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO ROOF DECK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 COMPONANT & CLADDING:
 FBC TABLE 301.2(2) FBC[R]
 DESIGN PRESSURE = +___ & -___
 301.2(3) FBC[R] CHECK EXPOSURE AND M.R.H. TO DETERMINE
 IF ADJUSTMENT FACTOR NEEDED.
 MULTIPLE DESIGN PRESUURES BY THE ADJUSTMENT FACTOR IF <
 OR > 1.00
  
 PROVIDE PRESSURE ON EACH WINDOW/DOOR AND INDICATE IF
 THE OPENING IS IN THE INTERIOR OR EXTERIOR ZONE.
  
 2) 107.3.4.1 FBC[AMENDED] PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR WINDOWS, WINDOW MULL(IF APPLICABLE) AND
 DOORS(IF BEING REPLACED)
  
 NOTES:
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-08-01 Cont ID  
Sent By aborngra Date 2019-08-01 Time 15:16 Rev Time 0.00
Received By aborngra Date 2019-08-01 Time 15:17 Sent To B
Notes
2019-08-01 15:16:51THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITIONS:
  
 A. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 B. ALL WINDOWS AND DOORS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW OR DOOR FRAME OPENING. ALL WINDOWS
 SHALL MATCH THE INSET/DEPTH OF THE ORIGINAL WINDOWS
 WITHIN THE WINDOW OPENING.
 C. THE EXISTING MULLIONS SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF THE SAME WIDTH.
 D. ALL WINDOW FRAMES SHALL BE WHITE IN COLOR.
 E. ALL WINDOWS AND DOORS THAT HAVE PROPOSED MUNTINS
 SHALL HAVE EXTERNAL OGEE DIMENSIONAL MUNTINS.
 F. THE SOUTH ELEVATION PAIRED SINGLE-HUNG WINDOWS WITH
 A HORIZONTAL 2/2 LITE PATTERN SHALL BE 1/1/ LITE
 PATTERN.
  
 STAFF RECOMMENDS RECYCLING, DONATING, OR STORING ANY
 ORIGINAL WOOD WINDOWS THAT SHALL BE REMOVED AS A PART
 OF THIS PROJECT.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2019-07-22 Cont ID  
Sent By aborngra Date 2019-07-22 Time 10:23 Rev Time 0.00
Received By aborngra Date 2019-07-19 Time 15:49 Sent To B
Notes
2019-07-22 10:23:43THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. REVISE THE ELEVATIONS TO REFLECT THAT THE WINDOWS
 AND DOORS ARE BEING REPLACED.
 2. PROVIDE A WINDOW AND DOOR SCHEDULE ILLUSTRATING THE
 EXISTING AND PROPOSED SIZES, MATERIAL, CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E, FRAME COLOR, LITE PATTERN AND
 ANY OTHER ADDITIONAL DETAILS THAT MAY BE REQUIRED.
  
 THE FOLLOWING ARE PROPOSED CONDITIONS OF APPROVAL,
 ADDITIONAL CONDITIONS MAY BE ADDED AFTER RESUBMITTAL.
  
 A. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 B. ALL WINDOWS AND DOORS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW OR DOOR FRAME OPENING. ALL WINDOWS
 SHALL MATCH THE INSET/DEPTH OF THE ORIGINAL WINDOWS
 WITHIN THE WINDOW OPENING.
 C. THE EXISTING MULLIONS SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF THE SAME WIDTH.
  
 STAFF RECOMMENDS RECYCLING, DONATING, OR STORING ANY
 ORIGINAL WOOD WINDOWS THAT SHALL BE REMOVED AS A PART
 OF THIS PROJECT.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By aborngra Date 2019-07-02 Time 09:38 Rev Time 0.00
Received By aborngra Date 2019-07-02 Time 09:38 Sent To B
Notes
2019-07-02 09:38:34THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. REVISE ?WIND NOTE?. ?NO EXTERIOR REVISIONS TO THIS
 BUILDING? AND ?ALL ? WINDOWS ARE TO REMAIN AS BUILT.?
 REVISE TO REFLECT UPDATED WORK.
 2. PROVIDE PRODUCT APPROVALS FOR WINDOWS. ONLY ALUMINUM
 OR WOOD WINDOWS SHALL BE APPROVED BY STAFF.
 3. REVISE WINDOW SCHEDULE TO REFLECT THAT ALL WINDOWS
 WILL BE REPLACED IN-KIND WITH MATCHING PROFILE AND
 EXTERNAL OGEE DIMENSIONAL MUNTINS.
  
 THE FOLLOWING ARE PROPOSED CONDITIONS OF APPROVAL,
 ADDITIONAL CONDITIONS MAY BE ADDED AFTER RESUBMITTAL.
  
 A. ALL WINDOWS SHALL HAVE CLEAR GLASS OR CLEAR GLASS
 WITH LOW-E COATING.
 B. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL
 WINDOW FRAME AND MATCH THE INSET/DEPTH OF THE ORIGINAL
 WINDOW WITHIN THE WINDOW OPENING.
 C. THE EXISTING MULLIONS SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF THE SAME WIDTH.
  
 STAFF RECOMMENDS RECYCLING OR DONATING ANY ORIGINAL
 WOOD WINDOWS THAT SHALL BE REMOVED AS A PART OF THIS
 PROJECT.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-06 Cont ID  
Sent By dbattles Date 2019-08-06 Time 13:13 Rev Time 0.00
Received By dbattles Date 2019-07-30 Time 13:31 Sent To  
Notes
2019-07-31 13:31:16RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-24 Cont ID  
Sent By dbattles Date 2019-07-24 Time 15:19 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 11:38 Sent To  
Notes
2019-07-19 11:38:19RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-10 Cont ID  
Sent By dbattles Date 2019-07-10 Time 09:55 Rev Time 0.00
Received By dbattles Date 2019-06-24 Time 15:01 Sent To  
Notes
2019-06-25 15:01:43REVISION ROUTED TO HISTORIC INBOX