| Plan Review Stops For Permit 19061126 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-20 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-12 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-12 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2019-07-12 10:51:01 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19061126 | | | REVIEWED: JULY 12, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS: | | | - PLEASE SHOW LOCATION OF SMOKE DETECTORS FOR NEW | | | ADDITION. | | | | | | 2) 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS | | | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED | | | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN | | | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, | | | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO | | | BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA | | | STATUTES. | | | - PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS. | | | | | | 3) 103.1.1.2 FBC[RE] THE ENERGY CALCULATIONS STATE | | | CAHTHEDRAL CEILING. | | | - IF CATHEDRAL CEILING WAS BEING USED THE AREA WOULD BE | | | MORE. PLEASE ADJUST ENERGY CALCULATIONS TO STATE THE | | | TYPE OF CEILING BEING UTILIZED. ALSO, CHECK ROOF TYPE | | | SAYS COMPOSITION SHINGLES. | | | | | | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL (IF APPLICABLE), DOORS AND | | | TRANSOMS, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED. | | | - ALSO, CHECK WINDOW SCHEDULE ON SHEET 9. SIZES DON?T | | | MATCH WHAT IS SHOWN ON FLOOR PLAN, AND I DON?T SEE | | | WINDOW IN BATHROOM ON THE SCHEDULE. | | | | | | 5) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED. | | | | | | NOTE: | | | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-08-12 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-08-12 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-18 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-18 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2019-07-18 16:41:31 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | SMOKE ALARMS MISSING R314 FBC | | | | | | OUTLET ON THE OUTDOOR SIDE MISSING | | | | | | E3901.7 OUTDOOR OUTLETS. | | | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY | | | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 | | | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE | | | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH | | | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. | | | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM | | | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE | | | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE | | | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE | | | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE | | | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] | | | | | | CODE IS BASED ON 2014 NEC NOT 2008 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-08-23 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-08-23 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-07 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-07-19 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-07-02 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-02 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-07-02 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-24 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-09-05 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-09-05 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-23 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2019-09-05 11:44:47 | RECEIPT 2019-0906-65 - $185.17 - PAID | | 2019-08-23 09:51:15 | 8/23/19 EMAILED IMPACT FEE OFFICE. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-12 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-12 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2019-07-12 10:04:15 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-20 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-07-19 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-07-19 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2019-07-19 11:12:08 | PLAN DENIED | | | PROVIDE EQUIPMENT SCHEDULE ON PLAN. | | | PROVIDE LOCATION OF CONDENSER ON PLAN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-20 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-18 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-18 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2019-07-18 09:06:51 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHOWER DRAINS SHALL HAVE AN OUTLET SIZE OF NOT LESS | | | THAN 11/2 INCHES IN DIAMETER. PER FBC RES P2708.2 | | | | | | 2. THE SHOWER DRAIN SHALL CONNECT TO THE HORIZONTAL WET | | | VENT PIPING IT SHALL NOT BE SHOWN ABOVE THE LAVATORY ON | | | THE VERTICAL VENT STACK. PER WPB AMEND TO FBC | | | 107.3.5.3(12) | | | | | | 3. PROVIDE SHOWER PAN DETAIL SHOWING COMPLIANCE WITH | | | FBC RES P2709 THROUGH P2709.4 | | | | | | 4. PROVIDE SIZING CHART FOR TANKLESS HEATER ALSO | | | PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION | | | GUIDE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. THE PLANS SHALL BE DIGITALLY SIGNED BY THE PERSON | | | RESPONSIBLE FOR DESIGN. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-20 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-12 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2019-07-12 11:01:50 | SEE BUILDING COMMENTS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-08-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-23 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-23 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2019-08-20 15:54:51 | 8/20/19 HARD COPIES ROUTED TO CTHROOP FOR REVIEW. LEM |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-20 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2019-08-20 09:47:31 | SIGNATURE AND SEAL REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | DIGITAL REVIEW | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-12 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-12 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2019-07-12 11:01:06 | ANY NEW SHEETS SUBMITTED WILL NEED TO BE VERIFIED FOR | | | SIGNATURE. | | 2019-07-02 09:54:59 | 7/2/19 ORIGINAL COPIES OF PLANS LOCATED IN LIBRARY. LEM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-08-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-08-20 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-07-05 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2019-07-05 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-07-05 10:01:58 | *********************************ZONING | | | FAILED********************************** | | | | | | PROVIDE A COPY OF SURVEY SHOWING ADDITION AND EXISTING | | | AND PROPOSED SETBACKS. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|