 |
Plan Review Details - Permit 19061087
| Plan Review Stops For Permit 19061087 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-12-27 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-27 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-27 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-11-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-11-16 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-11-16 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2019-11-16 08:26:15 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19061087 | | | ADD: 950 EVERNIA ST. 1ST FLOOR. | | | CONT: NKT CONSTRUCTION SERVICES. | | | TEL: 561-662-8150 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: SAT. NOV. 16TH/2019 | | | ACTION: DENIED | | | | | | 1-7 COMPLIED. | | | | | | 8) SEMI-COMPLIED. | | | 8A) THIS REVIEW THE DESIGNER OF RECORD HAS SHOWN THE | | | LOCATION OF A HI-LOW DRINKING FOUNTAIN. SINCE THE | | | DRINKING FOUNTAIN IS NOT LOCATED IN AN ALCOVE THE | | | DRINKING FOUNTAIN WILL ALSO NEED TO SHOW COMPLIANCE | | | WITH PROTRUDING OBJECTS. PLEASE REVIEW THE 2017 | | | FBC-ACCESSIBILITY CODE SECTION: | | | | | | 307.2 PROTRUSION LIMITS. OBJECTS WITH LEADING EDGES | | | MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80 | | | INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL | | | PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO | | | THE CIRCULATION PATH. | | | | | | 8B) RESTROOMS, SEMI-COMPLIED. THE LIFE-SAFETY SHEET NOW | | | SHOWS ELEVATIONS FOR THE RESTROOMS. ONE ISSUE WITH THE | | | ELEVATION VIEW IS THE DIMENSIONING FOR HEIGHTS OF THE | | | WATER CLOSET GRAB BARS. I T APPEARS THAT THE | | | MEASUREMENT IS BEING TAKEN FROM FINISH FLOOR TO THE | | | CENTERLINE OF THE GRAB BAR. NOTE THE RANGE IS CORRECT | | | BUT THE 2017 FBC-ACCESSIBILITY CODE DOES NOT TAKE THE | | | MEASUREMENT TO THE CENTERLINE BUT FROM FINISH FLOOR TO | | | THE TOP OF THE GRASPABLE SURFACE. THAT COULD MAKE AN | | | ELEVATION CHANGE FROM 5/8 INCH TO 1 INCH HIGHER THAN | | | WOULD BE ALLOWED IF THE CONTRACTOR PLACED THE GRAB BAR | | | AT 36 INCHES FROM FINISH FLOOR TO CENTERLINE. | | | 2017 ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB | | | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL | | | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE | | | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING | | | SURFACE, NOT CENTERLINE. | | | | | | 8C) THE OTHER ISSUE IS WITH THE DIMENSIONING OF THE | | | TOILET PAPER DISPENSER. THE ELEVATION DRAWINGS SHOW | | | DIMENSIONING OF 36 INCHES FROM THE REAR WALL TO THE | | | CENTERLINE OF THE DISPENSER. WITH NOT GIVING THE | | | DIMENSION OF THE FRONT OF THE WATERCLOSET FROM OF THE | | | BACK WALL THIS IS THEN AN UNKNOWN DISTANCE BETWEEN THE | | | FRONT OF THE WATERCLOSET AND THE CENTERLINE OF THE | | | DISPENSER. THE 2017 FBC-ACCESSIBILITY CODE REQUIRES | | | DIMENSIONING FROM THE FRONT OF THE WATERCLOSET TO | | | CENTERLINE OF THE DISPENSER. | | | | | | TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE 604.7 | | | DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH | | | 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES | | | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE | | | CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED | | | BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE | | | THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW | | | CONTINUOUS PAPER FLOW. | | | | | | 9) NEW COMMENT. PLEASE REFER TO THE M-1 SHEET. THIS | | | ISSUE IS WITH THE LOCATION OF SMOKE DETECTORS. | | | THE PLANS LIST THE REQUIREMENT FOR SMOKE DETECTORS IN 2 | | | LOCATIONS, (1) SMOKE DETECTORS IN PLENUMS AND (2) SMOKE | | | DETECTORS ARE TO BE IN COMPRESSORS. | | | PLEASE UPDATE THE PLANS TO SHOW COMPLIANCE WITH: | | | | | | SMOKE DETECTOR LOCATIONS: 2017 FBC-B 907.3 FIRE SAFETY | | | FUNCTIONS. | | | 907.3.1 DUCT SMOKE DETECTORS. SMOKE DETECTORS INSTALLED | | | IN DUCTS SHALL BE LISTED FOR THE AIR VELOCITY, | | | TEMPERATURE AND HUMIDITY PRESENT IN THE DUCT AND SHALL | | | PERFORM THE INTENDED FIRE SAFETY FUNCTION IN ACCORDANCE | | | WITH THIS CODE AND THE FLORIDA BUILDING CODE, | | | MECHANICAL. | | | | | | 2017 FBC-MECHANICAL CODE SECTION 606.2.1. TO PREVENT | | | THE RECIRCULATION OF DANGEROUS QUANTITIES OF SMOKE, A | | | DETECTOR APPROVED FOR AIR DUCT USE SHALL BE INSTALLED | | | ON THE SUPPLY SIDE OF AIR-HANDLING SYSTEMS AS REQUIRED | | | BY NFPA 90A. STANDARD FOR THE INSTALLATION OF AIR | | | CONDITIONING AND VENTILATING SYSTEMS. SMOKE DETECTORS | | | LISTED FOR USE IN AIR DISTRIBUTION SYSTEMS SHALL BE | | | LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY | | | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE | | | CAPACITY GREATER THAN 2000 CUFT/MIN. | | | | | | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-10-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-10-15 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-10-15 |
Time |
06:31 |
Sent To |
|
|
| Notes |
| 2019-10-15 08:15:44 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19061087 | | | ADD: 950 EVERNIA ST. 1ST FLOOR. | | | CONT: NKT CONSTRUCTION SERVICES. | | | TEL: 561-662-8150 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. OCT. 15/2019 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | 2) BUILDING PROVISO: RED LINED PLANS.SHEET 02. A ? HOUR | | | FIRE RATED DOOR REQUIRED BETWEEN THE GARAGE WALL TO | | | BUSINESS OCCUPANCY, REQUIRED OPENING PROTECTIVES. 2017 | | | FBC-B TABLE 716.5. | | | | | | 3-7) COMPLIED. | | | | | | 8) NEW COMMENT, PLEASE REFER TO THE PLUMBING PLAN | | | REVIEWERS COMMENTS CONCERNING THE MISSING DRINKING | | | FOUNTAINS 2017 FBC-ACCESS. CODE 211.2 AND SECTIONS 603, | | | 604 CONCERNING WATER CLOSET ROOMS, THE PLANS DO NOT | | | SHOW A FLOOR LAYOUT DETAIL AND ELEVATIONS WITH REQUIRED | | | DIMENSIONS. | | | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-07-08 |
Time |
12:16 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2019-07-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-07-08 12:15:55 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19061087 | | | ADD: 950 EVERNIA ST. 1ST FLOOR. | | | CONT: NKT CONSTRUCTION SERVICES. | | | TEL: 561-662-8150 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. JULY 08/2019 | | | ACTION: DENIED | | | | | | 1) THE COVERSHEET C-1 DETAIL A HAS A SECTION THROUGH A | | | BLOCK WALL FOR A NEW DOORWAY. SHEET 02 THE PROPOSED | | | FLOOR PLAN DOES NOT INDICATE WHERE THE NEW DOORWAYS ARE | | | BEING CUT THROUGH WHICH BLOCK WALLS? ADDITIONAL | | | INFORMATION IS REQUIRED. 107.2.1.2. THE ORIGINAL PERMIT | | | 02090419 SHOWS THE ORIGINAL BLOCK WALLS AND DOOR | | | OPENINGS. PLEASE PUT SECTION MARKS THROUGH THE NEW DOOR | | | WAY FROM THE GARAGE TO THE BUSINESS OCCUPANCY AND THE | | | ELEVATOR LOBBY AND NEW DOORWAY INTO THE BUSINESS | | | OCCUPANCY. | | | | | | 2) THE NEW DOORWAYS ELEVATOR LOBBY AND THE GARAGE WALL | | | TO BUSINESS OCCUPANCY ARE PENETRATING FIRE RATED WALLS, | | | PLEASE IDENTIFY THE FIRE RATING OF THE REQUIRED OPENING | | | PROTECTIVES. 2017 FBC-B 716.5. | | | | | | 3) THE DOOR SCHEDULE ON SHEET 02 INDICATES A DOOR MARK | | | # 1 AS A 2FOOT 8 INCH DOOR. PLEASE REVIEW THE CLEAR | | | WIDTH REQUIREMENTS FOR DOORWAYS: | | | | | | 2017 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR WIDTH. DOOR | | | OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | | MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS | | | SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE | | | STOP, WITH THE DOOR OPEN 90 DEGREES. | | | | | | 2017 FBC-B 1010.1.1 SIZE OF DOORS. THE REQUIRED | | | CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR | | | THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM | | | CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS | | | WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE | | | OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 | | | DEGREES. | | | | | | 4) SHEET 02 INDICATES THE SQUARE FOOTAGE FOR THIS | | | TENANT SPACE IS 3845 SQ. FT. THE 2017 FBC-B TABLE | | | 1004.1.2 FOR BUSINESS OCCUPANCY IS 100 GROSS WHICH WILL | | | GIVE YOU 39 OCCUPANTS. FBC-B TABLE 2902.1 WILL REQUIRE | | | 2 RESTROOMS. | | | | | | 5) THE SHEET 02 THE FLOOR PLAN DOES NOT GIVE A CLEAR | | | USE OF THE 2 LARGE ROOMS, THERE IS NO FURNITURE LAYOUT | | | TO SEE IF THE USE WILL BE GROUP THERAPY IN BOTH OR | | | EITHER ROOM. THE CONCERN IS A OCCUPANT LOAD OF 50 OR | | | MORE WHICH WILL BE THEN CONSIDERED AN ASSEMBLY | | | OCCUPANCY AND MIXED USE BUILDING. TABLE 508.4. PLEASE | | | PROVIDE A FURNITURE LAYOUT FOR THE USE OF THE ROOMS. | | | PLEASE ALSO PROVIDE THE FURNITURE LAYOUT FOR THE | | | EXAMINATION ROOMS. | | | | | | 6) THE COVERSHEET INDICATES WITH NOTE 28 PRODUCT | | | APPROVALS WILL BE REQUIRED FOR THE NEW GARAGE DOOR TO | | | INTAKE ROOM. 2017 FBC-B 1609.1.2 PROTECTION OF | | | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA | | | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE | | | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY | | | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE | | | PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | | | | 7) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-10-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-10-08 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-10-08 |
Time |
08:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-17 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-17 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2019-07-17 15:53:21 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | LOAD CALCULATION FOR THE SPACE MISSING THE LIGHTING | | | LOADS. | | | | | | NEED FAULT CURRENT CALCULATION FOR 400A WITH NEW LOADS | | | ADDED. | | | | | | RISER SHOWS A 200 AMPERE METERCAN ON A 400A SERVICE. | | | | | | EXAM ROOMS WHAT KIND OF EXAMS, DO YOU ADMINISTER ANY | | | MEDICATION OR USE MEDICAL EQUIPMENT? |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2019-12-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-16 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-11-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-11-18 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-10-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-10-01 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-06-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-25 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2019-06-25 14:41:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET O2 - THERE ARE INDICATIONS OF FIRE SPRINKLER | | | HEAD LOCATIONS; HOWEVER, SOME LOCATIONS DO NOT APPEAR | | | TO BE CODE COMPLIANT. | | | | | | ADDITIONALLY, THERE ARE NO INDICATIONS OF THE POSITION | | | OF EXISTING HEADS VS INSTALLED HEADS. I.E UPRIGHT VS | | | PENDANT. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE. | | | | | | | | | | | | 2) SHEET E 1 - THERE ARE NO INDICATIONS OF FIRE ALARM | | | DEVICES EXISTING NOR PROPOSED. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT AND | | | SHOP DRAWINGS. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE. | | | | | | | | | | | | 3) SHEET M 1 - THERE ARE INDICATIONS OF A/C UNITS WITH | | | OVER 2,000 CFM WITH NO DUCT DETECTORS INDICATED THAT | | | ARE REQUIRED TO BE TIED INTO THE FIRE ALARM SYSTEM. | | | | | | PER NFPA 90 A , CHAPTER 6 CONTROLS | | | 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL. | | | 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE | | | TESTED AT LEAST ANNUALLY. | | | 6.4.2* LOCATION. | | | 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR | | | DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: | | | (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY | | | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A | | | CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN) | | | (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON | | | RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR | | | INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A | | | CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND | | | SERVING MORE THAN ONE STORY | | | | | | 6.4.3* FUNCTION. | | | 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 | | | SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON | | | DETECTING THE PRESENCE OF SMOKE. | | | | | | 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE | | | AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A | | | BUILDING, THE SMOKE DETECTORS REQUIRED BY THE | | | PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE | | | FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS | | | OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING | | | CODE. | | | | | | PLEASE REVIEW AND PROVIDE DESIGN DETAIL AND AN | | | APPLICABLE NOTE OF ACKNOWLEDGEMENT OR JUSTIFY WHY NOT | | | WITH SPECIFIC NARRATIVE AND CODE REFERENCES. | | | | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-12-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-11 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-11-20 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-11-04 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-10-24 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-10-24 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-09-26 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-17 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-06-21 |
Time |
14:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-07-08 |
Time |
12:16 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2019-07-08 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2019-12-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-30 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-30 |
Time |
16:08 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-11-15 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-11-15 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2019-11-15 17:00:24 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19061087 | | | 11/15/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | THE COMMENTS FROM THE 1ST AND 2ND REVIEW PRINTED BELOW | | | ARE STILL COMPLETELY ADDRESSED. | | | | | | 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE | | | OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS | | | CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE | | | NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE | | | INDICATING- SEE TABLE 403.3.1.1 FBC M. | | | THE LARGE OPEN SPACE IS LISTED AS A LOBBY HOWEVER THE | | | ARCHITECTURAL PLANS APPEAR TO INDICATE A MULTI-PURPOSE | | | ROOM OR RECEPTION AREA. RECEPTION AREAS ARE CALCULATED | | | AT 30 PERSONS PER 1000 SQ. FT. + 0.06 CFMS PER SQ. FT. | | | PLEASE CORRECT THE CALCULATIONS. | | | | | | 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE | | | LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE | | | AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION | | | 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE | | | SUPPLY SYSTEMS. | | | DUCT SMOKE DETECTORS ARE REQUIRED IN THE "SUPPLY | | | SYSTEMS" OF EACH AIR HANDLER. THE CORRECTED PLAN IS | | | SHOWING THEM IN THE "RETURN PLENUMS" OF THE AIR | | | HANDLERS. ALSO THERE ARE NOTES INDICATING THEY ARE TO | | | BE LOCATED IN THE AC COMPRESSORS, WHICH IS NOT A | | | REQUIRED LOCATION. PLEASE CONSULT WITH THE MANUFACTURER | | | BECAUSE THE INSTALLATION MAY NOT COMPLY WITH | | | INSTALLATION GUIDELINES AND MAY VOID THE WARRANTIES. | | | | | | 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE | | | PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS | | | DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE | | | EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING | | | LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE | | | OVERSIZED- SEE SECTION C403.2.2 FBC EC. | | | AS NOTED ABOVE NO INTERNAL LOADS HAVE BEEN CALCULATED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | BUILDING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-10-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-10-03 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-10-02 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2019-10-03 08:44:51 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19061087 | | | 10/3/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE | | | OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS | | | CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE | | | NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE | | | INDICATING- SEE TABLE 403.3.1.1 FBC M. | | | | | | 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE | | | LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE | | | AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION | | | 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE | | | SUPPLY SYSTEMS. | | | | | | 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE | | | PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS | | | DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE | | | EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING | | | LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE | | | OVERSIZED- SEE SECTION C403.2.2 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | BUILDING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-07-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-07-16 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-07-16 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2019-07-16 16:09:26 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19061087 | | | 9/16/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE VENTILATION CALCULATIONS ARE | | | INDICATING OFFICE SPACES, HOWEVER THE LARGE OPEN SPACE | | | IS IDENTIFED AS A "FUTURE TENANT SPACE". PLEASE SEE THE | | | BUILDING REVIEW COMMENTS AND PROVIDE THE CORRECT | | | IDENTIFICATION AND USE OF THIS SPACE IN ORDER TO | | | PROVIDE ADEQUATE VENTILATION PER TABLE 403.3.1.1 FBC M. | | | | | | 2) M-1: PROVIDE SYMBOLS TO INDICATE THE LOCATIONS OF | | | THE REQUIRED DUCT SMOKE DETECTORS IN THE AIR HANDLER | | | SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION 606.2.1 FBC M. | | | | | | 3) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR | | | HANDLERS- SECTION 307.2.1 FBC M. | | | | | | 4) SHOW THE LOCATIONS OF THE AC CONDENSERS AND PROVIDE | | | ENGINEERED INSTALLATION DETAILS- SECTION 301.15 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | BUILDING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-12-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-12-30 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-12-30 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-11-20 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-11-19 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2019-11-19 18:54:24 | 3RD REVIEW 19061087 | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 54 = NATIONAL FUEL GAS CODE | | | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE | | | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 3RD REVIEW | | | PLUMBING COMMENTS: DENIED PREVIOUS COMMENTS NOT | | | COMPLIED WITH FROM 1ST REVIEW. | | | | | | 1.DRINKING FOUNTAIN SHALL COMPLY WITH FBC PL 410.3 AND | | | FBC ACC SECTIONS 602 AND 306. PER WPB 107.2.1, PROVIDE | | | DETAIL SHOWING COMPLIANCE. SOME OF THIS INFORMATION HAS | | | BEEN PREVIOUSLY REQUESTED AND HAS NOT BEEN RESPONDED | | | TO. THE WATER FOUNTAIN HAS BEEN ADDED TO THE SCOPE OF | | | THE PROJECTED PLEASE ADD THE FOLLOWING DETAIL TO SHOW | | | COMPLIANCE WITH FBC ACC 211.2 MINIMUM NUMBER. NO FEWER | | | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE | | | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 | | | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. | | | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND | | | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT | | | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS | | | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. | | | 602.2 CLEAR FLOOR SPACE. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | | FOUNTAINS. | | | | | | 5.SECOND REQUEST: FBC ACC 604.5.2 -THE REAR WALL GRAB | | | BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE | | | CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE | | | SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER WPB | | | 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE. THE 36" BAR | | | IS SHOWN WITH 6" FROM END OF THE BAR TO THE WALL THIS | | | DOES NOT SHOW COMPLIANCE WITH FBC ACC 604.5.2 -THE REAR | | | WALL GRAB BAR SHALL EXTEND FROM THE CENTERLINE OF THE | | | WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 | | | INCHES MINIMUM ON THE OTHER SIDE. | | | | | | PREVIOUS COMMENTS NOT COMPLIED WITH FROM 2ND REVIEW. | | | 1. THE TOILET PAPER DISPENSER IS SHOWN AT 36" OFF THE | | | BACK WALL THIS DOES NOT COMPLY WITH FBC ACC 604.7, | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. | | | | | | 6.PER FBC PL 607.1, HOT WATER IS REQUIRED TO THE | | | SERVICE SINK.IT HAS NOT BEEN SHOWN ON WATER ISOMETRIC. | | | IF YOUR USING A TANKLESS WATER HEATER WITH AN INTEGRAL | | | TEMPERATURE LIMITING DEVISE FOR TEMPERED WATER TO THE | | | LAVATORIES YOU CAN NOT USE THE SAME TANKLESS HEATER FOR | | | THE HOT WATER REQUIRED AT THE SERVICE SINK THE | | | TEMPERATURE FOR HOT WATER IS HIGH THAN THAT OF TEMPERED | | | WATER. IN ORDER FOR THIS TO BE CODE COMPLIANT IT WILL | | | BE REQUIRED THAT YOU USE TWO DIFFERENT WATER HEATERS OR | | | A SINGLE WATER HEATER WITH AN OUTLET TEMPERATURE OF | | | OVER 110 DEG. AND TEMPERING EACH LAVATORY TO A | | | TEMPERATURE BELOW 110DEG AND SUPPLING HOT WATER OVER | | | 110 DEG. TO THE SERVICE SINK. PER FBC PL 607.1 AND | | | 416.5 | | | | | | 7.WATER DISTRIBUTION FLOOR PLAN AND RISER DIAGRAM DO | | | NOT MATCH. PER WPB FBC 107.2.1, CLARIFY. THE FLOOR PLAN | | | SHOWS SEPARATE BRANCHES FOR THE COLD WATER FOR THE | | | WATER FOUNTAIN, LAVATORY SINK AND SERVICE SINK THE | | | ISOMETRIC SHOWS A SINGLE BRANCH OFF THE MAIN TO ALL | | | FIXTURES. | | | | | | 8. THE SANITARY ISOMETRIC DRAWING DOES NOT MATCH THE | | | FLOOR PLAN THE SANITARY ISOMETRIC SHOWS A SINGLE BRANCH | | | OFF THE MAIN BUILDING DRAIN THE FLOOR PLAN SHOWS | | | SEPARATE BRANCHES FOR EACH FIXTURE AND BATHROOM | | | GROUP.PER WPB FBC 107.2.1, CLARIFY | | | | | | 9.PER FBC PL (E)607.5, PROVIDE INSULATION FOR THE HOT | | | WATER. PROVIDE SPECIFICATION PER WPB FBC 107.2.1. | | | | | | | | | NEW COMMENTS: | | | | | | 1. ON THE WATER ISOMETRIC DRAWING THERE IS THE | | | FOLLOWING VIOLATIONS. | | | A) THE HOT IS SHOWN ON THE RIGHT SIDE OF THE LAVATORY'S | | | AND COLD ON THE LEFT IT NEEDS TO BE REVERSED.PER FBC PL | | | 607.4 | | | B) THE SUPPLY TO THE WC IS SHOWN AS HOT IT SHALL BE | | | SHOWN AS COLD AND A SEPARATE BRANCH FOR TEMPERED WATER | | | TO THE LAVATORY. PER WPB AMEND TO FBC 107.2.1 | | | C) THE HOT SUPPLY FOR THE SERVICE SINK IS MISSING. PER | | | FBC PL 607.1 | | | D) THE SIZE OF THE OF THE MAIN FEED TO THIS UNIT AT | | | 1/2" APPEARS TO BE UNDERSIZED THE MINIMUM WATER SERVICE | | | IS 3/4" THOUGH THIS IS NOT A SEPARATE STRUCTURE THE | | | SAME PRINCIPAL APPLIES. APPENDIX E IN THE PLUMBING CODE | | | IS NOT ENFORCEABLE BUT IS A GOOD SIZING METHOD, PLEASE | | | PROVIDE THE SIZING CALCULATION THAT WERE USED TO | | | DETERMINE PIPE SIZING ON THIS PROJECT. PER AMEND TO FBC | | | 107.2.1 | | | E) A VALVE IS REQUIRED ON THE COLD WATER DROP FROM MAIN | | | LINE AND AT THE WATER HEATER AND EACH FIXTURE. PER FBC | | | PL 606.1(5)(8), 606.2(1) | | | | | | 2. SHOW COMPLIANCE OR PROVIDE NOT ON PLAN. 606.3 ACCESS | | | TO VALVES. ACCESS SHALL BE PROVIDED TO ALL FULL-OPEN | | | VALVES AND SHUTOFF VALVES. | | | | | | 3.PROVIDE SPECIFICATIONS AND INSTILLATION GUIDE FOR | | | TANKLESS HEATER. MANUFACTURE SPECIFICATION SHALL SHOW | | | SIZE OF WATER HEATER IS APPROVED FOR THE DEMAND OF ALL | | | PLUMBING FIXTURE. PER WPB FBC 107.2.1. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-10-03 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-10-03 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-10-03 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2019-10-03 14:24:08 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 54 = NATIONAL FUEL GAS CODE | | | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE | | | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | PLUMBING COMMENTS: DENIED | | | 1.DRINKING FOUNTAIN SHALL COMPLY WITH FBC PL 410.3 AND | | | FBC ACC SECTIONS 602 AND 306. PER WPB 107.2.1, PROVIDE | | | DETAIL SHOWING COMPLIANCE. SOME OF THIS INFORMATION HAS | | | BEEN PREVIOUSLY REQUESTED AND HAS NOT BEEN RESPONDED | | | TO. | | | 2.SECOND REQUEST: FBC ACC 604.2 -THE WATER CLOSET SHALL | | | BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND | | | TO ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL | | | BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE | | | WALL OR PARTITION. PER WPB FBC 107.2.1. PER WPB | | | 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE. | | | 3.SECOND REQUEST: FBC ACC 604.4 -THE SEAT HEIGHT OF A | | | WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES | | | MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF | | | THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A | | | LIFTED POSITION. PER WPB FBC 107.2.1. PER WPB 107.2.1, | | | PROVIDE DETAIL SHOWING COMPLIANCE. | | | 4.SECOND REQUEST: FBC ACC 604.5.1 -THE SIDE WALL GRAB | | | BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES | | | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES | | | MINIMUM FROM THE REAR WALL. PER WPB 107.2.1, PROVIDE | | | DETAIL SHOWING COMPLIANCE. | | | 5.SECOND REQUEST: FBC ACC 604.5.2 -THE REAR WALL GRAB | | | BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE | | | CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE | | | SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER WPB | | | 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE. | | | 6.SECOND REQUEST: FBC ACC 609.4 -GRAB BARS SHALL BE | | | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM | | | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED | | | TO THE TOP OF THE GRIPPING SURFACE. PER WPB 107.2.1, | | | PROVIDE DETAIL SHOWING COMPLIANCE. | | | 7.SECOND REQUEST: 606.2 -A CLEAR FLOOR SPACE FOR THE | | | LAVATORIES COMPLYING WITH 305, POSITIONED FOR A FORWARD | | | APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 | | | SHALL BE PROVIDED. PER WPB FBC 107.2.1, REVISE DRAWING | | | TO SHOW COMPLIANCE. | | | 8.SECOND REQUEST: 606.3 -LAVATORIES AND SINKS SHALL BE | | | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR | | | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. PER WPB 107.2.1, PROVIDE DETAIL | | | SHOWING COMPLIANCE. ADDITIONALLY SHOW COMPLIANCE WITH | | | FBC ACC SECTION 306. | | | 9.SECOND REQUEST: 603.3 -MIRRORS LOCATED ABOVE | | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM | | | ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED | | | ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH | | | THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER WPB | | | 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE. | | | | | | ADDITIONAL COMMENTS: | | | 1.PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL | | | COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM) | | | MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE | | | WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | | INCHES (380 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM | | | ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND | | | GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE THAT | | | CONTROLS DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS | | | PAPER FLOW. PER WPB 107.2.1, PROVIDE DETAIL SHOWING | | | COMPLIANCE. | | | 2.PER FBC ACC 604.6, FLUSH CONTROLS SHALL BE HAND | | | OPERATED OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS | | | SHALL COMPLY WITH 309. FLUSH CONTROLS SHALL BE LOCATED | | | ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN | | | AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH | | | 604.8.2. PER WPB 107.2.1, PROVIDE DETAIL SHOWING | | | COMPLIANCE. | | | 3.PER FBC ACC 604.8.1.1, TOILET COMPARTMENT DOORS, | | | INCLUDING DOOR HARDWARE, SHALL COMPLY WITH 404 EXCEPT | | | THAT IF THE APPROACH IS TO THE LATCH SIDE OF THE | | | COMPARTMENT DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF | | | THE COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES | | | (1065 MM) MINIMUM. DOORS SHALL BE LOCATED IN THE FRONT | | | PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST | | | FROM THE WATER CLOSET. WHERE LOCATED IN THE FRONT | | | PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM) | | | MAXIMUM FROM THE SIDE WALL OR PARTITION FARTHEST FROM | | | THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL OR | | | PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM) | | | MAXIMUM FROM THE FRONT PARTITION. THE DOOR SHALL BE | | | SELF-CLOSING. A DOOR PULL COMPLYING WITH 404.2.7 SHALL | | | BE PLACED ON BOTH SIDES OF THE DOOR NEAR THE LATCH. | | | TOILET COMPARTMENT DOORS SHALL NOT SWING INTO THE | | | MINIMUM REQUIRED COMPARTMENT AREA. SEE ALSO FBC ACC | | | 604.8.1.7 AND ADVISORY 604.8.1.6 AND 604.8.1.7. PER WPB | | | FBC 107.2.1, REVISE DRAWING TO SHOW COMPLIANCE. | | | 4.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE | | | SCHEDULE WITH FIXTURE SPEC AND WATER USAGE | | | REQUIREMENTS. | | | 5.PER WPB FBC 107.2.1, PROVIDE A WATER HEATER EQUIPMENT | | | SCHEDULE SPECIFYING UNIT(S), GPM AND ELECTRICAL | | | CHARACTERISTICS. | | | 6.PER FBC PL 607.1, HOT WATER IS REQUIRED TO THE | | | SERVICE SINK. | | | 7.WATER DISTRIBUTION FLOOR PLAN AND RISER DIAGRAM DO | | | NOT MATCH. PER WPB FBC 107.2.1, CLARIFY. | | | 8.SANITARY PIPING FLOOR PLAN AND RISER DIAGRAM DO NOT | | | MATCH. PER WPB FBC 107.2.1, CLARIFY. | | | 9.PER FBC PL (E)607.5, PROVIDE INSULATION FOR THE HOT | | | WATER. PROVIDE SPECIFICATION PER WPB FBC 107.2.1. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | AS THE PLANS ARE NOT SIGNED AND SEALED BY A | | | PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN | | | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE | | | DESIGNER PER WPB FBC 107.2.1. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19061087 950 EVERNIA ST | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-07-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-10 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-10 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2019-07-10 13:39:05 | 1ST REVIEW: 19061087 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1.PLEASE SHOW COMPLIANCE WITH THE FOLLOWING | | | ACCESSIBILITY REQUIREMENTS FBC ACC 2017 6TH EDITION | | | | | | 602 DRINKING FOUNTAINS | | | A)602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR | | | FLOOR OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR | | | A FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND | | | TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. | | | B)602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND | | | C)602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT | | | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS | | | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. | | | 604 WATER CLOSETS AND TOILET COMPARTMENTS | | | A)604.2 LOCATION. THE WATER CLOSET SHALL BE POSITIONED | | | WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. | | | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES | | | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR | | | PARTITION, | | | B)604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE | | | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM | | | THE REAR WALL. | | | C)604.3.2 OVERLAP.THE REQUIRED CLEARANCE AROUND THE | | | WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER | | | CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY | | | NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE | | | ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT | | | OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER | | | FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE | | | REQUIRED WATER CLOSET CLEARANCE. | | | D)604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE | | | THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 | | | INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION | | | 604.5 GRAB BARS. | | | A)604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42 | | | INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL. | | | B)604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36 | | | INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF | | | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 | | | INCHES MINIMUM ON THE OTHER SIDE. | | | C)609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE | | | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM | | | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED | | | TO THE TOP OF THE GRIPPING SURFACE, | | | 606 LAVATORIES | | | A)606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING | | | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE | | | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. | | | B)606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED | | | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER | | | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. | | | 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR | | | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF | | | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE | | | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE | | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM | | | ABOVE THE FINISH FLOOR OR GROUND. | | | | | | | | | 2.TWO BATHROOMS ARE REQUIRED PER FBC PL 403.2 SEPARATE | | | FACILITIES. WHERE PLUMBING FIXTURES ARE REQUIRED, | | | SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | | | | | 3. A DRINKING FOUNTAIN IS REQUIRED AND SHALL COMPLY | | | WITH ACCESSIBILITY. PER FBC PL TABLE 403.1 | | | | | | 4. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 | | | | | | 5. SHT. P-1 THE SANITARY ISOMETRIC DRAWING SHOWS A VENT | | | CONNECTED TO THE TOP OF THE TOILET THIS IS NOT AN | | | APPROVED VENTING METHOD PLEASE REMOVE, THE VENT FROM | | | THE LAVATORY SHALL VENT THE TOILETS PER FBC PL 912.1 | | | | | | 6.TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | 7. SHT. LS-1 AND M-1 IS SHOWING A PARTION AND WALL HUNG | | | SINK NEXT TO THE TOILET THE RST OF THE PLAN DOES NOT | | | SHOW THIS PLEASE CLARIFY | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-10-23 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-10-23 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2019-10-23 16:27:24 | PROVISO: CALSS B SPECIAL USE CONDITIONS SHALL BE MET. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-07-12 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-07-12 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2019-07-12 16:26:00 | PROVISO: CLASS B SPECIAL USE PERMIT CONDITIONS SHALL BE | | | MET BEFORE FINAL CO |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |