Plan Review Details - Permit 19061087
Plan Review Stops For Permit 19061087
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-12-27 Cont ID  
Sent By dbattles Date 2019-12-27 Time 16:39 Rev Time 0.00
Received By dbattles Date 2019-12-27 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-11-16 Cont ID  
Sent By jwitmer Date 2019-11-16 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2019-11-16 Time 06:53 Sent To  
Notes
2019-11-16 08:26:152017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061087
 ADD: 950 EVERNIA ST. 1ST FLOOR.
 CONT: NKT CONSTRUCTION SERVICES.
 TEL: 561-662-8150
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. NOV. 16TH/2019
 ACTION: DENIED
  
 1-7 COMPLIED.
  
 8) SEMI-COMPLIED.
 8A) THIS REVIEW THE DESIGNER OF RECORD HAS SHOWN THE
 LOCATION OF A HI-LOW DRINKING FOUNTAIN. SINCE THE
 DRINKING FOUNTAIN IS NOT LOCATED IN AN ALCOVE THE
 DRINKING FOUNTAIN WILL ALSO NEED TO SHOW COMPLIANCE
 WITH PROTRUDING OBJECTS. PLEASE REVIEW THE 2017
 FBC-ACCESSIBILITY CODE SECTION:
  
 307.2 PROTRUSION LIMITS. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80
 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL
 PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 8B) RESTROOMS, SEMI-COMPLIED. THE LIFE-SAFETY SHEET NOW
 SHOWS ELEVATIONS FOR THE RESTROOMS. ONE ISSUE WITH THE
 ELEVATION VIEW IS THE DIMENSIONING FOR HEIGHTS OF THE
 WATER CLOSET GRAB BARS. I T APPEARS THAT THE
 MEASUREMENT IS BEING TAKEN FROM FINISH FLOOR TO THE
 CENTERLINE OF THE GRAB BAR. NOTE THE RANGE IS CORRECT
 BUT THE 2017 FBC-ACCESSIBILITY CODE DOES NOT TAKE THE
 MEASUREMENT TO THE CENTERLINE BUT FROM FINISH FLOOR TO
 THE TOP OF THE GRASPABLE SURFACE. THAT COULD MAKE AN
 ELEVATION CHANGE FROM 5/8 INCH TO 1 INCH HIGHER THAN
 WOULD BE ALLOWED IF THE CONTRACTOR PLACED THE GRAB BAR
 AT 36 INCHES FROM FINISH FLOOR TO CENTERLINE.
 2017 ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 8C) THE OTHER ISSUE IS WITH THE DIMENSIONING OF THE
 TOILET PAPER DISPENSER. THE ELEVATION DRAWINGS SHOW
 DIMENSIONING OF 36 INCHES FROM THE REAR WALL TO THE
 CENTERLINE OF THE DISPENSER. WITH NOT GIVING THE
 DIMENSION OF THE FRONT OF THE WATERCLOSET FROM OF THE
 BACK WALL THIS IS THEN AN UNKNOWN DISTANCE BETWEEN THE
 FRONT OF THE WATERCLOSET AND THE CENTERLINE OF THE
 DISPENSER. THE 2017 FBC-ACCESSIBILITY CODE REQUIRES
 DIMENSIONING FROM THE FRONT OF THE WATERCLOSET TO
 CENTERLINE OF THE DISPENSER.
  
 TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE 604.7
 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 9) NEW COMMENT. PLEASE REFER TO THE M-1 SHEET. THIS
 ISSUE IS WITH THE LOCATION OF SMOKE DETECTORS.
 THE PLANS LIST THE REQUIREMENT FOR SMOKE DETECTORS IN 2
 LOCATIONS, (1) SMOKE DETECTORS IN PLENUMS AND (2) SMOKE
 DETECTORS ARE TO BE IN COMPRESSORS.
 PLEASE UPDATE THE PLANS TO SHOW COMPLIANCE WITH:
  
 SMOKE DETECTOR LOCATIONS: 2017 FBC-B 907.3 FIRE SAFETY
 FUNCTIONS.
 907.3.1 DUCT SMOKE DETECTORS. SMOKE DETECTORS INSTALLED
 IN DUCTS SHALL BE LISTED FOR THE AIR VELOCITY,
 TEMPERATURE AND HUMIDITY PRESENT IN THE DUCT AND SHALL
 PERFORM THE INTENDED FIRE SAFETY FUNCTION IN ACCORDANCE
 WITH THIS CODE AND THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 2017 FBC-MECHANICAL CODE SECTION 606.2.1. TO PREVENT
 THE RECIRCULATION OF DANGEROUS QUANTITIES OF SMOKE, A
 DETECTOR APPROVED FOR AIR DUCT USE SHALL BE INSTALLED
 ON THE SUPPLY SIDE OF AIR-HANDLING SYSTEMS AS REQUIRED
 BY NFPA 90A. STANDARD FOR THE INSTALLATION OF AIR
 CONDITIONING AND VENTILATING SYSTEMS. SMOKE DETECTORS
 LISTED FOR USE IN AIR DISTRIBUTION SYSTEMS SHALL BE
 LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE
 CAPACITY GREATER THAN 2000 CUFT/MIN.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-15 Cont ID  
Sent By jwitmer Date 2019-10-15 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2019-10-15 Time 06:31 Sent To  
Notes
2019-10-15 08:15:442017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061087
 ADD: 950 EVERNIA ST. 1ST FLOOR.
 CONT: NKT CONSTRUCTION SERVICES.
 TEL: 561-662-8150
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 15/2019
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) BUILDING PROVISO: RED LINED PLANS.SHEET 02. A ? HOUR
 FIRE RATED DOOR REQUIRED BETWEEN THE GARAGE WALL TO
 BUSINESS OCCUPANCY, REQUIRED OPENING PROTECTIVES. 2017
 FBC-B TABLE 716.5.
  
 3-7) COMPLIED.
  
 8) NEW COMMENT, PLEASE REFER TO THE PLUMBING PLAN
 REVIEWERS COMMENTS CONCERNING THE MISSING DRINKING
 FOUNTAINS 2017 FBC-ACCESS. CODE 211.2 AND SECTIONS 603,
 604 CONCERNING WATER CLOSET ROOMS, THE PLANS DO NOT
 SHOW A FLOOR LAYOUT DETAIL AND ELEVATIONS WITH REQUIRED
 DIMENSIONS.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 12:16 Rev Time  
Received By jwitmer Date 2019-07-08 Time   Sent To  
Notes
2019-07-08 12:15:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061087
 ADD: 950 EVERNIA ST. 1ST FLOOR.
 CONT: NKT CONSTRUCTION SERVICES.
 TEL: 561-662-8150
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 08/2019
 ACTION: DENIED
  
 1) THE COVERSHEET C-1 DETAIL A HAS A SECTION THROUGH A
 BLOCK WALL FOR A NEW DOORWAY. SHEET 02 THE PROPOSED
 FLOOR PLAN DOES NOT INDICATE WHERE THE NEW DOORWAYS ARE
 BEING CUT THROUGH WHICH BLOCK WALLS? ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.2. THE ORIGINAL PERMIT
 02090419 SHOWS THE ORIGINAL BLOCK WALLS AND DOOR
 OPENINGS. PLEASE PUT SECTION MARKS THROUGH THE NEW DOOR
 WAY FROM THE GARAGE TO THE BUSINESS OCCUPANCY AND THE
 ELEVATOR LOBBY AND NEW DOORWAY INTO THE BUSINESS
 OCCUPANCY.
  
 2) THE NEW DOORWAYS ELEVATOR LOBBY AND THE GARAGE WALL
 TO BUSINESS OCCUPANCY ARE PENETRATING FIRE RATED WALLS,
 PLEASE IDENTIFY THE FIRE RATING OF THE REQUIRED OPENING
 PROTECTIVES. 2017 FBC-B 716.5.
  
 3) THE DOOR SCHEDULE ON SHEET 02 INDICATES A DOOR MARK
 # 1 AS A 2FOOT 8 INCH DOOR. PLEASE REVIEW THE CLEAR
 WIDTH REQUIREMENTS FOR DOORWAYS:
  
 2017 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 2017 FBC-B 1010.1.1 SIZE OF DOORS. THE REQUIRED
 CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR
 THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM
 CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES.
  
 4) SHEET 02 INDICATES THE SQUARE FOOTAGE FOR THIS
 TENANT SPACE IS 3845 SQ. FT. THE 2017 FBC-B TABLE
 1004.1.2 FOR BUSINESS OCCUPANCY IS 100 GROSS WHICH WILL
 GIVE YOU 39 OCCUPANTS. FBC-B TABLE 2902.1 WILL REQUIRE
 2 RESTROOMS.
  
 5) THE SHEET 02 THE FLOOR PLAN DOES NOT GIVE A CLEAR
 USE OF THE 2 LARGE ROOMS, THERE IS NO FURNITURE LAYOUT
 TO SEE IF THE USE WILL BE GROUP THERAPY IN BOTH OR
 EITHER ROOM. THE CONCERN IS A OCCUPANT LOAD OF 50 OR
 MORE WHICH WILL BE THEN CONSIDERED AN ASSEMBLY
 OCCUPANCY AND MIXED USE BUILDING. TABLE 508.4. PLEASE
 PROVIDE A FURNITURE LAYOUT FOR THE USE OF THE ROOMS.
 PLEASE ALSO PROVIDE THE FURNITURE LAYOUT FOR THE
 EXAMINATION ROOMS.
  
 6) THE COVERSHEET INDICATES WITH NOTE 28 PRODUCT
 APPROVALS WILL BE REQUIRED FOR THE NEW GARAGE DOOR TO
 INTAKE ROOM. 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 7) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By jleahy Date 2019-10-08 Time 08:02 Rev Time 0.00
Received By jleahy Date 2019-10-08 Time 08:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By jleahy Date 2019-07-17 Time 15:50 Rev Time 0.00
Received By jleahy Date 2019-07-17 Time 15:50 Sent To  
Notes
2019-07-17 15:53:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 LOAD CALCULATION FOR THE SPACE MISSING THE LIGHTING
 LOADS.
  
 NEED FAULT CURRENT CALCULATION FOR 400A WITH NEW LOADS
 ADDED.
  
 RISER SHOWS A 200 AMPERE METERCAN ON A 400A SERVICE.
  
 EXAM ROOMS WHAT KIND OF EXAMS, DO YOU ADMINISTER ANY
 MEDICATION OR USE MEDICAL EQUIPMENT?

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-12-16 Cont ID  
Sent By pleduc Date 2019-12-16 Time   Rev Time 0.00
Received By pleduc Date 2019-12-16 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-11-18 Cont ID  
Sent By pleduc Date 2019-11-18 Time   Rev Time 0.00
Received By pleduc Date 2019-11-18 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-01 Cont ID  
Sent By pleduc Date 2019-10-01 Time   Rev Time 0.00
Received By pleduc Date 2019-10-01 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By pleduc Date 2019-06-25 Time   Rev Time 0.00
Received By pleduc Date 2019-06-25 Time 13:53 Sent To  
Notes
2019-06-25 14:41:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET O2 - THERE ARE INDICATIONS OF FIRE SPRINKLER
 HEAD LOCATIONS; HOWEVER, SOME LOCATIONS DO NOT APPEAR
 TO BE CODE COMPLIANT.
  
 ADDITIONALLY, THERE ARE NO INDICATIONS OF THE POSITION
 OF EXISTING HEADS VS INSTALLED HEADS. I.E UPRIGHT VS
 PENDANT.
  
 PLEASE PROVIDE DETAILS.
  
 FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE.
  
  
  
 2) SHEET E 1 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES EXISTING NOR PROPOSED.
  
 PLEASE PROVIDE DETAILS.
  
 FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE.
  
  
  
 3) SHEET M 1 - THERE ARE INDICATIONS OF A/C UNITS WITH
 OVER 2,000 CFM WITH NO DUCT DETECTORS INDICATED THAT
 ARE REQUIRED TO BE TIED INTO THE FIRE ALARM SYSTEM.
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 PLEASE REVIEW AND PROVIDE DESIGN DETAIL AND AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT OR JUSTIFY WHY NOT
 WITH SPECIFIC NARRATIVE AND CODE REFERENCES.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-12-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-11 Time 14:52 Sent To  
Notes
2019-12-12 14:52:25B28

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-20 Cont ID  
Sent By gjohnson Date 2019-11-20 Time 11:35 Rev Time 0.00
Received By gjohnson Date 2019-11-04 Time 11:07 Sent To  
Notes
2019-11-05 11:08:05B05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-24 Cont ID  
Sent By cpuell Date 2019-10-24 Time 10:15 Rev Time 0.00
Received By cpuell Date 2019-09-26 Time 14:12 Sent To  
Notes
2019-09-27 14:12:16B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By jleahy Date 2019-07-17 Time 15:53 Rev Time 0.00
Received By jleahy Date 2019-06-21 Time 14:26 Sent To  
Notes
2019-06-24 14:26:52B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 12:16 Rev Time  
Received By jwitmer Date 2019-07-08 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-12-30 Cont ID  
Sent By ccole Date 2019-12-30 Time 16:21 Rev Time 0.00
Received By ccole Date 2019-12-30 Time 16:08 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-11-15 Cont ID  
Sent By ccole Date 2019-11-15 Time 16:49 Rev Time 0.00
Received By ccole Date 2019-11-15 Time 14:29 Sent To  
Notes
2019-11-15 17:00:242ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19061087
 11/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE COMMENTS FROM THE 1ST AND 2ND REVIEW PRINTED BELOW
 ARE STILL COMPLETELY ADDRESSED.
  
 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE
 OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS
 CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE
 NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE
 INDICATING- SEE TABLE 403.3.1.1 FBC M.
 THE LARGE OPEN SPACE IS LISTED AS A LOBBY HOWEVER THE
 ARCHITECTURAL PLANS APPEAR TO INDICATE A MULTI-PURPOSE
 ROOM OR RECEPTION AREA. RECEPTION AREAS ARE CALCULATED
 AT 30 PERSONS PER 1000 SQ. FT. + 0.06 CFMS PER SQ. FT.
 PLEASE CORRECT THE CALCULATIONS.
  
 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE
 LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE
 AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION
 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE
 SUPPLY SYSTEMS.
 DUCT SMOKE DETECTORS ARE REQUIRED IN THE "SUPPLY
 SYSTEMS" OF EACH AIR HANDLER. THE CORRECTED PLAN IS
 SHOWING THEM IN THE "RETURN PLENUMS" OF THE AIR
 HANDLERS. ALSO THERE ARE NOTES INDICATING THEY ARE TO
 BE LOCATED IN THE AC COMPRESSORS, WHICH IS NOT A
 REQUIRED LOCATION. PLEASE CONSULT WITH THE MANUFACTURER
 BECAUSE THE INSTALLATION MAY NOT COMPLY WITH
 INSTALLATION GUIDELINES AND MAY VOID THE WARRANTIES.
  
 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE
 PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS
 DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE
 EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING
 LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE
 OVERSIZED- SEE SECTION C403.2.2 FBC EC.
 AS NOTED ABOVE NO INTERNAL LOADS HAVE BEEN CALCULATED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-10-03 Cont ID  
Sent By ccole Date 2019-10-03 Time 08:30 Rev Time 0.00
Received By ccole Date 2019-10-02 Time 15:18 Sent To  
Notes
2019-10-03 08:44:512ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19061087
 10/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE
 OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS
 CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE
 NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE
 INDICATING- SEE TABLE 403.3.1.1 FBC M.
  
 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE
 LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE
 AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION
 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE
 SUPPLY SYSTEMS.
  
 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE
 PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS
 DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE
 EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING
 LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE
 OVERSIZED- SEE SECTION C403.2.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By ccole Date 2019-07-16 Time 16:01 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 13:56 Sent To  
Notes
2019-07-16 16:09:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19061087
 9/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE VENTILATION CALCULATIONS ARE
 INDICATING OFFICE SPACES, HOWEVER THE LARGE OPEN SPACE
 IS IDENTIFED AS A "FUTURE TENANT SPACE". PLEASE SEE THE
 BUILDING REVIEW COMMENTS AND PROVIDE THE CORRECT
 IDENTIFICATION AND USE OF THIS SPACE IN ORDER TO
 PROVIDE ADEQUATE VENTILATION PER TABLE 403.3.1.1 FBC M.
  
 2) M-1: PROVIDE SYMBOLS TO INDICATE THE LOCATIONS OF
 THE REQUIRED DUCT SMOKE DETECTORS IN THE AIR HANDLER
 SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION 606.2.1 FBC M.
  
 3) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS- SECTION 307.2.1 FBC M.
  
 4) SHOW THE LOCATIONS OF THE AC CONDENSERS AND PROVIDE
 ENGINEERED INSTALLATION DETAILS- SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-12-30 Cont ID  
Sent By gjohnson Date 2019-12-30 Time 15:43 Rev Time 0.00
Received By gjohnson Date 2019-12-30 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-11-20 Cont ID  
Sent By gjohnson Date 2019-11-20 Time 11:34 Rev Time 0.00
Received By gjohnson Date 2019-11-19 Time 18:33 Sent To  
Notes
2019-11-19 18:54:243RD REVIEW 19061087
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED PREVIOUS COMMENTS NOT
 COMPLIED WITH FROM 1ST REVIEW.
  
 1.DRINKING FOUNTAIN SHALL COMPLY WITH FBC PL 410.3 AND
 FBC ACC SECTIONS 602 AND 306. PER WPB 107.2.1, PROVIDE
 DETAIL SHOWING COMPLIANCE. SOME OF THIS INFORMATION HAS
 BEEN PREVIOUSLY REQUESTED AND HAS NOT BEEN RESPONDED
 TO. THE WATER FOUNTAIN HAS BEEN ADDED TO THE SCOPE OF
 THE PROJECTED PLEASE ADD THE FOLLOWING DETAIL TO SHOW
 COMPLIANCE WITH FBC ACC 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.2 CLEAR FLOOR SPACE. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 5.SECOND REQUEST: FBC ACC 604.5.2 -THE REAR WALL GRAB
 BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE. THE 36" BAR
 IS SHOWN WITH 6" FROM END OF THE BAR TO THE WALL THIS
 DOES NOT SHOW COMPLIANCE WITH FBC ACC 604.5.2 -THE REAR
 WALL GRAB BAR SHALL EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 PREVIOUS COMMENTS NOT COMPLIED WITH FROM 2ND REVIEW.
 1. THE TOILET PAPER DISPENSER IS SHOWN AT 36" OFF THE
 BACK WALL THIS DOES NOT COMPLY WITH FBC ACC 604.7,
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 6.PER FBC PL 607.1, HOT WATER IS REQUIRED TO THE
 SERVICE SINK.IT HAS NOT BEEN SHOWN ON WATER ISOMETRIC.
 IF YOUR USING A TANKLESS WATER HEATER WITH AN INTEGRAL
 TEMPERATURE LIMITING DEVISE FOR TEMPERED WATER TO THE
 LAVATORIES YOU CAN NOT USE THE SAME TANKLESS HEATER FOR
 THE HOT WATER REQUIRED AT THE SERVICE SINK THE
 TEMPERATURE FOR HOT WATER IS HIGH THAN THAT OF TEMPERED
 WATER. IN ORDER FOR THIS TO BE CODE COMPLIANT IT WILL
 BE REQUIRED THAT YOU USE TWO DIFFERENT WATER HEATERS OR
 A SINGLE WATER HEATER WITH AN OUTLET TEMPERATURE OF
 OVER 110 DEG. AND TEMPERING EACH LAVATORY TO A
 TEMPERATURE BELOW 110DEG AND SUPPLING HOT WATER OVER
 110 DEG. TO THE SERVICE SINK. PER FBC PL 607.1 AND
 416.5
  
 7.WATER DISTRIBUTION FLOOR PLAN AND RISER DIAGRAM DO
 NOT MATCH. PER WPB FBC 107.2.1, CLARIFY. THE FLOOR PLAN
 SHOWS SEPARATE BRANCHES FOR THE COLD WATER FOR THE
 WATER FOUNTAIN, LAVATORY SINK AND SERVICE SINK THE
 ISOMETRIC SHOWS A SINGLE BRANCH OFF THE MAIN TO ALL
 FIXTURES.
  
 8. THE SANITARY ISOMETRIC DRAWING DOES NOT MATCH THE
 FLOOR PLAN THE SANITARY ISOMETRIC SHOWS A SINGLE BRANCH
 OFF THE MAIN BUILDING DRAIN THE FLOOR PLAN SHOWS
 SEPARATE BRANCHES FOR EACH FIXTURE AND BATHROOM
 GROUP.PER WPB FBC 107.2.1, CLARIFY
  
 9.PER FBC PL (E)607.5, PROVIDE INSULATION FOR THE HOT
 WATER. PROVIDE SPECIFICATION PER WPB FBC 107.2.1.
  
  
 NEW COMMENTS:
  
 1. ON THE WATER ISOMETRIC DRAWING THERE IS THE
 FOLLOWING VIOLATIONS.
 A) THE HOT IS SHOWN ON THE RIGHT SIDE OF THE LAVATORY'S
 AND COLD ON THE LEFT IT NEEDS TO BE REVERSED.PER FBC PL
 607.4
 B) THE SUPPLY TO THE WC IS SHOWN AS HOT IT SHALL BE
 SHOWN AS COLD AND A SEPARATE BRANCH FOR TEMPERED WATER
 TO THE LAVATORY. PER WPB AMEND TO FBC 107.2.1
 C) THE HOT SUPPLY FOR THE SERVICE SINK IS MISSING. PER
 FBC PL 607.1
 D) THE SIZE OF THE OF THE MAIN FEED TO THIS UNIT AT
 1/2" APPEARS TO BE UNDERSIZED THE MINIMUM WATER SERVICE
 IS 3/4" THOUGH THIS IS NOT A SEPARATE STRUCTURE THE
 SAME PRINCIPAL APPLIES. APPENDIX E IN THE PLUMBING CODE
 IS NOT ENFORCEABLE BUT IS A GOOD SIZING METHOD, PLEASE
 PROVIDE THE SIZING CALCULATION THAT WERE USED TO
 DETERMINE PIPE SIZING ON THIS PROJECT. PER AMEND TO FBC
 107.2.1
 E) A VALVE IS REQUIRED ON THE COLD WATER DROP FROM MAIN
 LINE AND AT THE WATER HEATER AND EACH FIXTURE. PER FBC
 PL 606.1(5)(8), 606.2(1)
  
 2. SHOW COMPLIANCE OR PROVIDE NOT ON PLAN. 606.3 ACCESS
 TO VALVES. ACCESS SHALL BE PROVIDED TO ALL FULL-OPEN
 VALVES AND SHUTOFF VALVES.
  
 3.PROVIDE SPECIFICATIONS AND INSTILLATION GUIDE FOR
 TANKLESS HEATER. MANUFACTURE SPECIFICATION SHALL SHOW
 SIZE OF WATER HEATER IS APPROVED FOR THE DEMAND OF ALL
 PLUMBING FIXTURE. PER WPB FBC 107.2.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-10-03 Cont ID  
Sent By jesmith Date 2019-10-03 Time 14:24 Rev Time 0.00
Received By jesmith Date 2019-10-03 Time 14:23 Sent To  
Notes
2019-10-03 14:24:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1.DRINKING FOUNTAIN SHALL COMPLY WITH FBC PL 410.3 AND
 FBC ACC SECTIONS 602 AND 306. PER WPB 107.2.1, PROVIDE
 DETAIL SHOWING COMPLIANCE. SOME OF THIS INFORMATION HAS
 BEEN PREVIOUSLY REQUESTED AND HAS NOT BEEN RESPONDED
 TO.
 2.SECOND REQUEST: FBC ACC 604.2 -THE WATER CLOSET SHALL
 BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND
 TO ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL
 BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION. PER WPB FBC 107.2.1. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE.
 3.SECOND REQUEST: FBC ACC 604.4 -THE SEAT HEIGHT OF A
 WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES
 MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF
 THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A
 LIFTED POSITION. PER WPB FBC 107.2.1. PER WPB 107.2.1,
 PROVIDE DETAIL SHOWING COMPLIANCE.
 4.SECOND REQUEST: FBC ACC 604.5.1 -THE SIDE WALL GRAB
 BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL. PER WPB 107.2.1, PROVIDE
 DETAIL SHOWING COMPLIANCE.
 5.SECOND REQUEST: FBC ACC 604.5.2 -THE REAR WALL GRAB
 BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE.
 6.SECOND REQUEST: FBC ACC 609.4 -GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER WPB 107.2.1,
 PROVIDE DETAIL SHOWING COMPLIANCE.
 7.SECOND REQUEST: 606.2 -A CLEAR FLOOR SPACE FOR THE
 LAVATORIES COMPLYING WITH 305, POSITIONED FOR A FORWARD
 APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED. PER WPB FBC 107.2.1, REVISE DRAWING
 TO SHOW COMPLIANCE.
 8.SECOND REQUEST: 606.3 -LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER WPB 107.2.1, PROVIDE DETAIL
 SHOWING COMPLIANCE. ADDITIONALLY SHOW COMPLIANCE WITH
 FBC ACC SECTION 306.
 9.SECOND REQUEST: 603.3 -MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE.
  
 ADDITIONAL COMMENTS:
 1.PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES (380 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM
 ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND
 GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE THAT
 CONTROLS DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS
 PAPER FLOW. PER WPB 107.2.1, PROVIDE DETAIL SHOWING
 COMPLIANCE.
 2.PER FBC ACC 604.6, FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS
 SHALL COMPLY WITH 309. FLUSH CONTROLS SHALL BE LOCATED
 ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN
 AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH
 604.8.2. PER WPB 107.2.1, PROVIDE DETAIL SHOWING
 COMPLIANCE.
 3.PER FBC ACC 604.8.1.1, TOILET COMPARTMENT DOORS,
 INCLUDING DOOR HARDWARE, SHALL COMPLY WITH 404 EXCEPT
 THAT IF THE APPROACH IS TO THE LATCH SIDE OF THE
 COMPARTMENT DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF
 THE COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. DOORS SHALL BE LOCATED IN THE FRONT
 PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST
 FROM THE WATER CLOSET. WHERE LOCATED IN THE FRONT
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE SIDE WALL OR PARTITION FARTHEST FROM
 THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL OR
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE FRONT PARTITION. THE DOOR SHALL BE
 SELF-CLOSING. A DOOR PULL COMPLYING WITH 404.2.7 SHALL
 BE PLACED ON BOTH SIDES OF THE DOOR NEAR THE LATCH.
 TOILET COMPARTMENT DOORS SHALL NOT SWING INTO THE
 MINIMUM REQUIRED COMPARTMENT AREA. SEE ALSO FBC ACC
 604.8.1.7 AND ADVISORY 604.8.1.6 AND 604.8.1.7. PER WPB
 FBC 107.2.1, REVISE DRAWING TO SHOW COMPLIANCE.
 4.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 SCHEDULE WITH FIXTURE SPEC AND WATER USAGE
 REQUIREMENTS.
 5.PER WPB FBC 107.2.1, PROVIDE A WATER HEATER EQUIPMENT
 SCHEDULE SPECIFYING UNIT(S), GPM AND ELECTRICAL
 CHARACTERISTICS.
 6.PER FBC PL 607.1, HOT WATER IS REQUIRED TO THE
 SERVICE SINK.
 7.WATER DISTRIBUTION FLOOR PLAN AND RISER DIAGRAM DO
 NOT MATCH. PER WPB FBC 107.2.1, CLARIFY.
 8.SANITARY PIPING FLOOR PLAN AND RISER DIAGRAM DO NOT
 MATCH. PER WPB FBC 107.2.1, CLARIFY.
 9.PER FBC PL (E)607.5, PROVIDE INSULATION FOR THE HOT
 WATER. PROVIDE SPECIFICATION PER WPB FBC 107.2.1.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19061087 950 EVERNIA ST
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By gjohnson Date 2019-07-10 Time 13:37 Rev Time 0.00
Received By gjohnson Date 2019-07-10 Time 13:37 Sent To  
Notes
2019-07-10 13:39:051ST REVIEW: 19061087
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 ACCESSIBILITY REQUIREMENTS FBC ACC 2017 6TH EDITION
  
 602 DRINKING FOUNTAINS
 A)602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR
 FLOOR OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR
 A FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 B)602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 C)602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 604 WATER CLOSETS AND TOILET COMPARTMENTS
 A)604.2 LOCATION. THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 B)604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 C)604.3.2 OVERLAP.THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
 D)604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION
 604.5 GRAB BARS.
 A)604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
 B)604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
 C)609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
 606 LAVATORIES
 A)606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 B)606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
  
 2.TWO BATHROOMS ARE REQUIRED PER FBC PL 403.2 SEPARATE
 FACILITIES. WHERE PLUMBING FIXTURES ARE REQUIRED,
 SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 3. A DRINKING FOUNTAIN IS REQUIRED AND SHALL COMPLY
 WITH ACCESSIBILITY. PER FBC PL TABLE 403.1
  
 4. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 5. SHT. P-1 THE SANITARY ISOMETRIC DRAWING SHOWS A VENT
 CONNECTED TO THE TOP OF THE TOILET THIS IS NOT AN
 APPROVED VENTING METHOD PLEASE REMOVE, THE VENT FROM
 THE LAVATORY SHALL VENT THE TOILETS PER FBC PL 912.1
  
 6.TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 7. SHT. LS-1 AND M-1 IS SHOWING A PARTION AND WALL HUNG
 SINK NEXT TO THE TOILET THE RST OF THE PLAN DOES NOT
 SHOW THIS PLEASE CLARIFY
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By aaponte Date 2019-10-23 Time 16:27 Rev Time 0.00
Received By aaponte Date 2019-10-23 Time 16:24 Sent To  
Notes
2019-10-23 16:27:24PROVISO: CALSS B SPECIAL USE CONDITIONS SHALL BE MET.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-12 Cont ID  
Sent By aaponte Date 2019-07-12 Time 16:25 Rev Time 0.00
Received By aaponte Date 2019-07-12 Time 16:25 Sent To  
Notes
2019-07-12 16:26:00PROVISO: CLASS B SPECIAL USE PERMIT CONDITIONS SHALL BE
 MET BEFORE FINAL CO


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved