| 2019-09-09 06:07:10 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19061078 |
| | ADD: 5800 CORPORATE WAY |
| | CONT: GEN-X CONSTRUCTION, INC. |
| | TEL: 561-963-4490 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SUN. SEPT. 08/2019 |
| | ACTION: DENIED |
| | |
| | 1A) SEMI-COMPLIED. THE BUILDING IN QUESTION BEING |
| | LOCATED IN A FLOOD ZONE AE IS THE MODULAR BUILDING. |
| | THE NEW SURVEY THAT WAS SUBMITTED FOR THIS REVIEW IS IN |
| | NAVD 88 WITH A FINISH FLOOR OF 13.89 FT. NAVD88, WHICH |
| | IS APPROXIMATELY 1 13/16TH OF AN INCH BELOW THE |
| | REQUIRED 2 FEET FREEBOARD. |
| | |
| | THE PROPOSED IMPROVEMENT ($138,917 PLUS $448,181.00 |
| | DOLLARS, OF LAST 5 YEARS OF IMPROVEMENTS) APPEARS TO BE |
| | A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH |
| | COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE |
| | STRUCTURE ($704,160.00). IF THIS IS A SUBSTANTIAL |
| | IMPROVEMENT. THE STRUCTURE IS TO BE BROUGHT INTO |
| | COMPLIANCE (BFE 14.0 FT. NAVD88 FOR THE LOWEST FINISHED |
| | FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT CAN |
| | PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE |
| | PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL |
| | BULLETIN 758 SECTION 4.5: |
| | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 |
| | 5045-2915/P_758_COMPLETE_R3.PDF |
| | |
| | IMPORTANT!!!!!!! PLEASE NOTE THE VALUE OF THE |
| | STRUCTURES FROM THE PROPERTY APPRAISER?S OFFICE IS FOR |
| | BOTH BUILDINGS AND THE MAJORITY OF THE LAST 5 YEARS |
| | WORK IS ON THE LARGER BUILDING WHICH IS OUT OF THE |
| | FLOOD ZONE. WHAT WE NEED IS THE VALUE OF THE WORK |
| | COMPLETED ON THE MAIN BUILDING AND A VALUE OF WORK |
| | COMPLETED ON THE ANNEXED MANUFACTURED BUILDING AND AN |
| | ASSESSED VALUE FOR THE ANNEXED BUILDING AND MAIN |
| | BUILDING TO SEE IF ON THE ANNEXED BUILDING, THE VALUE |
| | OF THE WORK COMPLETED AND NEW WORK IS GOING TO STILL BE |
| | CONSIDERED SUBSTANTIAL IMPROVEMENT. THIS IS A CRITICAL |
| | PROCESS TO SEE IF THE ANNEXED MANUFACTURED BUILDING |
| | WOULD STILL BE CONSIDERED SUBSTANTIAL IMPROVEMENT AND |
| | HAVE TO BE RAISED OR NOT MEET THE 50 % OF THE VALUE OF |
| | THE STRUCTURE AND NOT BE CONSIDERED A SUBSTANTIAL |
| | IMPROVEMENT AND STAY AT THE SAME HEIGHT. YOU CAN GET A |
| | CERTIFIED APPRAISAL THAT MAY HELP INCREASE THE VALUE OF |
| | THE MANUFACTURERED BUILDING FOR THE BUILDING OFFICIAL |
| | TO REVIEW AND APPROVE. |
| | |
| | 1B) THE SITE PLAN SHOWS A NEW 4 X 5 FOOT MONOLITHIC A/C |
| | COMPRESSOR PAD ON THE GROUND. PLEASE NOTE THIS PAD |
| | SHOULD BE ELEVATED TO THE 14.00 FT. + TO BE ABOVE THE |
| | BASE FLOOD AND 2 FEET FREEBOARD. NEW CONSTRUCTION. |
| | |
| | 1C) SHEET M2 ALSO HAS A NOTE ABOUT THE NEW A/C |
| | COMPRESSOR PAD. NOTE # 4 STATES THAT IT SHOULD BE ABOVE |
| | THE 100 YEAR FLOOD PLAIN. PLEASE NOTE THE NEW PROPOSED |
| | PAD SHOULD ALSO INCLUDE THE 2 ADDITIONAL FEET OF |
| | ELEVATION TO 14.00 FEET NAVD88 TO MEET THE CITIES |
| | FREEBOARD REQUIREMENT. |
| | |
| | 1ST ROUND COMMENT. THE SITE PLAN CREATED BY ARCHITECT |
| | JEFFREY ORNSTEIN IDENTIFIES THE BUILDING FOR THE |
| | PROPOSED PERMITTED WORK AS ANNEX SUBJECT ONE STORY |
| | BUILDING WITH A FINISH FLOOR ELEVATION 15.5 FEET. |
| | PLEASE PROVIDE A CURRENT SURVEY FOR THIS BUILDING IN |
| | NAVD 88. THIS BUILDING IS IN AN AE FLOOD ZONE WITH A |
| | BFE OF 12.0 FEET NAVD88. |
| | THE CITY HAS GONE THROUGH A SERIES OF FREEBOARD CHANGES |
| | TO KEEP UP WITH THE FBC-BUILDING CODE PLUS INCREASE OUR |
| | FREEBOARD TO 2 FEET ABOVE THE BASE FLOOD. |
| | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & |
| | CONTROL |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE |
| | AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF |
| | PERMIT APPLICATION AFTER SEPT. 12/2016, |
| | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| | |
| | THE PROPOSED IMPROVEMENT ($138,917 PLUS $448,181.00 |
| | DOLLARS, OF LAST 5 YEARS OF IMPROVEMENTS) APPEARS TO BE |
| | A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH |
| | COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE |
| | STRUCTURE ($704,160.00). IF THIS IS A SUBSTANTIAL |
| | IMPROVEMENT. THE STRUCTURE IS TO BE BROUGHT INTO |
| | COMPLIANCE (BFE 14.0? NAVD88 FOR THE LOWEST FINISHED |
| | FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT CAN |
| | PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE |
| | PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL |
| | BULLETIN 758 SECTION 4.5: |
| | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 |
| | 5045-2915/P_758_COMPLETE_R3.PDF |
| | |
| | PLEASE NOTE THE VALUE OF THE STRUCTURES FROM THE |
| | PROPERTY APPRAISER?S OFFICE IS FOR BOTH BUILDINGS AND |
| | THE MAJORITY OF THE LAST 5 YEARS IS ON THE LARGER |
| | BUILDING WHICH IS OUT OF THE FLOOD ZONE. WHAT WE NEED |
| | IS THE ASSESSED VALUE FOR THE ANNEXED BUILDING PLUS A |
| | NEW SURVEY IN NAVD88 TO DETERMINE IF THIS BUILDING |
| | COMPLIES WITH THE FEMA REGULATIONS. SINCE THE ANNEXED |
| | BUILDING IS IN AN AE FLOOD ZONE WITH A BFE OF 12.0 FT. |
| | NAVD 88 A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | |
| | 2-3) COMPLIED. |
| | |
| | 4)SEMI-COMPLIED. 2017 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | |
| | (31)(A) EXTERIOR DOOR. COMPLIED. NOA 14-0513.03 NOT |
| | REVIEWED BY THE DESIGNER OF RECORD. |
| | (B) WINDOWS , MULLIONS, NO WINDOW REPORT SUBMITTED 2ND |
| | REVIEW. NOA 17-0630.08 |
| | (MULLIONS) NONE FOR THIS PROJECT, REVIEWED BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 5) SEMI-COMPLIED, NEED WINDOW PRODUCT APPROVAL. W. P. |
| | B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6-8) COMPLIED. |
| | |
| | 9) SEMI-COMPLIED. I APOLOGIZE FOR NOT GIVING THE OTHER |
| | CODE REFERENCE FOR WORK SURFACES. WE USUALLY SEE THE |
| | WHOLE COUNTER GO TO 34 INCHES IN HEIGHT. PLEASE REFER |
| | TO: 2017 FBC-ACCESSIBILITY CODE SECTION: |
| | WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK SURFACES |
| | SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | ADVISORY 226.1. |
| | IN FACILITIES COVERED BY THE ADA, THIS REQUIREMENT DOES |
| | NOT APPLY TO WORK SURFACES USED ONLY BY EMPLOYEES. |
| | HOWEVER, THE ADA AND, WHERE APPLICABLE, SECTION 504 OF |
| | THE REHABILITATION ACT OF 1973, AS AMENDED, PROVIDE |
| | THAT EMPLOYEES ARE ENTITLED TO ?REASONABLE |
| | ACCOMMODATIONS.? WITH RESPECT TO WORK SURFACES, THIS |
| | MEANS THAT EMPLOYERS MAY NEED TO PROCURE OR ADJUST WORK |
| | STATIONS SUCH AS DESKS, LABORATORY AND WORK BENCHES, |
| | FUME HOODS, RECEPTION COUNTERS, TELLER WINDOWS, STUDY |
| | CARRELS, COMMERCIAL KITCHEN COUNTERS, AND CONFERENCE |
| | TABLES TO ACCOMMODATE THE INDIVIDUAL NEEDS OF EMPLOYEES |
| | WITH DISABILITIES ON AN ?AS NEEDED? BASIS. CONSIDER |
| | WORK SURFACES THAT ARE FLEXIBLE AND PERMIT INSTALLATION |
| | AT VARIABLE HEIGHTS AND CLEARANCES. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET 02 LOUNGE AREA DETAIL |
| | SHOWS THE TOP OF THE CABINETS AT 36 INCHES IN HEIGHT. |
| | PLEASE SHOW COMPLIANCE WITH 2017 ACCESS. CODE SECTION |
| | SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 |
| | HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |