Plan Review Details - Permit 19061078
Plan Review Stops For Permit 19061078
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-10-22 Cont ID  
Sent By pvalenti Date 2019-10-22 Time 08:07 Rev Time 0.00
Received By pvalenti Date 2019-10-17 Time 10:04 Sent To  
Notes
2019-10-22 09:54:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD BUILDING REVIEW DENIED:
  
 1A) FAILED: FEMA TECHNICAL BULLETIN 2; THE NEW FINISH
 FLOOR ELEVATION DETAIL INDICATES 14' 1/4" AT TOP OF
 SUB-FLOOR. THIS ELEVATION IS NOT ACCEPTABLE DUE TO THE
 FLOOR FRAMING NOT MEETING THE REQUIREMENTS OF FLOOD
 DAMAGE-RESISTANT MATERIALS. A NEW ELEVATION CERTIFICATE
 WILL HAVE TO BE SUBMITTED IF ELEVATIONS ARE ADJUSTED.
 1B) FAILED: FBC B 107.2.1 PROVIDE ANCHORING DETAILS FOR
 THE EXTERIOR A/C RACKS (MEETING 14.00' ELEVATION
 REQUIREMENT). THE NEW ELEVATION CERTIFICATE (SECTION
 C2-E) WILL HAVE TO INCLUDE ELEVATION OF EQUIPMENT.
 2.) APPROVED.
 3.) APPROVED.
 4.) APPROVED.
 5.) APPROVED.
 6.) APPROVED.
 7.) APPROVED.
 8.) APPROVED.
 9.) APPROVED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-09 Cont ID  
Sent By jwitmer Date 2019-09-09 Time 06:07 Rev Time 0.00
Received By jwitmer Date 2019-09-07 Time 09:41 Sent To  
Notes
2019-09-09 06:07:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061078
 ADD: 5800 CORPORATE WAY
 CONT: GEN-X CONSTRUCTION, INC.
 TEL: 561-963-4490
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. SEPT. 08/2019
 ACTION: DENIED
  
 1A) SEMI-COMPLIED. THE BUILDING IN QUESTION BEING
 LOCATED IN A FLOOD ZONE AE IS THE MODULAR BUILDING.
 THE NEW SURVEY THAT WAS SUBMITTED FOR THIS REVIEW IS IN
 NAVD 88 WITH A FINISH FLOOR OF 13.89 FT. NAVD88, WHICH
 IS APPROXIMATELY 1 13/16TH OF AN INCH BELOW THE
 REQUIRED 2 FEET FREEBOARD.
  
 THE PROPOSED IMPROVEMENT ($138,917 PLUS $448,181.00
 DOLLARS, OF LAST 5 YEARS OF IMPROVEMENTS) APPEARS TO BE
 A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE
 STRUCTURE ($704,160.00). IF THIS IS A SUBSTANTIAL
 IMPROVEMENT. THE STRUCTURE IS TO BE BROUGHT INTO
 COMPLIANCE (BFE 14.0 FT. NAVD88 FOR THE LOWEST FINISHED
 FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT CAN
 PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE
 PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL
 BULLETIN 758 SECTION 4.5:
 HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2
 5045-2915/P_758_COMPLETE_R3.PDF
  
 IMPORTANT!!!!!!! PLEASE NOTE THE VALUE OF THE
 STRUCTURES FROM THE PROPERTY APPRAISER?S OFFICE IS FOR
 BOTH BUILDINGS AND THE MAJORITY OF THE LAST 5 YEARS
 WORK IS ON THE LARGER BUILDING WHICH IS OUT OF THE
 FLOOD ZONE. WHAT WE NEED IS THE VALUE OF THE WORK
 COMPLETED ON THE MAIN BUILDING AND A VALUE OF WORK
 COMPLETED ON THE ANNEXED MANUFACTURED BUILDING AND AN
 ASSESSED VALUE FOR THE ANNEXED BUILDING AND MAIN
 BUILDING TO SEE IF ON THE ANNEXED BUILDING, THE VALUE
 OF THE WORK COMPLETED AND NEW WORK IS GOING TO STILL BE
 CONSIDERED SUBSTANTIAL IMPROVEMENT. THIS IS A CRITICAL
 PROCESS TO SEE IF THE ANNEXED MANUFACTURED BUILDING
 WOULD STILL BE CONSIDERED SUBSTANTIAL IMPROVEMENT AND
 HAVE TO BE RAISED OR NOT MEET THE 50 % OF THE VALUE OF
 THE STRUCTURE AND NOT BE CONSIDERED A SUBSTANTIAL
 IMPROVEMENT AND STAY AT THE SAME HEIGHT. YOU CAN GET A
 CERTIFIED APPRAISAL THAT MAY HELP INCREASE THE VALUE OF
 THE MANUFACTURERED BUILDING FOR THE BUILDING OFFICIAL
 TO REVIEW AND APPROVE.
  
 1B) THE SITE PLAN SHOWS A NEW 4 X 5 FOOT MONOLITHIC A/C
 COMPRESSOR PAD ON THE GROUND. PLEASE NOTE THIS PAD
 SHOULD BE ELEVATED TO THE 14.00 FT. + TO BE ABOVE THE
 BASE FLOOD AND 2 FEET FREEBOARD. NEW CONSTRUCTION.
  
 1C) SHEET M2 ALSO HAS A NOTE ABOUT THE NEW A/C
 COMPRESSOR PAD. NOTE # 4 STATES THAT IT SHOULD BE ABOVE
 THE 100 YEAR FLOOD PLAIN. PLEASE NOTE THE NEW PROPOSED
 PAD SHOULD ALSO INCLUDE THE 2 ADDITIONAL FEET OF
 ELEVATION TO 14.00 FEET NAVD88 TO MEET THE CITIES
 FREEBOARD REQUIREMENT.
  
 1ST ROUND COMMENT. THE SITE PLAN CREATED BY ARCHITECT
 JEFFREY ORNSTEIN IDENTIFIES THE BUILDING FOR THE
 PROPOSED PERMITTED WORK AS ANNEX SUBJECT ONE STORY
 BUILDING WITH A FINISH FLOOR ELEVATION 15.5 FEET.
 PLEASE PROVIDE A CURRENT SURVEY FOR THIS BUILDING IN
 NAVD 88. THIS BUILDING IS IN AN AE FLOOD ZONE WITH A
 BFE OF 12.0 FEET NAVD88.
 THE CITY HAS GONE THROUGH A SERIES OF FREEBOARD CHANGES
 TO KEEP UP WITH THE FBC-BUILDING CODE PLUS INCREASE OUR
 FREEBOARD TO 2 FEET ABOVE THE BASE FLOOD.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 THE PROPOSED IMPROVEMENT ($138,917 PLUS $448,181.00
 DOLLARS, OF LAST 5 YEARS OF IMPROVEMENTS) APPEARS TO BE
 A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE
 STRUCTURE ($704,160.00). IF THIS IS A SUBSTANTIAL
 IMPROVEMENT. THE STRUCTURE IS TO BE BROUGHT INTO
 COMPLIANCE (BFE 14.0? NAVD88 FOR THE LOWEST FINISHED
 FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT CAN
 PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE
 PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL
 BULLETIN 758 SECTION 4.5:
 HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2
 5045-2915/P_758_COMPLETE_R3.PDF
  
 PLEASE NOTE THE VALUE OF THE STRUCTURES FROM THE
 PROPERTY APPRAISER?S OFFICE IS FOR BOTH BUILDINGS AND
 THE MAJORITY OF THE LAST 5 YEARS IS ON THE LARGER
 BUILDING WHICH IS OUT OF THE FLOOD ZONE. WHAT WE NEED
 IS THE ASSESSED VALUE FOR THE ANNEXED BUILDING PLUS A
 NEW SURVEY IN NAVD88 TO DETERMINE IF THIS BUILDING
 COMPLIES WITH THE FEMA REGULATIONS. SINCE THE ANNEXED
 BUILDING IS IN AN AE FLOOD ZONE WITH A BFE OF 12.0 FT.
 NAVD 88 A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 2-3) COMPLIED.
  
 4)SEMI-COMPLIED. 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
  
 (31)(A) EXTERIOR DOOR. COMPLIED. NOA 14-0513.03 NOT
 REVIEWED BY THE DESIGNER OF RECORD.
 (B) WINDOWS , MULLIONS, NO WINDOW REPORT SUBMITTED 2ND
 REVIEW. NOA 17-0630.08
 (MULLIONS) NONE FOR THIS PROJECT, REVIEWED BY THE
 DESIGNER OF RECORD.
  
 5) SEMI-COMPLIED, NEED WINDOW PRODUCT APPROVAL. W. P.
 B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6-8) COMPLIED.
  
 9) SEMI-COMPLIED. I APOLOGIZE FOR NOT GIVING THE OTHER
 CODE REFERENCE FOR WORK SURFACES. WE USUALLY SEE THE
 WHOLE COUNTER GO TO 34 INCHES IN HEIGHT. PLEASE REFER
 TO: 2017 FBC-ACCESSIBILITY CODE SECTION:
 WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK SURFACES
 SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 ADVISORY 226.1.
 IN FACILITIES COVERED BY THE ADA, THIS REQUIREMENT DOES
 NOT APPLY TO WORK SURFACES USED ONLY BY EMPLOYEES.
 HOWEVER, THE ADA AND, WHERE APPLICABLE, SECTION 504 OF
 THE REHABILITATION ACT OF 1973, AS AMENDED, PROVIDE
 THAT EMPLOYEES ARE ENTITLED TO ?REASONABLE
 ACCOMMODATIONS.? WITH RESPECT TO WORK SURFACES, THIS
 MEANS THAT EMPLOYERS MAY NEED TO PROCURE OR ADJUST WORK
 STATIONS SUCH AS DESKS, LABORATORY AND WORK BENCHES,
 FUME HOODS, RECEPTION COUNTERS, TELLER WINDOWS, STUDY
 CARRELS, COMMERCIAL KITCHEN COUNTERS, AND CONFERENCE
 TABLES TO ACCOMMODATE THE INDIVIDUAL NEEDS OF EMPLOYEES
 WITH DISABILITIES ON AN ?AS NEEDED? BASIS. CONSIDER
 WORK SURFACES THAT ARE FLEXIBLE AND PERMIT INSTALLATION
 AT VARIABLE HEIGHTS AND CLEARANCES.
  
 1ST ROUND OF COMMENTS. SHEET 02 LOUNGE AREA DETAIL
 SHOWS THE TOP OF THE CABINETS AT 36 INCHES IN HEIGHT.
 PLEASE SHOW COMPLIANCE WITH 2017 ACCESS. CODE SECTION
 SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2019-07-08 Time 15:58 Sent To  
Notes
2019-07-08 15:58:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061078
 ADD: 5800 CORPORATE WAY
 CONT: GEN-X CONSTRUCTION, INC.
 TEL: 561-963-4490
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 08/2019
 ACTION: DENIED
  
 1) THE SITE PLAN CREATED BY ARCHITECT JEFFREY ORNSTEIN
 IDENTIFIES THE BUILDING FOR THE PROPOSED PERMITTED WORK
 AS ANNEX SUBJECT ONE STORY BUILDING WITH A FINISH FLOOR
 ELEVATION 15.5 FEET. PLEASE PROVIDE A CURRENT SURVEY
 FOR THIS BUILDING IN NAVD 88. THIS BUILDING IS IN AN AE
 FLOOD ZONE WITH A BFE OF 12.0 FEET NAVD88.
 THE CITY HAS GONE THROUGH A SERIES OF FREEBOARD CHANGES
 TO KEEP UP WITH THE FBC-BUILDING CODE PLUS INCREASE OUR
 FREEBOARD TO 2 FEET ABOVE THE BASE FLOOD.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 THE PROPOSED IMPROVEMENT ($138,917 PLUS $448,181.00
 DOLLARS, OF LAST 5 YEARS OF IMPROVEMENTS ) APPEARS TO
 BE A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE
 STRUCTURE ($704,160.00). IF THIS IS A SUBSTANTIAL
 IMPROVEMENT. THE STRUCTURE IS TO BE BROUGHT INTO
 COMPLIANCE (BFE 14.0? NAVD88 FOR THE LOWEST FINISHED
 FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT CAN
 PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE
 PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL
 BULLETIN 758 SECTION 4.5:
 HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2
 5045-2915/P_758_COMPLETE_R3.PDF
  
 PLEASE NOTE THE VALUE OF THE STRUCTURES FROM THE
 PROPERTY APPRAISER?S OFFICE IS FOR BOTH BUILDINGS AND
 THE MAJORITY OF THE LAST 5 YEARS IS ON THE LARGER
 BUILDING WHICH IS OUT OF THE FLOOD ZONE. WHAT WE NEED
 IS THE ASSESSED VALUE FOR THE ANNEXED BUILDING PLUS A
 NEW SURVEY IN NAVD88 TO DETERMINE IF THIS BUILDING
 COMPLIES WITH THE FEMA REGULATIONS. SINCE THE ANNEXED
 BUILDING IS IN AN AE FLOOD ZONE WITH A BFE OF 12.0 FT.
 NAVD 88 A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 2) NEITHER SHEET 00 OR 01 INDICATE THE FOLLOWING
 MISSING INFORMATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 504.4 & TABLE 506.2).
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
  
 3) SHEET 01 INDICATES THE REPLACEMENT OF ALL WINDOWS
 AND DOORS BUT NO WIND DESIGN CRITERIA HAS BEEN GIVEN.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR NOA 14-0513.03 NOT REVIEWED BY THE
 DESIGNER OF RECORD.
 (B) WINDOWS NOA 17-0630.08 NOT REVIEWED BY THE DESIGNER
 OF RECORD.
  
 5) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8) SHEET 01 THE RESTROOM BACK WALL MEASUREMENT SHOWS 7
 FEET WHEREAS THE DETAIL OF THE RESTROOM SHOWS A
 BACKWALL MEASUREMENT OF 7 FEET 6 INCHES. DISCREPANCY IN
 PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) SHEET 02 LOUNGE AREA DETAIL SHOWS THE TOP OF THE
 CABINETS AT 36 INCHES IN HEIGHT. PLEASE SHOW COMPLIANCE
 WITH 2017 ACCESS. CODE SECTION SINKS. 2017
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By jpearson Date 2019-07-19 Time 08:42 Rev Time 0.00
Received By jpearson Date 2019-07-19 Time 08:42 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-10-15 Cont ID  
Sent By pleduc Date 2019-10-15 Time   Rev Time 0.00
Received By pleduc Date 2019-10-15 Time 13:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-22 Cont ID  
Sent By pleduc Date 2019-08-22 Time   Rev Time 0.00
Received By pleduc Date 2019-08-22 Time 12:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By pleduc Date 2019-06-25 Time   Rev Time 0.00
Received By pleduc Date 2019-06-25 Time 14:44 Sent To  
Notes
2019-06-25 15:05:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 02 - THERE IS AN INDICATION UNDER THE CALL-OUT
 DRAWING OF THE MTAL STUD PARTITION, "REFER TO FINSIH
 SCHEDULE FOR APPLIED FINISHES."
  
 THERE IS NO FINISH SCHEDULE FOR REFERRING.
  
 PER NFPA 101, CH 38, NEW BUSINESS OCCUPANCIES
  
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH
 SECTION 10.2 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN EXIT ACCESS
 CORRIDORS.
 38.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASS A,
 CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE SPECIFIED
 IN
 38.3.3.2.1.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
  
 2) SHEET 00 - THERE IS AN INDICATION UNDER D. FLOORING,
 "SEE SCHEDULE FOR ALLOWANCES FOR NEW FLOORING"
  
 THERE IS NO SCHEDULE FOR REFERRING.
  
 PER NFPA 101, CH 38, NEW BUSINESS OCCUPANCIES
  
 38.3.3.3 INTERIOR FLOOR FINISH.
 38.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 38.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES
 SHALL BE CLASS
 I OR CLASS II.
 38.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-22 Cont ID  
Sent By pvalenti Date 2019-10-22 Time 10:27 Rev Time 0.00
Received By pvalenti Date 2019-10-02 Time 12:58 Sent To  
Notes
2019-10-03 12:59:02B10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-20 Time 15:38 Sent To  
Notes
2019-08-20 15:38:16B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-21 Time 13:13 Sent To  
Notes
2019-06-24 13:13:49B30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-10-22 Cont ID  
Sent By pvalenti Date 2019-10-22 Time 10:26 Rev Time 0.00
Received By pvalenti Date 2019-10-22 Time 10:26 Sent To  
Notes
2019-10-22 10:27:20***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 15:58 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-17 Cont ID  
Sent By ccole Date 2019-07-17 Time 08:42 Rev Time 0.00
Received By ccole Date 2019-07-17 Time 08:42 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By pvalenti Date 2019-10-22 Time 10:30 Rev Time 0.00
Received By pvalenti Date 2019-10-22 Time 09:55 Sent To  
Notes
2019-10-22 09:56:25***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 NFIP REVIEW DENIED:
  
  
 1.) FAILED: FEMA TECHNICAL BULLETIN 2; THE NEW FINISH
 FLOOR ELEVATION DETAIL INDICATES 14? 1/4" AT TOP OF
 SUB?FLOOR. THIS ELEVATION IS NOT ACCEPTABLE DUE TO THE
 FLOOR FRAMING NOT MEETING THE REQUIREMENTS OF FLOOD
 DAMAGE?RESISTANT MATERIALS. A NEW ELEVATION CERTIFICATE
 WILL HAVE TO BE SUBMITTED IF ELEVATIONS ARE ADJUSTED.
  
 2.) FAILED: FBC B 107.2.1 PROVIDE ANCHORING DETAILS FOR
 THE EXTERIOR A/C RACKS (MEETING 14.00? ELEVATION
 REQUIREMENT).
 THE NEW ELEVATION CERTIFICATE (SECTION
 C2?E) WILL HAVE TO INCLUDE ELEVATION OF EQUIPMENT.
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By tklarge Date 2019-08-27 Time 14:47 Rev Time 0.00
Received By tklarge Date 2019-08-27 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By gjohnson Date 2019-07-10 Time 09:57 Rev Time 0.00
Received By gjohnson Date 2019-07-10 Time 14:58 Sent To  
Notes
2019-07-10 15:01:391ST REVIEW: 19061078
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DIMENSIONS OF THE BATHROOM ON THE FLOOR PLAN
 DOES NOT MATCH THE DETAIL OF THE TOILET STALL THE 7'
 WIDTH OF THE BATHROOM ON THE FLOOR PLAN IS NOT WIDE
 ENOUGH TO ACCOMMODATE THE REQUIRED CLEAR FLOOR SPACE
 FOR THE TOILET AND THE LAVATORY THE MINIMUM SIZE SHOULD
 BE 7'1" TO MEET ACCESSIBILITY REQUIREMENTS.CHANGE PLANS
 TO MATCH AND COMPLY WITH FBC ACC CH 6
  
 2. THE SINK IN THE LOUNGE SHALL COMPLY WITH FBC ACC
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3. SHT P-1 AS BUILT DRAWINGS SHALL BE SUBMITTED AS A
 REVISION AND APPROVED BY BUILDING DEPARTMENT BEFORE
 FINAL INSPECTIONS. PER WPB AMEND TO FBC 107.2.1
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. FBC PL 416.5
  
 5. PROVIDE FIRE STOPPING DETAIL FOR PVC PIPING. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2019-10-11 Cont ID  
Sent By llouie Date 2019-10-11 Time   Rev Time 0.00
Received By llouie Date 2019-10-11 Time   Sent To  
Notes
2019-10-11 13:06:28ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) NEW A/C COMPRESSOR UNIT SHALL BE SCREENED FROM VIEW
 WITH A LANDSCAPE HEDGE.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-08-23 Cont ID  
Sent By llouie Date 2019-08-23 Time   Rev Time 0.00
Received By llouie Date 2019-08-23 Time   Sent To  
Notes
2019-08-23 15:46:26ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) NEW A/C COMPRESSOR UNIT SHALL BE SCREENED FROM VIEW
 WITH A LANDSCAPE HEDGE.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By llouie Date 2019-07-03 Time   Rev Time  
Received By llouie Date 2019-07-03 Time   Sent To  
Notes
2019-07-03 10:25:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED AND SEALED SURVEY OF THE PROPERTY MISSING
 FROM THE PERMIT APPLICATION.
  
 2.) NEW HVAC PAD LOCATED ON THE NORTH SIDE OF THE
 SUBJECT BUILDING (SEE SHEET 01) NOT REFLECTED IN THE
 SITE PLAN. PAD MUST BE REFLECTED IN THE SITE PLAN FOR
 CONSISTENCY.
  
  
 NOTES:
  
 * VALUE OF THE SCOPE OF WORK DOES NOT EXCEED 50% VALUE
 OF THE STRUCTURE.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: IL (CORPORATE WAY)
  