Plan Review Details - Permit 19061015
Plan Review Stops For Permit 19061015
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By pvalenti Date 2019-09-20 Time 15:31 Rev Time 0.00
Received By pvalenti Date 2019-09-20 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By pvalenti Date 2019-07-19 Time 08:59 Rev Time 0.00
Received By pvalenti Date 2019-07-19 Time 08:59 Sent To  
Notes
2019-07-19 09:23:31***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1. FBC B 107.2 PROVIDE A PRODUCT APPROVAL FOR WINDOW
 MULLION LOCATED IN STUDIO.
 2. FBC B 107.2.1 ADJUST DETAIL # 7 OF PAGE A06 TO SHOW
 WINDOW AND DOOR BUCKS TO BE A MINIMUM FULL WIDTH OF
 WINDOW/DOOR FRAMES.
 3. FBC B 107.2.1 PROVIDE TIE IN AND SPECIFIC
 REINFORCING DETAIL FOR INCREASE IN FLOOR SLAB
 THICKNESS/RAISED 4".
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-22 Cont ID  
Sent By jpearson Date 2019-10-22 Time 08:55 Rev Time 0.00
Received By jpearson Date 2019-10-22 Time 08:55 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-20 Cont ID  
Sent By ppetty Date 2019-09-20 Time 10:32 Rev Time 0.00
Received By ppetty Date 2019-09-20 Time 10:32 Sent To  
Notes
2019-09-20 10:31:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.
 2.
 3.
 4..
 5
 6.
 7. WHERE IS THE ELECTRICAL FEED AND LOAD FOR WATER
 HEATER SHOWN ON PLAN? PROVIDE CORRECTION. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-11 Cont ID  
Sent By jpearson Date 2019-07-11 Time 11:21 Rev Time 0.00
Received By jpearson Date 2019-07-11 Time 10:47 Sent To  
Notes
2019-07-11 11:20:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 2. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL C. NEC 225.31,
 225.32
 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 4. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 5. NOTE 5 STATES THAT LIGHTING IN CLOTHES CLOSETS SHALL
 COMPLY WITH NEC 410.8, WHICH DOESN?T APPLY TO CLOTHES
 CLOSETS. PROVIDE CORRECTION. NEC 410.16; FBC RE
 E4003.12
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 7. WHERE IS THE ELECTRICAL FEED FOR TANKLESS WATER
 HEATER SHOWN ON PLUMBING PLAN? PROVIDE CORRECTION. WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-09-25 Cont ID  
Sent By gjohnson Date 2019-09-25 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2019-09-25 Time 10:25 Sent To  
Notes
2019-09-25 10:26:27NO GAS SHOWN ON PLAN CHANGED GAS HEATER TO AN ELECTRIC
 WATER HEATER./GPJ

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By thunt Date 2019-06-25 Time 10:24 Rev Time 0.00
Received By thunt Date 2019-06-25 Time 10:24 Sent To  
Notes
2019-06-25 10:24:50GAS 1ST REVIEW**DENIED**
  
 1) PROVIDE INSTALLATION MANUAL FOR THE TANKLESS WATER
 HEATER. FBC 107.2.1
  
 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING
 APPLIANCES.FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) THE 1 1/4" LINE APPEARS TO BE UNDERGROUD AND SCH 40
 METAL PIPE AS THE ONLY SIZING CHART PROVIDED. SCH 40
 METAL PIPING IS NOT PERMITTED UNDER GROUND. PLEASE
 CLARIFY. FBC-G 404.11, 404.11.1, 404.11.2
  
 4) PROVIDE MOUNTING DISTANCE OF TANKLESS WATER HEATER,
 FROM CORNER WALL, OVERHANG, AND FROM ANY DOOR OR WINDOW
 THAT OPENS. FBC 107.2.1PLEASE VERIFY WITH INSTALLATION
 MANUAL FOR REQUIRED DISTANCES.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-10-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-11 Time 14:03 Sent To  
Notes
2019-10-15 14:03:17RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-25 Cont ID  
Sent By gjohnson Date 2019-09-25 Time 10:26 Rev Time 0.00
Received By gjohnson Date 2019-09-13 Time 14:32 Sent To  
Notes
2019-09-16 14:32:36R03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By pvalenti Date 2019-07-19 Time 09:23 Rev Time 0.00
Received By pvalenti Date 2019-06-20 Time 11:47 Sent To  
Notes
2019-06-24 11:47:27R24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-16 Cont ID  
Sent By cmontell Date 2019-07-16 Time 11:33 Rev Time 0.00
Received By cmontell Date 2019-07-16 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-21 Cont ID  
Sent By gjohnson Date 2019-10-21 Time 13:57 Rev Time 0.00
Received By gjohnson Date 2019-10-21 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By gjohnson Date 2019-09-24 Time 18:53 Rev Time 0.00
Received By gjohnson Date 2019-09-24 Time 13:21 Sent To  
Notes
2019-09-24 18:53:442ND REVIEW: 19061015
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.THE BAR SINK BRANCH DRAIN SHALL CONNECT TO THE
 BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER
 FBC P3108.1
  
 2. THE LAVATORY SHALL CONNECT BETWEEN THE TUB AND THE
 TOILET TWO FIXTURES ARE NOT ALLOWED UPSTREAM OF THE WET
 VENT. PER FBC RES P3108.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By thunt Date 2019-06-25 Time 10:35 Rev Time 0.00
Received By thunt Date 2019-06-25 Time 10:35 Sent To  
Notes
2019-06-25 10:35:39PLUMBING 1ST REVIEW**DENIED**
  
 1) PLUMBING ISOMETRIC SHOW THE BAR SINK BEING VENTED BY
 AAV. EACH BUILDING DRAIN SHALL HAVE A VENTTHAT ENTENDS
 TO THE OUTDOORS. REFER TO FBCR-P3102.1
  
 2) PLUMBING ISOMETRIC DOES NOT SHOW THE BATHROOM SINK
 AS BEING VENTED. PROVIDE A VENT. FBCR-P 3101.2.1
  
 3) PROVIDE SHOWER PAN DETAIL SHOWING MATERIAL TO BE
 USED AND FLOORING PRE PITCH IF NOT RECESSED. FBC
 107.2.1
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By llouie Date 2019-09-24 Time   Rev Time 0.00
Received By llouie Date 2019-09-24 Time   Sent To  
Notes
2019-09-24 09:43:47ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) NO KITCHEN FACILITY PERMITTED.
  
 NOTES:
  
 * AS NOTED BY THE ARCHITECT, SCOPE OF WORK IS
 CONVERSION OF A GARAGE TO A HOBBY SPACE ONLY. NOT AN
 ACCESSORY DWELLING UNIT.
  
 * ZONE: SF7

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-28 Cont ID  
Sent By llouie Date 2019-06-28 Time   Rev Time  
Received By llouie Date 2019-06-28 Time   Sent To  
Notes
2019-06-28 14:44:34** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY IS REQUIRED.
  
 2.) THE PROPERTY IS ZONED SINGLE-FAMILY LOW DENSITY
 (SF7) RESIDENTIAL. SCOPE OF WORK INDICATES THAT AN
 ACCESSORY APARTMENT IS PROPOSED; HOWEVER, AN ACCESSORY
 APARTMENT IS NOT PERMITTED IN THE SF7 ZONING DISTRICT.
  
  
 NOTES:
  
 * SCOPE OF WORK DOES NOT TRIGGER 50% OF THE VALUE OF
 THE STRUCTURE (2018 PAPA).
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  