Plan Review Details - Permit 19061006
Plan Review Stops For Permit 19061006
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-01 Cont ID  
Sent By pvalenti Date 2019-07-01 Time 15:19 Rev Time 0.00
Received By pvalenti Date 2019-07-01 Time 15:19 Sent To  
Notes
2019-07-01 15:23:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLAN REVIEW APPROVED:
  
 RECEIVED SIGNED AND SEALED DELEGATED ENGINEER'S
 INSPECTION APPROVAL LETTERS THAT HAVE BEEN REVIEW
 STAMPED AND APPROVED BY THE DESIGN PROFESSIONAL. THESE
 LETTERS PERTAIN TO THE STRUCTURAL STEEL AT THE
 MEZZANINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-22 Cont ID  
Sent By pvalenti Date 2019-06-22 Time 12:56 Rev Time 0.00
Received By pvalenti Date 2019-06-22 Time 12:55 Sent To  
Notes
2019-06-22 13:48:52***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW OF THIS SUBMITTAL IS DENIED.
  
 FBC B 107.
 1. THE ERECTION OF THE MEZZANINE STRUCTURAL FRAMING
 MEMBERS IS NOT SPECIFIC AS TO THE CONFLICT, OBSERVED
 ON-SITE, OF THE STRUCTURAL DRAWING DETAILS WITH THE
 FRAMING MEMBERS THAT WERE ERECTED.
 THE FLAT/HORIZONTAL LEG OF THE STEEL JOISTS THAT BEAR
 AND ARE TO BE WELDED TO THE TOP FLANGE OF THE
 SUPPORTING BEAMS DID NOT EXIST AS PART OF THE JOISTS AT
 TIME OF INSPECTION. SEE, INCLUDED IN THE PERMIT
 PACKAGE, A COPY OF THE AREA OF CONCERN.
 PLEASE PROVIDE BY DESIGNER OF RECORD: 1. PHOTOS AND
 SPECIFIC APPROVAL OF REPAIR TO JOISTS; AND 2. APPROVAL
 OF ERECTION AND ALL WELDED CONNECTIONS.
  
 2. THE SIGNATURES ON THE SUBMITTED INSPECTION REPORTS
 WERE NOT SIGNED IN ACCORDANCE WITH THE PROVISIONS OF
 SECTION 471.025,F.S. AND RULE 61G15-23.001 OF THE
 FLORIDA ADMINISTRATIVE CODE.
 AS THESE DOCUMENTS WERE SUBMITTED ON PAPER, A DIGITAL
 SIGNATURE IS NOT APPLICABLE IN THIS CASE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-01 Cont ID  
Sent By pvalenti Date 2019-07-01 Time 15:24 Rev Time 0.00
Received By pvalenti Date 2019-07-01 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-22 Cont ID  
Sent By pvalenti Date 2019-06-22 Time 13:49 Rev Time 0.00
Received By pvalenti Date 2019-06-20 Time 16:56 Sent To  
Notes
2019-06-20 16:56:53SUBMITTAL ROUTED TO PVALENTI