| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE |
| | SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| | ASSEMBLIES: COLUMN HEADING ?SHUTTER SPAN?; SEE TYPICAL |
| | (1) HV BLADE SHUTTER ELEVATION; SHEET 5 OF PRODUCT |
| | APPROVAL FL1850. COLUMN HEADING ?ANCHOR SPACING?; |
| | PROVIDE INFORMATION FROM PAGE 12 OF PRODUCT APPROVAL |
| | FL1850. COLUMN HEADING ?SPECIFIC ANCHOR TYPE?; PROVIDE |
| | INFORMATION FROM PAGE 13 OF PRODUCT APPROVAL FL1850, |
| | *SPECIFCATIONS ON ANCHOR REQUIREMENTS: POURED CONCRETE |
| | OR CONCRETE BLOCK SUBSTRATES; ELCO ULTRACON IS NOT A |
| | PART OF THESE SPECIFICATIONS. COLUMN HEADING ?SHUTTER |
| | MOUNTING: CONNECTION TYPE PER PRODUCT APPROVAL? PROVIDE |
| | INFORMATION FROM PAGES 6 & 7 OF PRODUCT APPROVAL |
| | FL1850. COLUMN HEADING ?SHUTTER INSTALLED |
| | VERTICAL/HORIZONTAL?: ACCORDION SHUTTERS ARE INSTALLED |
| | VERTICALLY AS PER PRODUCT APPROVAL FL1580. |
| | 2. FBC B 107.2.1. PLEASE VERIFY THE INFORMATION ON THE |
| | SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| | ASSEMBLIES FOR PRODUCT APPROVAL FL11291. EXAMPLE: |
| | ANCHOR SPACING FOR TYPE 1 CONNECTION PAGE 6 OF PRODUCT |
| | APPROVAL FL11291 IS 24? O.C. |
| | |