Plan Review Details - Permit 19060948
Plan Review Stops For Permit 19060948
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-11 Cont ID  
Sent By jleahy Date 2019-07-11 Time 14:55 Rev Time 0.00
Received By jleahy Date 2019-07-11 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-21 Cont ID  
Sent By jleahy Date 2019-06-21 Time 14:22 Rev Time 0.00
Received By jleahy Date 2019-06-21 Time 14:21 Sent To  
Notes
2019-06-21 14:30:03FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E2.0 FLOATING MIXERS AND CONTROLLERS NEED CUT
 SHEETS ON THIS EQUIPMENT.
  
 2) PAGE E2.1MCC-1 SHOW BUSS TAP PLEASE HAVE FIELD
 EVALUATION FOR THIS WORK BY A NATIONALY RECOGNIZED
 TESTING LAB. PER 110.3(B) LISTING AND USE.
 PLEASE INDICATE NEW EQUIPMENT ON PLAN.
  
 3) PAGE E2.2 NEED TO SUBMIT CUT SHEETS ON CABLES USED
 FOR MIXERS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-11 Cont ID  
Sent By jleahy Date 2019-07-11 Time 14:56 Rev Time 0.00
Received By jleahy Date 2019-07-08 Time 14:38 Sent To  
Notes
2019-07-09 14:38:51RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-21 Cont ID  
Sent By jleahy Date 2019-06-21 Time 14:30 Rev Time 0.00
Received By jleahy Date 2019-06-20 Time 14:25 Sent To  
Notes
2019-06-20 14:25:43ROUTED TO ELECTRICAL INBOX