Plan Review Details - Permit 19060924
Plan Review Stops For Permit 19060924
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-07 Cont ID  
Sent By pvalenti Date 2019-08-07 Time 13:16 Rev Time 0.00
Received By pvalenti Date 2019-08-07 Time 13:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By pvalenti Date 2019-07-05 Time 15:14 Rev Time 0.00
Received By pvalenti Date 2019-07-05 Time 15:14 Sent To  
Notes
2019-07-05 16:28:13***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN REVIEW DENIED:
  
 1. FBC B 107. INDICATE COMPLIANCE WITH FAIR HOUSING AS
 NOTED IN PLUMBING REVIEW COMMENTS.
  
  
 2. FBC B 107. PROVIDE THE REQUIRED FLOORING
 UNDERLAYMENT AND FLOORING TEST RESULTS LISTED BELOW:
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
 3. FBC B 2403.2, PROVIDE ENGINEER SIGNED/SEALED
 DETAILED DOCUMENTATION AND ANALYSIS OR TEST DATA
 ENSURING SAFE PERFORMANCE OF GLASS SHOWER PANES.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-13 Cont ID  
Sent By jpearson Date 2019-08-13 Time 13:59 Rev Time 0.00
Received By ppetty Date 2019-08-13 Time 13:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By jpearson Date 2019-07-15 Time 10:10 Rev Time 0.00
Received By jpearson Date 2019-07-15 Time 09:49 Sent To I
Notes
2019-07-15 10:10:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE
 CORRECTION FOR BATH A. NEC 210.11(C)(3), 210.52(D)
 2. RECEPTACLE OUTLET ON PENINSULA IS SHOWN UNDER AN
 OVERHANG OF COUNTER TOP THAT IS MORE THAN 6 INCHES.
 PROVIDE CORRECTION FOR REQUIRED RECEPTACLE OUTLET IN
 THIS LOCATION. NEC 210.52(C)(3) AND (5).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By pleduc Date 2019-08-02 Time   Rev Time 0.00
Received By pleduc Date 2019-08-02 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-24 Cont ID  
Sent By scaldero Date 2019-06-24 Time   Rev Time 0.00
Received By pleduc Date 2019-06-24 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-22 Cont ID  
Sent By jesmith Date 2019-08-22 Time 09:22 Rev Time 0.00
Received By jesmith Date 2019-08-22 Time 09:22 Sent To  
Notes
2019-08-01 15:02:22B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-19 Time 13:54 Sent To  
Notes
2019-06-20 13:54:54B14

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-22 Cont ID  
Sent By gjohnson Date 2019-08-22 Time 09:21 Rev Time 0.00
Received By jesmith Date 2019-08-22 Time 09:03 Sent To  
Notes
2019-08-22 09:21:26PLUMBING COMMEMTS: APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-27 Cont ID  
Sent By thunt Date 2019-06-27 Time 09:51 Rev Time 0.00
Received By gjohnson Date 2019-06-27 Time 09:51 Sent To  
Notes
2019-06-27 10:11:56 
 1ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-1 GENERAL NOTE #09 WORK SHALL COMPLY WITH FBC
 2017 6TH EDITION PER WPB AMEND TO FBC 107.2.1
  
 2.THIS BUILDING WAS BUILT TO COMPLY WITH FAIR HOUSING
 PLEASE SHOW ON THE PLAN WHICH BATHROOMS COMPLIES AND
 WHAT SPEC A OR B AND SHOW ALL CLEAR FLOOR SPACES. PER
 FHA DESIGN MANUAL
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]