Plan Review Details - Permit 19060896
Plan Review Stops For Permit 19060896
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-12-31 Cont ID  
Sent By dbattles Date 2019-12-31 Time 15:11 Rev Time 0.00
Received By dbattles Date 2019-12-31 Time 15:11 Sent To  
Notes
2019-12-31 15:11:57PROVISO:
 NEED PRODUCT APPROVAL FOR NEW BACK DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-12-16 Cont ID  
Sent By jwitmer Date 2019-12-16 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2019-12-16 Time 06:08 Sent To  
Notes
2019-12-16 15:03:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060896
 ADD: 1242 PALM BEACH LAKES
 CONT: DCOTA CONTRACTING INC.
 TEL: 561-718-6565
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. DEC. 16/ 2019
 ACTION: DENIED
  
 1) THIS SUBMITTAL THE PLANS HAVE NOT BEEN COLLATED
 CORRECTLY, MISSING THE COVERSHEET, SHEET 1.1 THE FLOOR
 DEMOLITION PLAN. THERE IS NOW A SHEET 2.0 NOT FOUND ON
 THE ORIGINAL INDEX PLUMBING PLAN, WATER PLAN.
 2) ON THE ORIGINAL REVIEW THE INDEX SHEET INDICATED
 SHEET 2.1 WAS THE LIFE SAFETY PLAN WITH PROJECT DATA,
 SHEET 2.1 IS NOW THE GAS RISER AND SANITARY RISER
 SHEET.
 3) BUILDING/ STRUCTURAL DETAILS THAT WERE ON THE VOIDED
 SHEET 4.1 ARE NOW ON SHEET 4.0 A VERY LIGHT GRAY LINE
 DRAWING. WILL NOT MEET THE STANDARDS TO BE SCANNED IN
 FOR RECORD RETENTION.
 107.2.1.3 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 4) ADDITIONAL COMMENTS FROM THE 1ST REVIEW THAT CANNOT
 BE FOUND ON THE CURRENT SET OF PLANS.
  
  
 1) SHEET 2.1 THE LIFE SAFETY FLOOR PLAN.
  
 1C) PLEASE CORRECT THE STATEMENT, PLANS COMPLY WITH THE
 2014 FBC. DEC. 31/ 2017 THE 2017 FBC FAMILY OF CODES
 WAS ADOPTED STATEWIDE.
  
 1D) SHEET 2.1 SHOWS THE BACK DOOR BEING INFILLED FROM 6
 FEET TO 4 FOOT 4 INCHES IN WIDTH. SHEET 4.1 HAS A
 DETAIL FOR THE WINDOW INFILL DETAIL ABOVE THE DOOR BUT
 THERE IS NO DETAIL FOR THE DOOR INFILL. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.2.
  
 1E) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW
 DOOR OPENING. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1E)(1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1E)(2.) RISK CATEGORY.
  
 1E)(3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE.
  
 1E)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1E)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 1F) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 1G) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 1H) IF THE NEW DOOR IS GLAZED. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 1I) THE SHEET 2.1 INDICATES ONLY ONE RESTROOM. PLEASE
 SEE THE 2017 FBC-B TABLE 2902.1 REQUIRING 2 RESTROOMS.
 SECTION 2902.2 OF THE FBC-B SEPARATE FACILITIES
 EXCEPTION 2 ONLY ALLOWS FOR A SINGLE RESTROOM WHEN
 THERE IS A TOTAL OCCUPANT LOAD OF 15 OR FEWER EMPLOYEES
 AND CUSTOMERS. 2 RESTROOMS ARE REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-11-07 Cont ID  
Sent By ccole Date 2019-11-07 Time 11:16 Rev Time 0.00
Received By ccole Date 2019-11-07 Time 11:16 Sent To I
Notes
2019-11-07 11:20:033RD REVIEW FBC-2017 BUILDING
 PERMIT #19060896
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE APPROVED ARCHITRECTURAL PLAN
 SHEETS WERE NOT ATTACHED AND RETURNED WITH THE
 CORRECTED MEP PLANS. PLEASE RESUBMIT THE SHEETS- SEE
 INDEX ON C.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-23 Cont ID  
Sent By jwitmer Date 2019-09-23 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2019-09-23 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2019-07-08 Time 08:18 Sent To  
Notes
2019-07-08 10:04:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060896
 ADD: 1242 PALM BEACH LAKES
 CONT: DCOTA CONTRACTING INC.
 TEL: 561-718-6565
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 08/2019
 ACTION: DENIED
  
 1) SHEET 2.1 THE LIFE SAFETY FLOOR PLAN.
 1A) PROJECT DATA INDICATES THIS IS A BUSINESS OCCUPANCY
 WITH 1, 882 SQ. FT. AND AN OCCUPANT LOAD OF 18. PLEASE
 REVIEW THE 2017 FBC-B TABLE 1004.1.2. YOU CANNOT HAVE A
 PORTION OF AN OCCUPANT, THE OCCUPANT LOAD IS 19
 OCCUPANTS, AND YOU ALWAYS ROUND UP.
  
 1B) THE FLOOR PLAN INDICATES THIS SPACE IS FIRE
 SPRINKLERED BUT THERE WERE NO FIRE SPRINKLER PLANS.
 107.2.2 FIRE PROTECTION SYSTEM SHOP DRAWINGS. SHOP
 DRAWINGS FOR THE FIRE PROTECTION SYSTEM(S) SHALL BE
 SUBMITTED TO INDICATE CONFORMANCE WITH THIS CODE AND
 THE CONSTRUCTION DOCUMENTS AND SHALL BE APPROVED PRIOR
 TO THE START OF SYSTEM INSTALLATION. SHOP DRAWINGS
 SHALL CONTAIN ALL INFORMATION AS REQUIRED BY THE
 REFERENCED INSTALLATION STANDARDS IN CHAPTER 9.
  
 1C) PLEASE CORRECT THE STATEMENT, PLANS COMPLY WITH THE
 2014 FBC. DEC. 31/ 2017 THE 2017 FBC FAMILY OF CODES
 WAS ADOPTED STATEWIDE.
  
 1D) SHEET 2.1 SHOWS THE BACK DOOR BEING INFILLED FROM 6
 FEET TO 4 FOOT 4 INCHES IN WIDTH. SHEET 4.1 HAS A
 DETAIL FOR THE WINDOW INFILL DETAIL ABOVE THE DOOR BUT
 THERE IS NO DETAIL FOR THE DOOR INFILL. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.2.
  
 1E) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW
 DOOR OPENING. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1E)(1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1E)(2.) RISK CATEGORY.
  
 1E)(3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE.
  
 1E)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1E)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 1F) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 1G) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 1H) IF THE NEW DOOR IS GLAZED. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 1I) THE SHEET 2.1 INDICATES ONLY ONE RESTROOM. PLEASE
 SEE THE 2017 FBC-B TABLE 2902.1 REQUIRING 2 RESTROOMS.
 SECTION 2902.2 OF THE FBC-B SEPARATE FACILITIES
 EXCEPTION 2 ONLY ALLOWS FOR A SINGLE RESTROOM WHEN
 THERE IS A TOTAL OCCUPANT LOAD OF 15 OR FEWER EMPLOYEES
 AND CUSTOMERS. 2 RESTROOMS ARE REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-12-31 Cont ID  
Sent By jpearson Date 2019-12-31 Time 10:06 Rev Time 0.00
Received By jpearson Date 2019-12-31 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-23 Cont ID  
Sent By jpearson Date 2019-09-23 Time 11:03 Rev Time 0.00
Received By jpearson Date 2019-09-23 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-17 Cont ID  
Sent By jleahy Date 2019-07-17 Time 15:26 Rev Time 0.00
Received By jleahy Date 2019-07-17 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-01-03 Cont ID  
Sent By pleduc Date 2020-01-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-03 Time 10:56 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-12-04 Cont ID  
Sent By pleduc Date 2019-12-04 Time   Rev Time 0.00
Received By pleduc Date 2019-12-04 Time 15:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By pleduc Date 2019-09-09 Time   Rev Time 0.00
Received By pleduc Date 2019-09-09 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-24 Cont ID  
Sent By pleduc Date 2019-06-24 Time   Rev Time 0.00
Received By pleduc Date 2019-06-24 Time 11:06 Sent To  
Notes
2019-06-24 11:32:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER AND/OR
 FIRE ALARM SYSTEMS WITHIN THIS PROPOSED PROJECT.
  
 PLEASE PROVIDE A NOTE INDICATING EXISTING OR NOT, AND
 IF EXISTING, ALL WORK ON THE FS & FA SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 2) THE PROPOSED PROJECT APPEARS TO BE IN A STRIP MALL
 TYPE BUILDING; HOWEVER, THERE IS NO SUITE NUMBER
 INDICATED ON THE APPLICATION NOR TITLE BLK.
  
 PLEASE PROVIDE A SUITE NUMBER OR OTHER IDENTIFICATION
 OF THIS SPACE ON THE PLAN SHEETS OR CONFIRM THE
 ADDRESS.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-01-02 Cont ID  
Sent By jesmith Date 2020-01-02 Time 13:59 Rev Time 0.00
Received By jesmith Date 2020-01-02 Time 13:33 Sent To  
Notes
2020-01-02 13:58:59GAS COMMENTS: APPROVED W/PROVISO
 1. COMBUSTION AIR ISSUES SHALL BE RESOLVED WITH
 MECHANICAL AND APPROVED PRIOR TO CO.
 2. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION.
 CALL 561-805-6692 FOR FURTHER INFORMATION.
 3. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-12-24 Cont ID  
Sent By gjohnson Date 2019-12-24 Time 11:13 Rev Time 0.00
Received By gjohnson Date 2019-12-24 Time 11:13 Sent To  
Notes
2019-12-24 11:13:433RD REVIEW: 19060896
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHT. 2.0 ON THE WATER AND GAS PLAN IT LIST 12 OF THE
 T-50 THE PLAN ONLY SHOWS 10 IF 2 OF THEM ARE FUTURE
 PLEASE SHOW LOCATION ON PLAN AND LABEL AS FUTURE. PER
 WPB AMEND TO FBC PL 107.2.1
  
 2. SHT. 2.0 THE NOTE ON THE WATER GAS PLAN LIST T-50
 BUT THE PLAN SHOWS T-50X2 PLEASE CLARIFY. PER WPB AMEND
 TO FBC PL 107.2.1
  
 3. SHT. 2.1 ON THE GAS RISER THE SIZING ON THE 2LB
 PIPING IS SHOWN AT THE METER AS 11/4" FOR THE FIST
 SECTION 11/2 FOR THE 40' SECTION AND 2" ON THE 18'
 SECTION PLEASE CLARIFY. PER WPB AMEND TO FBC PL 107.2.1
  
 4.SHT. 3.1 APPEARS TO BE A PREVIOUS VERSION OF THE GAS
 RISER PLEASE REMOVE PLANS THAT ARE TO BE VOIDED AND
 HAVE BEEN REVISED. PER WPB AMEND TO FBC PL 107.2.1
  
 5. COMBUSTIONS AIR PLEASE SEE COMMENTS ON MECHANICAL
 REVIEW ALSO PROVIDE DIMENSIONS OF THE SPACE ABOVE THE
 BATHROOMS BELOW THE PENTHOUSE VENTILATOR. PER WPB AMEND
 TO FBC PL 107.2.1
 I BELIEVE YOUR CALCULATIONS USING THE MAKE UP AIR
 LISTED IN THE MANUFACTURE SPECIFICATIONS MAYBE
 INCORRECT THE MAKE AIR IS THE AIR REPLACING THE AIR
 SUCKED OUT OF THE SPACE USED IN THE DRYING PROCESS AND
 EXHAUSTED TO THE OUTSIDE THE COMBUSTION AIR IS THE
 AMOUNT OF AIR NEEDED TO BURN THE FUEL COMPLETELY THIS
 IS IS SEPARATE FROM ANY MAKE UP AIR AND WITHOUT THE
 PROPER AMOUNT OF COMBUSTION AIR THERE CAN BE INCOMPLETE
 BURN RESULTING IN EXCESS CARBINE MONOXIDE. USING THE
 STANDARD METHOD OUT OF THE CODE OF 50 CUBIC FT PER 1000
 RESULTS IN 151,000 CUBIC FT OF COMBUSTION AIR WHICH CAN
 COME FROM THE SPACE THE DRYERS ARE IN AND IF THAT IS
 NOT ENOUGH THEN YOU CAN BRING IN AIR FRO THE OUTSIDE.
 PER FBCFG 304.5.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-11-05 Cont ID  
Sent By jesmith Date 2019-11-05 Time 15:55 Rev Time 0.00
Received By jesmith Date 2019-11-05 Time 15:18 Sent To  
Notes
2019-11-05 15:55:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
 A SEPARATE GAS PERMIT IS REQUIRED
  
 1. ENGINEER HAS NOW PROVIDED GAS TANKLESS WATER HEATERS
 IN AN OUTDOOR SETTING. SUBMITTED SPECIFICATIONS ARE FOR
 INDOORS. PLEASE PROVIDE CORRECT SPECIFICATION SHEETS TO
 MATCH OUTDOOR APPLICATION.
 2. PLAN SHEET 2.1: GAS LOAD CALCULATIONS SHOULD BE
 2,558,000 BTUS AT 2 PSI FARTHEST DISTANCE FROM METER TO
 MP REGULATOR IN THE CEILING AT THE BEGINNING OF THE
 DRYERS. PLEASE SIZE ACCORDINGLY IN ACCORDANCE WITH FBC
 FG TABLE 402.4(5), CALLING OUT THE DISTANCE.
 3. PLAN SHEET 2.1: GAS LOAD CALCULATIONS SHOULD BE
 2,160,000 BTUS AT LESS THAN 2 PSI FARTHEST DISTANCE
 FROM MP REGULATOR IN THE CEILING AT THE BEGINNING OF
 THE DRYERS TO THE FARTHEST DRYER GAS CONNECTION. PLEASE
 SIZE ACCORDINGLY IN ACCORDANCE WITH FBC FG TABLE
 402.4(4), CALLING OUT THE DISTANCE.
 4. PLAN SHEET 2.1: GAS LOAD CALCULATIONS ARE 398,000
 BTUS AT LESS THAN 2 PSI FARTHEST DISTANCE FROM MP
 REGULATOR TO THE FARTHEST GAS HEATER CONNECTION. PLEASE
 SIZE ACCORDINGLY IN ACCORDANCE WITH FBC FG TABLE
 402.4(4), CALLING OUT THE DISTANCE.
 5. PLAN SHEET 2.1: CLEARLY SHOW ON THE ISOMETRIC
 DRAWING THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC
 FG, SECS. 402.4.1, 402.4.2. SHOW ALL SIZING, VALVES AND
 PRESSURE REGULATORS. IDENTIFY TYPE OF MATERIAL BEING
 USED.
 5. PROVIDE SPECIFICATION FOR MP REGULATORS FOR WATER
 HEATERS AND DRYERS. MP REGULATOR SHALL BE RATED FOR
 OUTDOORS.
 6. PLAN SHEET 3.1 ALSO NOTES GAS RISER DIAGRAM WHICH IS
 STAMPED FROM AN EARLIER REVIEW. PER WPB FBC 107.2.1,
 PLEASE CLARIFY. REMOVE ANY RISERS OR INFORMATION THAT
 IS NO LONGER PART OF THE PROJECT AND RESUBMIT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060896 1242 PALM BEACH LAKES BLVD
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By jesmith Date 2019-07-02 Time 16:05 Rev Time 0.00
Received By jesmith Date 2019-07-02 Time 16:04 Sent To  
Notes
2019-07-02 16:05:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 A SEPARATE GAS PERMIT IS REQUIRED
 1. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS
 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SEALED
 COMBUSTION AND DIRECT VENT SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505.
 4. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR THE
 GAS PRESSURE REGULATORS.
 5. PER WPB FBC 107.2.1, CLEARLY SHOW ON THE ISOMETRIC
 DRAWING THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC
 FG, SECS. 402.4.1, 402.4.2. SHOW ALL SIZING, VALVES AND
 PRESSURE REGULATORS. IDENTIFY TYPE OF MATERIAL BEING
 USED.
 6. PER WPB FBC 107.2.1, LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37). INDICATE EXISTING AND NEW.
 7. PER WPB FBC 107.2.1, CLEARLY INDICATE THE TYPE OF
 GAS (LP OR NATURAL).
 8. PER WPB FBC 107.2.1, SHOW THE DISTANCE FROM THE
 POINT OF DELIVERY, (GAS METER / MP REGULATOR TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 FBC FG SEC.402.4.1, 402.4.2. CLEARLY INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN.
 9. PER WPB FBC 107.2.1, PROVIDE SIZING OF ALL PIPING
 REFERENCING THE APPLICABLE FBC FG TABLES 402.4 (1) THRU
 402.4 (37). SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM FBC FG THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM.
 10. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 MANUAL GAS SHUTOFF VALVES.
 11. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC FG 305.1
 12. PER WPB FBC 107. 2.1, PROVIDE A PLAN VIEW OF ALL
 EXISTING AND ADDED GAS DISTRIBUTION. CLARIFY EXISTING
 AND ADDED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060896 1242 PALM BEACH LAKES BLVD
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-01-03 Cont ID  
Sent By lmarchan Date 2020-01-03 Time 12:54 Rev Time 0.00
Received By lmarchan Date 2019-12-24 Time 08:49 Sent To  
Notes
2019-12-27 08:49:36B14

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-12-24 Cont ID  
Sent By jwitmer Date 2019-12-24 Time 11:31 Rev Time  
Received By gjohnson Date 2019-12-02 Time 15:21 Sent To  
Notes
2019-12-17 11:25:02STEVE KENNEDY GAVE OK FOR THE ARCHITERCT TO SIGN OUT
 ONE SET OF PLANS. I STOPPED OUT. J. WITMER 12/17/2019
2019-12-03 15:22:11B13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-11-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-04 Time 11:31 Sent To  
Notes
2019-11-05 16:19:58RESUB ROUTED TO CCOLE
2019-11-05 14:39:33PLUMBING PLANS HAVE ADDED ELECTRIC WATER HEATER. DEVICE
 WAS ADDED AFTER PREVIOUS ELECTRICAL REVIEWS. CURRENT
 REVIEWED ELECTRICAL PLANS DO NOT REFLECT THE DEVICE.
2019-11-05 11:31:51RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-05 Time 11:42 Sent To  
Notes
2019-09-17 14:35:46GAS WAS NOT SUBMITTED FOR REVIEW AT THIS TIME
2019-09-06 11:42:55B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By jleahy Date 2019-07-17 Time 15:26 Rev Time 0.00
Received By jleahy Date 2019-06-19 Time 13:22 Sent To  
Notes
2019-06-20 13:22:21B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 10:04 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-01-02 Cont ID  
Sent By ccole Date 2020-01-02 Time 17:33 Rev Time 0.00
Received By ccole Date 2020-01-02 Time 15:08 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-12-17 Cont ID  
Sent By ccole Date 2019-12-17 Time 09:56 Rev Time 0.00
Received By ccole Date 2019-12-16 Time 17:17 Sent To  
Notes
2019-12-17 10:04:064TH REVIEW FBC-2017 MECHANICAL
 PERMIT #19060896
 2/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.1: THE 21 SF. GRAVITY VENTILATOR OPENING IS
 UNDERSIZED FOR THE TOTAL NUMBER OF DRYERS TO BE
 INSTALLED. THERE ARE 12- T50X2 UNITS (24 TUMBLERS) PLUS
 2- T80 UNITS (2 TUMBLERS)= (26 TUMBLERS) X (1.5 SF.
 EACH) = 39 SF. OF FREE AIR OPENING REQUIRED.
  
 2) PLEASE PROVIDE A DUPLICATE COPY OF THE
 MANUFACTURER'S SPECS FOR THE X2 DRYERS- THERE IS ONLY
 ONE COPY SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-11-07 Cont ID  
Sent By ccole Date 2019-11-07 Time 10:43 Rev Time 0.00
Received By ccole Date 2019-11-06 Time 17:04 Sent To B
Notes
2019-11-07 10:58:162ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19060896
 11/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.1: THE REQUIRED MAKEUP AIR FOR THE GAS
 DRYERS HAS NOT BEEN PROVIDED AS REQUIRED BY THE
 SUBMITTED MANUFACTURER'S SPECIFICATIONS- SECTION 613.1
 FBC FG. ACCORDING TO THE SPECS PRINTED ON SHEET 4.1, A
 1.5 SQ. FT. NET CLEAR MAKEUP AIR OPENING IS REQUIRED
 FOR EACH CLOTHES DRYER. ACCORDING TO THE NOTES ON PAGE
 15, MULTIPLE OPENINGS SHOULD BE PROVIDED TO ALLOW EVEN
 AIRFLOW TO THE DRYERS. THE USE OF THE EXISTING DRYER
 VENTS DO NOT MEET THE CRITERIA AS OUTLINED IN THE
 MANUFACTURER'S SPECIFICATIONS AND IN SECTIONS 304.6 FBC
 FG.
  
 2) 2ND REQUEST FOR CORRECT ENERGY COMPLIANCE DATA. THE
 COMPLIANCE DATA FOR THE10-TON RTU AS SHOWN IN THE
 ENERGY COMPLIANCE REPORT DOES NOT MATCH THE UNIT SPECS-
 120,000 BTUH COOLING, 34121 BTUH HEATING, AND 11.3 EER.
 PLEASE NOTE EFFICENCIES FOR 10-TON UNITS ARE RATED PER
 EER NOT SEER- SEE TABLE C403.2.3(1) FBC EC. .PLEASE
 CORRECT THE REPORT TO MATCH THE SCHEDULE AND SPECS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-09-18 Cont ID  
Sent By ccole Date 2019-09-18 Time 14:50 Rev Time 0.00
Received By ccole Date 2019-09-18 Time 12:53 Sent To  
Notes
2019-09-18 15:09:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060896
 9/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.1: THE REQUIRED MAKEUP AIR FOR THE GAS
 DRYERS HAS NOT BEEN PROVIDED AS REQUIRED BY THE
 SUBMITTED MANUFACTURER'S SPECIFICATIONS- SEE PAGES
 15-16 OF THE SPECS AND REVISE THE PLAN TO SHOW
 COMPLIANCE AND INCLUDE CALCULATIONS.
  
 2) SHEET 4.1: REFER TO PAGES 17-18 OF THE SUBMITTED GAS
 DRYER SPECIFICATIONS AND PROVIDE DIAGRAMS OF THE
 EXISTING DRYER VENT SYSTEMS TO VERIFY COMPLIANCE WITH
 THE SPECS. INDICATE IN THE DIAGRAMS THE TYPES AND SIZES
 OF VENTS, NUMBER OF ELBOWS, LENGTH OF VENT RUNS,
 TERMINATION HEIGHTS ABOVE THE ROOF, AND CLEARANCES TO
 COMBUSTIBLES.
  
 3) SHEET 4.1: THE MODEL NUMBERS OF THE DRYERS ARE NOT
 LEGIBLE ON THE PLAN. PLEASE ENLARGE THE PRINT- SECTION
 107.2 WPB.
  
 4) THE COMPLIANCE DATA FOR THE10-TON RTU AS SHOWN IN
 THE ENERGY COMPLIANCE REPORT DOES NOT MATCH THE UNIT
 SPECS- 120,000 BTUH COOLING, 34121 BTUH HEATING, AND
 11.3 EER. PLEASE NOTE EFFICENCIES FOR 10-TON UNITS ARE
 RATED PER EER NOT SEER- SEE TABLE C403.2.3(1) FBC EC.
 .PLEASE CORRECT THE REPORT TO MATCH THE SCHEDULE AND
 SPECS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By ccole Date 2019-07-15 Time 10:07 Rev Time 0.00
Received By ccole Date 2019-07-12 Time 15:35 Sent To  
Notes
2019-07-15 10:47:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060896
 7/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC
 AND SECTION 312.1 FBC M.
  
 2) SHEET 4.1: PLEASE CORRECT THE AHU DETAIL WHICH IS
 CITING THE FBC RESIDENTIAL CODE. THE PROPOSED PROJECT
 SHALL BE IN COMPLIANCE WITH THE FBC-17 MECHANICAL-
 SIXTH EDITION.
  
 3) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GAS DRYERS VERIFYING THE APPLIANCES IN COMPLIANCE WITH
 EITHER THE ANSI Z21.5.1 OR ANZI Z21.1.5.2 STANDARDS-
 SECTION 613.1 FBC FG.
  
 5) SHEET 4.1: SHOW THE LOCATIONS OF THE NEW GAS DRYERS
 AND PROVIDE COMPLETE VENTING PLANS. PLEASE NOTE THAT
 TYPE 2 COMMERCIAL GAS DRYER VENTING SYSTEMS SHALL BE
 ENGINEERED IN ACCORDANCE WITH MANUFACTURER'S
 SPECIFICATIONS. IF THE EXISTING SYSTEM DOES NOT MEET
 THE SPECIFICATIONS FOR THE NEW DRYERS, THAT SYSTEM
 SHALL BE ABANDONED AND A NEW SYSTEM SHALL BE INSTALLED.
 THE MECHANICAL PLANS SHALL SHOW THE INDIVIDUAL AND
 COMMON VENT LOCATIONS, SHOW THE BRANCH AND COMMON VENT
 TYPES AND VENT RUN LENGTHS AND TERMINATION LOCATION(S).
 PLEASE NOTE THAT EXHAUST FANS AND A MAKEUP AIR SYSTEM
 MAY BE REQUIRED PER THE MANUFACTURER'S SPECIFICATIONS.
 THE VENTING PLANS SHALL ALSO INDICATE THE SEQUENCE OF
 OPERATION IN ACCORDANCE WITH SECTION 614.9 FBC M WHICH
 REQUIRES CONTINUOUS FAN OPERATION OR INTERLOCKING OF OF
 INDIVIDUAL UNITS TO THE FAN.
  
 THE PLAN REVIEW IS STOPPED AT THIS TIME DUE TO LACK OF
 INFORMATION, AND DRYER AND DRYER VENTING DETAILS AND
 SPECIFICATIONS- SECTION 107.2.1 WPB.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-01-02 Cont ID  
Sent By jesmith Date 2020-01-02 Time 13:33 Rev Time 0.00
Received By jesmith Date 2020-01-02 Time 09:22 Sent To  
Notes
2020-01-02 13:32:59PLUMBING COMMENTS: APPROVED W/PROVISO
 1. ONE (1) EACH ACUMMIX WATER HEATER IS REQUIRED FOR
 EACH OF THE TWO (2) LAVS
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-12-24 Cont ID  
Sent By gjohnson Date 2019-12-24 Time 11:27 Rev Time 0.00
Received By gjohnson Date 2019-12-23 Time 13:16 Sent To  
Notes
2019-12-24 11:31:211. REVIEW COULD NOT BE COMPLETED AT THIS TIME PREVIOUS
 SHT 3.1 HAS OLD DRAWINGS THAT HAVE BEEN REVISED ON
 SHEET 2.1 THIS REVIEW WAS STOPPED SO THAT ARCHITECT CAN
 RESUBMIT NEW SHEETS. PER STEVE KENNEDY
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-11-05 Cont ID  
Sent By jesmith Date 2019-11-05 Time 14:36 Rev Time 0.00
Received By jesmith Date 2019-11-05 Time 14:35 Sent To  
Notes
2019-11-05 14:36:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1.REGARDING THE EEMAX ACCUMIX II AM005240T TANLESS
 WATER HEATER, PLEASE NOTE THE FOLLOWING.
 A. PER THE MANUFACTURER, EACH LAVATORY IN THIS
 APPLICATION WILL REQUIRE A DEDICATED POINT OF USE WATER
 HEATER LOCATED WITHIN 2 FEET OF THE FIXTURE BEING
 SERVICED.
 B. THE ELECTRIC TANKLESS WATER HEATER HAS BEEN ADDED TO
 THE PLUMBING PLANS BUT HAS NOT BEEN INCORPORATED INTO
 THE ELECTRICAL PLANS FOR REVIEW.
 C. THE ACCUMIX II CUT SHEET ON PLAN SHEET 2.1 IS
 BLURRED AND DIFFICULT TO READ. PROVIDE TWO (2) SETS
 EACH OF CLEAN 8-1/2 X 11 SHEETS AS AN ATTACHMENT.
 2. PLAN SHEET 3.1 ALSO NOTES A SANITARY RISER DIAGRAM
 WHICH IS STAMPED FROM AN EARLIER REVIEW. PER WPB FBC
 107.2.1, PLEASE CLARIFY. REMOVE ANY RISERS OR
 INFORMATION THAT IS NOT PART OF THE RESUBMISSION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060896 1242 PALM BEACH LAKES BLVD
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-09-17 Cont ID  
Sent By jesmith Date 2019-09-17 Time 14:22 Rev Time 0.00
Received By jesmith Date 2019-09-17 Time 14:20 Sent To  
Notes
2019-09-17 14:20:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. 2ND REQUEST; PER FBC ACC 609.4, GRAB BARS SHALL BE
 INSTALLED IN HORIZONTAL POSITION 33 INCHES MINIMUM/36
 INCHES MAXIMUM ABOVE FINISHED FLOOR TO TOP OF THE
 GRIPPING SURFACE, NOT TO CENTER. PER WPB FBC 107.2.1,
 CORRECT "TOILET ACCESSORY SCHEDULE" ON PLAN SHT. 2.1
 AND "TYPICAL TOILET ROOM ELEVATIONS" ON PLAN SHT. 3.1.
 2. 2ND REQUEST; RE: "TYPICAL TOILET ROOM ELEVATIONS" ON
 PLAN SHT. 3.1.
  
 A. WATER CLOSET SHALL BE 16 INCHES MINIMUM/18 INCHES
 MAXIMUM FROM SIDE WALL TO CENTER PER FBC ACC 604.2.
 B. REAR GRAB BAR SHALL BE 12 INCHES MINIMUM FROM CENTER
 OF WATER CLOSET TOWARD SIDEWALL AND 24 INCHES MINIMUM
 FROM CENTER OF WATER CLOSET TOWARD OPEN SIDE PER FBC
 ACC 604.5.2.
  
 3. 2ND REQUEST; PER WPB FBC 107. 2.1, PROVIDE PRODUCT
 SPECS FOR LINT INTERCEPTORS (SEE NOTE ON PLAN SHT.
 3.1).
 4. 2ND REQUEST; PER WPB FBC 107. 2.1, PROVIDE DETAIL OF
 WASHER CONNECTION TO INTERCEPTOR AND INTERCEPTOR
 DISCHARGE
 5. 2ND REQUEST; PER WPB FBC 107. 2.1, PROVIDE PIPING
 DETAIL FOR TYPICAL BANK OF LINT INTERCEPTORS. INCLUDE
 SIZING AND VENTING
 6. 2ND REQUEST; PER PROVIDE TEMPERED WATER FOR
 LAVATORY/LAVATORIES CONFORMING TO ASSE 1070 PER FBC PL
 416.5. PROVIDE SPEC FOR SAME PER WPB FBC 107.2.1.
 7. 2ND REQUEST; PER WPB FBC 107.2.1, PROVIDE A DETAIL
 FOR THE TWO (2) TANKLESS WATER HEATERS SHOWING PIPING
 AND VALVE ARRANGEMENT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 NEW GAS PLANS WERE NOT SUBMITTED FOR REVIEW AT THIS
 TIME
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060896 1242 PALM BEACH LAKES BLVD
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By jesmith Date 2019-07-02 Time 15:46 Rev Time 0.00
Received By jesmith Date 2019-07-02 Time 14:44 Sent To  
Notes
2019-07-02 15:46:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. OCCUPANT LOAD OF 18 IS LESS THAN 100? GROSS/1882 SQ.
 FT. SHOULD BE 19. FBC PL 403.2 REQUIRES TWO TOILET
 ROOMS. IF USING FBC EX ALTERATIONS LEVEL 2 SECTION 810
 TO JUSTIFY THE LACK OF THE SECOND TOILET ROOM, THEN
 PROVIDE DETAILED INFORMATION AND CALCULATIONS AS TO HOW
 THIS WOULD BE ACHEIVED AND STILL BE COMPLIANT.
 2. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN
 HORIZONTAL POSITION 33? MIN/36? MAXIMUM ABOVE FINISHED
 FLOOR TO TOP OF THE GRIPPING SURFACE, NOT TO CENTER.
 PER WPB FBC 107.2.1, CORRECT ?TOILET ACCESSORY
 SCHEDULE? ON PLAN SHT. 2.1 AND ?TYPICAL TOILET ROOM
 ELEVATIONS? ON PLAN SHT. 3.1.
 3. PER FBC ACC 604.7, TOILET PAPER HOLDERS SHALL BE
 INSTALLED 7?MINIMUM/9?MAXIMUM IN FRONT OF THE WATER
 CLOSET. PER WPB FBC 107.2.1, CORRECT ?TOILET ACCESSORY
 SCHEDULE? ON PLAN SHT. 2.1 AND ?TYPICAL TOILET ROOM
 ELEVATIONS? ON PLAN SHT. 3.1.
 4. RE: ?TYPICAL TOILET ROOM ELEVATIONS? ON PLAN SHT.
 3.1.
 5. WATER CLOSET SHALL BE 16?-18? FROM SIDE WALL TO
 CENTER PER FBC ACC 604.2.
 6. REAR GRAB BAR SHALL BE 12? MINIMUM FROM CENTER OF
 WATER CLOSET TOWARD SIDEWALL AND 24? MINIMUM FROM
 CENTER OF WATER CLOSET TOWARD OPEN SIDE PER FBC ACC
 604.5.2.
 7. FLUSH CONTROL SHALL BE LOCATED ON OPEN SIDE OF WATER
 CLOSET PER FBC ACC 604.6.
 8. FIXTURE SCHEDULE ON PLAN SHT. 3.1 REFERS TO TABLE
 604.3 FBC 2010 AND 2010 FBC 2517.5.1.1. WEST PALM BEACH
 HAS ADOPTED THE 2017 FLORIDA BUILDING CODES INCLUDING
 PLUMBING. THE SECTIONS INDICATED DO NOT MATCH UP TO THE
 2017 FBC PL. PLEASE CLARIFY PER WPB FBC 107.2.1.
 10.PER WPB FBC 107. 2.1, PROVIDE A PLAN VIEW OF ALL
 EXISTING AND ADDED SANITARY PIPING AND WATER
 DISTRIBUTION. AND WATER. CLARIFY EXISTING AND ADDED.
 11.SEE WASTE RISER DIAGRAM ON PLAN SHT. 3.1.
 A. A VENT IS REQUIRED ON THIS SYSTEM WHICH SHALL PIPE
 TO THE EXTERIOR OF THE BUILDING PER FBC PL 904.1.
 REQUIRED VENT MAY BE USED AS THE DRY VENT FOR THE
 SYSTEM IF SYSTEM COMPLIES WITH FBC PL
 B. INTERCEPTORS WITH A WATER SEAL TRAP SHALL NOT
 DISCHARGE DIRECTLY INTO ANOTHER TRAP (DOUBLE TRAPPED)
 PER FBC PL 1002.1.
 12.PER WPB FBC 107. 2.1, PROVIDE PRODUCT SPECS FOR LINT
 INTERCEPTORS (SEE NOTE ON PLAN SHT. 3.1).
 13.PER WPB FBC 107. 2.1, PROVIDE DETAIL OF WASHER
 CONNECTION TO INTERCEPTOR AND INTERCEPTOR DISCHARGE
 14.PER WPB FBC 107. 2.1, PROVIDE PIPING DETAIL FOR
 TYPICAL BANK OF LINT INTERCEPTORS. INCLUDE SIZING AND
 VENTING
 15.PROVIDE TEMPERED WATER FOR LAVATORY/LAVATORIES
 CONFORMING TO ASSE 1070 PER FBC PL 416.5. PROVIDE SPEC
 FOR SAME PER WPB FBC 107.2.1.
 16.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE TWO
 (2) TANKLESS WATER HEATERSSHOWING PIPING AND VALVE
 ARRANGEMENT.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060896 1242 PALM BEACH LAKES BLVD
  