| 2019-06-21 05:23:31 | 1) A "REVISED" GAS PLAN HAS BEEN SUBMITTED TO SHOW |
| | FUTURE GAS APPLIANCES AND THE BTU LOAD. THIS IS THE |
| | EXACT SAME DRAWING THAT WAS SUBMITTED WITH THE ORIGINAL |
| | PERRMIT FOR THE GENERATOR, SO WHAT WAS REVISED? THE |
| | PIPING, PIPE SIZES FOR THESE FUTURE APPLIANCES AND THE |
| | FURTHEST OUTLET ( IF IT IS LONGER THAN 30 FEET) MUST BE |
| | SHOWN ON THE GAS PLAN. |
| | 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| | FBC-R SEC. G2413.4.1, G2413.4.2. |
| | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED & ALL |
| | PIPE SIZES.2017 FBC- RES. SEC. G 2413.1, G2412.8. |
| | 4) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017 |
| | FBC-FUEL GAS SEC. 410.2 (7). |
| | 5) EACH FUTURE LINE SHALL HAVE A SHUTOFF VALVE, THE |
| | REGULATOR, A UNION WITHIN ONE FOOT UPSTREM OR |
| | DOWNSTREAM OF THE REGULATOR, AND A NIPPLE AND A HARDCAP |
| | INSTALLED ON THE OUTLET OF THE REGULATOR. NOTE THIS ON |
| | THE PLANS. |
| | |
| | NOTE** A SEPARATE GAS PERMIT WILL BE REQUIREDD FOR THE |
| | INSTALLATION OF THE "FUTURE " GAS APPLIANCES AND |
| | COMBUSTION AIR CALCULATIONS WILL BE REQURED FOR THE |
| | COOKTOP & DRYER. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |