| Plan Review Stops For Permit 19060855 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-08-13 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-08-13 |
Time |
18:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-07-19 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-07-19 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-08-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-08-07 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-08-07 |
Time |
08:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-17 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-17 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-08-13 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-07-30 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-07-19 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-06-21 |
Time |
10:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-13 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-09 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-07-08 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-07-08 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2019-07-08 16:03:02 | PLUMBING 1ST REVIEW**DENIED** | | | | | | | | | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | | ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD | | | CALCULATION IS NO LONGER ALLOWED TO BE USED IN | | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | | FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS | | | MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING | | | SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER, | | | FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT | | | THE PUMP. | | | | | | 2) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR | | | THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-08-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-08-07 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-08-07 |
Time |
08:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-17 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-17 |
Time |
07:16 |
Sent To |
|
|
| Notes |
| 2019-07-17 07:16:08 | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | | VERIFICATION. THE DIGITAL SIGNATURE MUST INCLUDE THE | | | STATEMENT "SIGNED AND SEALED" AS PER FAC 61G15-23.004. | | | PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-09 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-08-09 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-08-09 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2019-08-09 12:36:32 | PROVISOS | | | | | | 1. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR | | | SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS | | | BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE | | | RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED | | | (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS | | | OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE | | | GRADE. | | | | | | 2. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH | | | A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING | | | GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES | | | PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. | | | | | | 3. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE | | | POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT | | | NOT ONTO ADJACENT PROPERTIES. | | | | | | _______________________________________________________ | | | _____________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | P: 561.822.1448 | E: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-07-16 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-07-16 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-07-16 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2019-07-16 15:42:32 | PROVISOS | | | | | | 1. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR | | | SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS | | | BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE | | | RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED | | | (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS | | | OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE | | | GRADE. | | | | | | 2. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH | | | A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING | | | GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES | | | PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. | | | | | | 3. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE | | | POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT | | | NOT ONTO ADJACENT PROPERTIES. | | | | | | _______________________________________________________ | | | _____________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | P: 561.822.1448 | E: [email protected] |
|
|