Plan Review Details - Permit 19060842
Plan Review Stops For Permit 19060842
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-07 Cont ID  
Sent By jwitmer Date 2019-08-07 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2019-08-07 Time 12:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By jwitmer Date 2019-07-03 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2019-07-01 Time 13:07 Sent To  
Notes
2019-07-03 11:37:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060842
 ADD: 534 DATURA ST.
 CONT: P DELTA CONSTRUCTION LLC
 TEL: 786-395-2534
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 03/2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE COPYRIGHTED PLANS, SIGNED
 AND SEALED BY A REGISTERED ENGINEER OF FLORIDA AND
 WOULD REQUIRE THE PLANS TO BE SIGNED AND SEALED PLANS.
 NO ONE BUT THE ENGINEER OF RECORD CAN DRAW ON THEIR SET
 OF PLANS AND THEN THEY (THE ENGINEER) SIGN AND DATE THE
 CHANGES MADE.
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 2) THE PLANS SUBMITTED HAVE BEEN REPRODUCED AND REDUCED
 IN SIZE. THE ORIGINAL PLANS WERE THE MINIMUM SIZE THE
 CITY ACCEPTS 1/8 INCH SCALE DRAWINGS. THE SUBMITTED
 PLANS ARE REDUCED AND ACCEPTABLE FOR RECORD RETENTION.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.3
 QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 3A) WE NEED A DESIGNER OF RECORD TO EXPLAIN WHY A WALL
 IS BEING REMOVED FROM WHAT APPEARS TO BE AN ENCLOSED
 STAIR WAY. THIS STAIRWAY IS WHAT APPEARS TO BE THE ONLY
 STAIRWAY FOR ROOMS 403 & 405 ON THE 4TH FLOOR? SHOW
 COMPLIANCE WITH 2017 FBC-B TABLE 1006.3.2(1).
  
 3B) DOES THIS BUILDING HAVE A FIRE SPRINKLER?
  
 4) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 SECTION 503)
 HEIGHT OF BUILDING IN STORIES
 FIRE SPRINKLERS? REQUIRED?
  
 5) UNDER THE EXISTING BUILDING CODE WHICH METHOD OF
 COMPLIANCE WAS USED IN THE DESIGN OF THESE PLANS. 2017
 EXISTING BUILDING CODE THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT.
  
 6) CREATION OR EXTENSION OF NONCONFORMITY. 2017
 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-09 Cont ID  
Sent By jleahy Date 2019-07-09 Time 15:50 Rev Time 0.00
Received By jleahy Date 2019-07-09 Time 15:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-26 Cont ID  
Sent By pleduc Date 2019-07-26 Time   Rev Time 0.00
Received By pleduc Date 2019-07-26 Time 12:14 Sent To  
Notes
2019-07-26 12:16:56THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THE FIRE INSPECTOR SHALL VERIFY LOCATIONS OF FIRE
 SPRINKLER HEADS AND FIRE ALARM DEVICES TO THE NOTED
 LOCATION OF THE PLANS.
  
 ENSURE LOCATIONS ARE ACCURATE AND/OR PROVIDE REVISIONS
 SHOWING ACTUAL LOCATIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 15:05 Sent To  
Notes
2019-06-20 15:12:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PALNS ARE TOO SMALL AND UNREADABLE AND
 THERE INSUFFICIENT DETAIL TO MAKE A DETEMINATION OF
 FIRE CODE COMPLIANCE.
  
 PLEASE PROVIDE LARGER READABLE PLANS AND PROVIDE
 GREATER DETAIL.
  
  
 2) DOES THIS BUIDLIGN HAVE FIRE SPRINKLERS AND FIRE
 ALARMS.
  
 PLEASE PROVIDE FS & FA DEVICE LOCATION AND PROVIDE AN
 APPLICABLE NOTE STATING ALL FS & FA WORK SHALL BE DONE
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 3) THERE IS INDICATIONS OF MOVING WASHER AND DRYER.
 PLEASE PROVIDE DRYER VENT DETAIL, INCLUDING VENT
 DIMENSIONS THAT MEET THE REQUIREMENTS OF THE DRYER
 MANUFACTURER.
  
 DRYER SPECIFICATIONS SHEETS NEED TO BE PROVDED TO
 ENSURE REQUIREMENTS ARE MET.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-08-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-24 Time 14:14 Sent To  
Notes
2019-07-25 14:14:18B30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-18 Time 11:36 Sent To  
Notes
2019-06-19 11:36:59B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-07 Cont ID  
Sent By jwitmer Date 2019-08-07 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2019-08-07 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-09 Cont ID  
Sent By ccole Date 2019-07-09 Time 16:33 Rev Time 0.00
Received By ccole Date 2019-07-09 Time 16:33 Sent To I
Notes
2019-07-09 16:52:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060842
 7/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MECHANICAL FLOOR PLAN THAT SHOWS
 THE NEW ROOM LOCATION OF THE DRYERS, AND PLEASE
 IDENTIFY THE ROOM OR SPACE WHERE THEY ARE LOCATED-
 SECTION 107.2.1 WPB.
  
 A) INDICATE ON THE PLAN THE MAKES AND MODELS OF THE
 DRYERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION 504.1 FBC M.
  
 B) PROVIDE ON THE PLAN A DRYER EXHAUST PLAN THAT
 INDICATES THE TYPE AND SIZES OF EXHAUST DUCT(S), AND
 SHOWS THE EXHAUST DUCT RUN(S) FROM THE CONNECTIONS AT
 THE DRYERS TO THE OUTLET TERMINAL(S) OR SHAFT. PLEASE
 INCLUDE THE TOTAL LENGTH MEASUREMENT OF THE EXHAUST
 DUCT RUN(S)- SEE SECTIONS 504.4, 504.6, 504.8.1,
 504.8.4, 504.9, AND 5-04.10 INCLUDING ALL SUBSECTIONS
 FOR CODE COMPLIANCE REQUIREMENTS.
  
 C) PLEASE NOTE THAT ALL PLANS SHALL BE ORIGINAL PLANS
 DRAWN AT A MINIMUM 1/8" SCALE, AND SHALL EITHER BEAR
 THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL OF
 RECORD, OR THE THE SIGNATURE OF THE CONTRACTOR OF
 RECORD- SECTION 107.2.1 WPB. THE SUBMITTED UNSIGNED AND
 REDUCED IN SIZE COPIED PLANS ARE NOT ACCEPTABLE FOR
 REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-07 Cont ID  
Sent By jwitmer Date 2019-08-07 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2019-08-07 Time 12:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By jesmith Date 2019-07-02 Time 10:57 Rev Time 0.00
Received By jesmith Date 2019-07-02 Time 10:21 Sent To  
Notes
2019-07-02 10:56:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 PLUMBING COMMENTS: DENIED
 1. A REVIEW OF PAST PERMITTED PLANS DOES NOT SHOW AN
 EXISTING DRYER OR AN EXISTING LAUNDRY ROOM. IT APPEARS
 THE DRYER WAS INSTALLED WITHOUT A PERMIT. INCLUDE IN
 PERMIT APPLICATION FOR NEW WORK.
 2. AS A DRYER IS USUALLY ACCOMPANIED BY A WASHER, IT
 SEEMS UNLIKELY THAT PLUMBING WOULD NOT BE INVOLVED AND
 NONE IS NOTED. PER WPB FBC 107.2.1, PROVIDE DETAILED
 PLAN SHOWING IMPACTED ROOMS AND ANY AND ALL LAUNDRY
 FACILITIES, BOTH EXISTING AND AS PROPOSED.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060842 534 DATURA ST
  
  
  