| 2019-07-22 18:40:20 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | EXTERIOR DOOR IS INCOMPLETE. THERE IS NO FL# OR NOA |
| | NUMBER LINKED TO THE DRAWINGS. SUBMIT COVERSHEET WITH |
| | THE PRODUCT APPROVAL NUMBERS AND ANY OTHER APPROVAL |
| | DOCUMENTS FOR THE MASONITE DOOR. FBC 107.3.4 - PROVIDE |
| | TWO SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH |
| | ARE REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. |
| | |
| | 2) GENERAL NOTE 3 ON SHEET 1 OF THE DRAWINGS FOR THE |
| | MASONITE OUTSWING DOOR STATES THAT AN IMPACT PROTECTION |
| | SYSTEM IS REQUIRED FOR THIS DOOR. SUBMIT PRODUCT |
| | APPROVALS FOR THE STORM PROTECTION DEVICES THAT WILL BE |
| | INSTALLED. FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN |
| | INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM |
| | PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES, |
| | TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL |
| | LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO |
| | GLASS AND THE APPLICABLE SECTION NUMBER FROM THE |
| | INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE |
| | CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF |
| | THE RELATED FORMS INCLUDING |
| | THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| | DEVICES. |
| | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| | |
| | 3) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY CONSERVATION FORM R402-2017. FBC ENERGY |
| | CONSERVATION SECTION R103.1.1.2 |
| | |
| | 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |