Plan Review Details - Permit 19060808
Plan Review Stops For Permit 19060808
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By ppetty Date 2019-07-22 Time 13:29 Rev Time 0.00
Received By ppetty Date 2019-07-22 Time 13:28 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-02 Cont ID  
Sent By ppetty Date 2019-07-02 Time 11:42 Rev Time 0.00
Received By ppetty Date 2019-07-02 Time 11:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By pleduc Date 2019-07-19 Time   Rev Time 0.00
Received By pleduc Date 2019-07-19 Time 13:48 Sent To E
Notes
2019-07-19 13:51:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) REVIEW AND ENSURE COMPLIANCE WITH NFPA 13; 6.9.1
  
 6.9 WATERFLOW ALARM DEVICES.
 6.9.1 GENERAL. WATERFLOW ALARM DEVICES SHALL BE LISTED
 FOR THE
 SERVICE AND SO CONSTRUCTED AND INSTALLED THAT ANY FLOW
 OF WATER
 FROM A SPRINKLER SYSTEM EQUAL TO OR GREATER THAN THAT
 FROM A
 SINGLE AUTOMATIC SPRINKLER OF THE SMALLEST K-FACTOR
 INSTALLED ON
 THE SYSTEM WILL RESULT IN AN AUDIBLE ALARM ON THE
 PREMISES WITHIN
 5 MINUTES AFTER SUCH FLOW BEGINS AND UNTIL SUCH FLOW
 STOPS.
  
  
 2) PROVIDE MANUFACTURES SPECIFICATION SHEETS FOR THE
 FIRE INSPECTOR REVIEW ON FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-21 Cont ID  
Sent By sathomas Date 2019-06-21 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-06-21 Time 00:00 Sent To M
Notes
2019-06-21 14:20:28PROVISO:
  
 1. NFPA 13:6.9.1 GENERAL. "WATERFLOW ALARM APPARATUS
 SHALL BE LISTED FOR THE SERVICE
 AND SO CONSTRUCTED AND INSTALLED THAT ANY FLOW OF WATER
 FROM A SPRINKLER
 SYSTEM EQUAL TO OR GREATER THAN THAT FROM A SINGLE
 AUTOMATIC SPRINKLER OF
 THE SMALLEST ORIFICE SIZE INSTALLED ON THE SYSTEM WILL
 RESULT IN AN AUDIBLE ALARM ON THE PREMISES WITHIN5
 MINUTES
 AFTER SUCH FLOW BEGINS AND UNTIL SUCH FLOW STOPS.
  
 2. MANUFACTURER'S DATA SHEETS TO BE PROVIDED UPON
 INSPECTION.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-22 Cont ID  
Sent By cmontell Date 2019-07-22 Time 14:46 Rev Time 0.00
Received By cmontell Date 2019-07-22 Time 14:45 Sent To  
Notes
2019-07-18 15:29:09RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-02 Cont ID  
Sent By ppetty Date 2019-07-02 Time 11:43 Rev Time 0.00
Received By ppetty Date 2019-06-18 Time 11:16 Sent To  
Notes
2019-06-19 11:16:13ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By cmontell Date 2019-07-22 Time 14:45 Rev Time 0.00
Received By cmontell Date 2019-07-22 Time 14:45 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By ccole Date 2019-07-02 Time 09:10 Rev Time 0.00
Received By ccole Date 2019-07-02 Time 09:10 Sent To E
Notes
2019-07-02 09:39:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060808
 7/2/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD- REGINA BOBO-JACKSON P.E.
 SHALL PROVIDE A RAISED OR INK SEAL AND WET SIGNATURE ON
 EACH OF THE FIRE ALARRM PLANS BEARING HER TITLE BLOCK-
 REFER TO FL. STATUTE 471.005 AND SECTION 61G15-23.002
 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  