| 2019-06-26 13:13:40 | 06/26/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT SPECIFICATION AND SHOW ON DOCUMENTATION THAT |
| | THE GAS POOL HEATER MEETS THE MINIMUM REQUIRED |
| | EFFICIENCY AS REQUIRED BY THE 2017 FBC-ENERGY |
| | SEC.R403.10.4. ALL GAS AND SPA HEATERS SHALL HAVE A |
| | MINIMUM THERMAL EFFICIENCY OF 82 % FOR HEATERS |
| | MANUFACTURED ON OR AFTER APRIL 16, 2013, WHEN TESTED IN |
| | ACCORDANCE WITH ANSI Z 21.56. |
| | 2. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| | PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| | LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| | PRIOR TO FINAL INSPECTION. A RPZ IS REQUIRED AT METER |
| | AND A PVB REQUIRED FOR POOL FILL. PLEASE ADD NOTES ON |
| | PLANS AND IF OR BY OTHER! |
| | 3. ON GENERAL NOTES ITEM 15 IS REFERRING TO 5TH EDITION |
| | 2014, PLEASE CHANGE TO CURRENT CODE, WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |