Plan Review Details - Permit 19060746
Plan Review Stops For Permit 19060746
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-17 Cont ID  
Sent By fgiaquin Date 2019-09-17 Time 06:44 Rev Time 0.00
Received By fgiaquin Date 2019-09-17 Time 06:18 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-13 Cont ID  
Sent By fgiaquin Date 2019-08-13 Time 07:24 Rev Time 0.00
Received By fgiaquin Date 2019-08-13 Time 06:50 Sent To I
Notes
2019-08-13 07:22:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AS PER LAST PLAN REVIEW COMMENTS NO LOAD CALCULATION
 HAS BEEN PROVIDED SHOWING EDITION THE EXISTING LOAD AND
 THE ADDITION OF NEW RECEPTACLES TO PANEL "LA". LOAD
 CALCULATION PROVIDED APPEARS TO BE A RESIDENTIAL LOAD
 CALC FOR A UNIT AND A 200AMP SERVICE AT 220V??? PROVIDE
 CORRECTION. FBC 107.2.1 NEC 220.
  
 2. AS PER LAST PLAN REVIEW COMMENTS PLAN IS NOT SIGNED
 BY ELECTRICAL CONTACTOR QUALIFIER. (EVERY PAGE) .
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC
 107.1
  
 3. AS PER LAST PLAN REVIEW COMMENTS NOTHING WAS
 ADDRESSED IN RELATION TO DERATING CONDUCTORS. 1-1/2''
 CONDUITS SHOWS 12 CURRENT CARRYING CONDUCTORS, AFTER
 DERATING AT 50% #6 WIRE IS RATED AT 37.5 AMPS AND MAX
 OCP ALLOWED WOULD BE 40 AMPS PER NEC 240.4B. SPECS
 SHEET PROVIDED CALLS FOR MINIMUM CIRCUIT AMPACITY OF
 40AMP AND OCP OF 50AMPS. PROVIDE CORRECTION.
  
 4. PROVIDE SPEC SHEETS FOR PRODUCT APPROVAL SHOWING UL
 LISTING OR OTHER NRTL LISTING. FBC 107.2.1 NEC
 90.7,110.2,110.3B
  
 5. SHOW COMPLIANCE FOR ADA IN REFERENCE TO CAR CHARGERS
 AND LOCATIONS.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By fgiaquin Date 2019-06-25 Time 06:54 Rev Time 0.00
Received By fgiaquin Date 2019-06-25 Time 05:48 Sent To I
Notes
2019-06-25 06:53:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOT ENOUGH INFORMATION ON PLAN. PLEASE PROVIDE PLAN
 INCLUDING GARAGE LAYOUT AND ACTUAL LOCATION OF NEW
 JBOXES, NEW RECEPTACLES, AND ELEC ROOM. FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED (EVERY
 PAGE) BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 3. IS PANEL 3 PHASE? WHAT IS VOLTAGE OF PANEL? LOAD
 CALC IS DIVDED BY 220 FOR VOLTAGE. VOLTAGE IS BELIEVED
 TO BE 208. NEC 220, FBC 107.2.1
  
 4. PROVIDE ACCURATE LOAD CALCULATION PROVIDING ALL
 LOADS BOTH NEW AND EXISTING. NEW RECEPTACLES LOADS ARE
 NOT SHOWN IN LOAD CALCULATION.
  
 5. ARE NEW RECEPTACLES FOR CAR CHARGERS? PLEASE PROVIDE
 MORE INFORMATION. FBC 107.2.1
  
 6. 8, #6'S AND 4, #8 CONDUCTORS SHOWN IN ONE 1-1/2
 CONDUIT. TOTAL OF 12 CURRENT-CARRYING-CONDUCTORS. AFTER
 ADJUSTMENT FACTORS ARE APPLIED PER NEC 310.15B3A THE
 CONDUCTORS ARE NOT SUFFICENT FOR A 50AMP OCP PROTECTED
 CIRCUIT. YOU MUST DERATE CONDUCTORS @ 50% @ 90 DEGREES
 CELCIUS
  
 #6 @ 90 DEGREES IS RATED AT 75A. 75X50%= 37.5AMPS.
 CONDUCTOR RATING MUST MATCH OCP RATING PER NEC 210.3.
  
 #8 @ 90 DEGREES IS RATED AT 55A. 55X50%= 22.5AMPS.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-17 Cont ID  
Sent By fgiaquin Date 2019-09-17 Time 06:44 Rev Time 0.00
Received By fgiaquin Date 2019-09-12 Time 13:53 Sent To  
Notes
2019-09-13 13:53:50RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-13 Cont ID  
Sent By fgiaquin Date 2019-08-13 Time 07:24 Rev Time 0.00
Received By fgiaquin Date 2019-08-09 Time 14:51 Sent To  
Notes
2019-08-12 14:51:22RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By fgiaquin Date 2019-06-25 Time 06:54 Rev Time 0.00
Received By fgiaquin Date 2019-06-17 Time 13:09 Sent To  
Notes
2019-06-18 13:09:49ROUTED TO ELECTRICAL INBOX