| 2019-06-21 13:42:35 | THE FOLLOWING COMMENTS WERE SUBMITTED BY SANDRA THOMAS, |
| | FIRE INVESTIGATOR, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | 1. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. |
| | |
| | 2. NO ADDRESS PROVIDED ON THE PLAN TITLEBLOCK. |
| | |
| | 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 4. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | 5.PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| | TRAVEL ETC. |
| | |
| | 6.WHAT IS CURRENT OCCUPANCY TYPE, AND WHAT WILL THE |
| | PROPOSED OCCUPANCY BE AFTER RENOVATION? |
| | |
| | 7. ALL LIFE SAFETY ASPECTS OF THE PROPOSED PROJECT |
| | SHALL COMPLY WITH THE CURRENT EDITION OF THE 2015 |
| | FLORIDA FIRE PREVENTION CODE AND ALL APPLICABLE CODES |
| | CONTAINED THEREIN. 1. BUILDING PLANS, FLOOR PLANS, |
| | ELEVATIONS AND/OR DETAILED DRAWINGS WERE NOT CONTAINED |
| | IN THE SUBMITTAL AND CANNOT BE COMMENTED ON. |
| | |
| | 8.THE LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE ALARM, |
| | SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. |
| | |
| | 9.ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | 10.PROVIDE DRAWING NOTE INDICATING, FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | S. THOMAS |
| | 561-804-4728 |