| Plan Review Stops For Permit 19060691 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-09 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-22 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2019-09-09 11:17:55 | PLANS FOR ADDITION ON-SITE UNDER PERMIT #18051483. CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-27 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-27 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2019-06-27 15:38:03 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | | EDITION | | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | 1. PROVIDE TWO COPIES OF THE MOST RECENT SURVEY. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 2. PROVIDE SOILS INVESTIGATION REPORT PER DESIGNER OF | | | RECORD. | | | R401.4 SOIL TESTS. | | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. | | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | | APPROVED METHOD. | | | | | | 3. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF. | | | | | | 4. PROVIDE AN ACCURATELY COMPLETED ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | | (MANDATORY). | | | | | | 5. ROOFING PERMIT REQUIRED. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 6. PROVIDE PRODUCT APPROVALS FOR ALL EXTERIOR DOORS, | | | WINDOWS AND ROOFING SYSTEM COMPONENTS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | 7. ALARMS REQUIRED ON NEW BEDROOM DOORS OR VERIFY | | | KIDDIE FENCE INSTALLED AT POOL PERIMETER. | | | R4501.17.1.9 | | | WHERE A WALL OF A DWELLING SERVES AS PART OF THE | | | BARRIER, ONE OF THE FOLLOWING SHALL APPLY: | | | 1.ALL DOORS AND WINDOWS PROVIDING DIRECT ACCESS FROM | | | THE HOME TO THE POOL SHALL BE EQUIPPED WITH AN EXIT | | | ALARM COMPLYING WITH UL 2017 THAT HAS A MINIMUM SOUND | | | PRESSURE RATING OF 85 DBA AT 10 FEET (3048 MM). ANY | | | DEACTIVATION SWITCH SHALL BE LOCATED AT LEAST 54 INCHES | | | (1372 MM) ABOVE THE THRESHOLD OF THE ACCESS. SEPARATE | | | ALARMS ARE NOT REQUIRED FOR EACH DOOR OR WINDOW IF | | | SENSORS WIRED TO A CENTRAL ALARM SOUND WHEN CONTACT IS | | | BROKEN AT ANY OPENING. | | | | | | 8. APPLICATION INDICATES A NEW SITE WALL WILL BE | | | INSTALLED. SHOW LOCATION OF PROPOSED WALL ON SITE PLAN. | | | PROVIDE STRUCTURAL DETAILS OF WALL. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-09-19 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-09-19 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-09-19 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-08-07 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-08-07 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-08-07 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2019-08-07 13:15:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PANEL SCHEDULES PROVIDED ARE FOR PANEL MDP, SUBPANEL | | | 1, AND SUBPANEL 2. THE RISER DIGRAM SHOWS A TRANSFER | | | SWITCH AND THE SUBPANEL 1, SUBPANEL 2, AND POOL | | | SUBPANEL. SUBPANEL 1 IS SHOWN AS 100 AMP IN RISER, AND | | | AS 70 AMP IN PANEL SCHEDULE. PROVIDE ACCURATE RISER | | | DIAGRAM AND FEEDERS, CORRECT DISCREPANCIES. NEC 215.5, | | | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 2. PROVIDE LOCATION OF SERVICE AND MAIN | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-20 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-20 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2019-06-20 14:49:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PANEL SCHEDULES PROVIDED ARE FOR PANEL MDP, SUBPANEL | | | 1, AND SUBPANEL 2. THE RISER DIGRAM SHOWS A TRANSFER | | | SWITCH AND THE SUBPANEL 1, SUBPANEL 2, AND POOL | | | SUBPANEL. SUBPANEL 1 IS SHOWN AS 100 AMP IN RISER, AND | | | AS 70 AMP IN PANEL SCHEDULE. PROVIDE ACCURATE RISER | | | DIAGRAM AND FEEDERS, CORRECT DISCREPANCIES. NEC 215.5, | | | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 2. SUBPANEL 1 IS SHOWN AS BEING FED WITH # 6 WIRE, | | | WHICH HAS AN AMPACITY OF 65 AMPS AT 75 DEGREE | | | TERMINALS. THIS WIRE IS CURRENTLY OVERLOADED AS SHOWN | | | WITH 69 AMPS ON B PHASE. PROVIDE LOAD CALCULATION FOR | | | SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM | | | CAPACITY OF SERVICE IS ADEQUATE. PROVIDE CORRECTION. | | | NEC 215.2 | | | 3. SUBPANEL 1 IS SHOWN AS BEING LOCATED IN A BATHROOM, | | | WHICH IS A CODE VIOLATION. PROVIDE CORRECTION. NEC | | | 240.24(E); FBC RE E3705.7 | | | 4. SUBPANEL 2 SHOWS A LOAD OF 20 AMPS FOR THE DRYER, | | | BUT THERE IS NO LOAD INCLUDED IN THE LOAD CALCULATION | | | FOR THE DRYER. PROVIDE CORRECTION. NEC 220; FBC RE | | | E3602.2 | | | 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING | | | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS | | | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC | | | 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2019-06-18 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-06-18 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-06-18 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2019-06-18 11:00:43 | A GAS PLAN AND PERMIT WILL BE REQUIRED AS THE LOCATION | | | FOR THE TANKLESS WATER HEATER IS HWERE THE NEW TOILET | | | ROOM IS ACCORING TO PERMIT # 18051483. | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-09-25 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-09-25 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-09-11 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-09 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-07-30 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-27 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-14 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-08-22 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-22 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2019-08-22 09:00:48 | MU-2019-021262-0000. CT |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-27 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-27 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2019-06-27 15:13:36 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-09-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-24 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-24 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-09 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-22 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2019-09-09 11:18:23 | PROVIDE 2ND PLAN PAGE. CT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-27 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-27 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2019-06-27 15:08:34 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | | EDITION | | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON | | | RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. | | | | | | 1. PROVIDE A MECHANICAL PLAN. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 2. PROVIDE AN ACCURATELY COMPLETED ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | | (MANDATORY). | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2019-06-18 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-06-18 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-06-18 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-09 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-22 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-27 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-27 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2019-06-27 15:12:50 | BUILDING PLAN REVIEW - ROOFING | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM | | | COMPONENTS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-09-25 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-09-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-09-25 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-08-09 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-08-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-08-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-08-09 09:39:57 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE VALUE OF THE CONSTRUCTION ($168,000.00) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($134,567.00) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. [6/21/19 REPEAT | | | COMMENT] | | | | | | | | | NOTES: | | | | | | * SPOKE TO GC RICK FERRER ON 8/9/19. CLARIFIED THAT THE | | | PROPOSED SITE WALL HAS BEEN ELIMINATED FROM THE PLAN | | | PER PROPERTY OWNER'S REQUEST. IF LANDSCAPE PLAN IS | | | SUBMITTED PRIOR TO THE COMPLETION OF THE REVIEW CYCLE, | | | AND EXISTING LANDSCAPING IS FOUND TO BE SUFFICIENT, | | | ZONING WILL CHANGE STATUS. | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPE. | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-06-21 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-06-21 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-06-21 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2019-06-21 09:57:22 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) NO SURVEY WAS PROVIDED WITH THE PERMIT SUBMITTAL. | | | AN UPDATED SURVEY OF THE PROPERTY IS REQUIRED AS PART | | | OF THE PERMIT. PLEASE PROVIDE. | | | | | | 2.) SHOW REAR SETBACK FROM THE PROPOSED NEW MASTER | | | BEDROOM ADDITION TO THE REAR PROPERTY LINE. [ZLDR | | | S.94-72(A)(2)] | | | | | | 3.) CLEARLY SHOW THE LOCATION OF THE PROPOSED NEW SITE | | | WALL IN THE SITE PLAN (SHEET SP1). THE PROPOSED WALL | | | CANNOT EXCEED 4 FT. IN HEIGHT WITHIN THE REQUIRED FRONT | | | SETBACK (AREA WITHIN THE FIRST 25 FT. OF THE FRONT LOT | | | LINE, ALHAMBRA PLACE) AND 6 FT. WITHIN THE SIDE AND | | | REAR SETBACKS. [ZLDR S.94-302(B)] | | | | | | 4.) THERE IS A NOTATION IN THE SITE PLAN "NEW 5'-0" | | | A.F.G. HIGH WALL," BUT DOES NOT SEEM TO BE POINTING TO | | | ANY WALL IN THE PLAN. PLEASE CLARIFY. | | | | | | 5.) THE VALUE OF THE CONSTRUCTION ($168,000.00) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($134,567.00) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPE AND SITE | | | WALL | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|