Plan Review Details - Permit 19060678
Plan Review Stops For Permit 19060678
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 11:35 Rev Time 0.00
Received By dbattles Date 2019-08-27 Time 11:35 Sent To  
Notes
2019-09-06 11:54:11PROVISO:
 PERMIT FOR NEW STAIRS AND FULL REMODEL WORK TO BE
 PROVIDED, APPROVED AND FINAL INSPECTIONS COMPLETED
 PRIOR TO ANY OCCUPANCY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 14:34 Rev Time 0.00
Received By dbattles Date 2019-06-21 Time 14:34 Sent To  
Notes
2019-06-21 14:37:03BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19060678
 REVIEWED: JUNE 21, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[R] = FBC RESIDENTIAL
  
 105.2 WORK EXEMPT FROM PERMIT.
 BUILDING PERMITS ARE NOT REQUIRED FOR REPLACEMENT OR
 REPAIR WORK HAVING VALUE OF LESS THAN $1,000.00,
 PROVIDING, HOWEVER, THAT SUCH WORK WILL NOT ADVERSELY
 AFFECT THE STRUCTURAL INTEGRITY, FIRE RATING, EXIT
 ACCESS OR EGRESS REQUIREMENTS.
  
 USUALLY REPAIRS (AS EXCEMPT FROM ABOVE) ARE DONE
 WITHOUT A PERMIT UNLESS THEY ARE STRUCTURAL UNIQUE.
 STAIRS ARE OF COURSE OF STRUCTURAL IMPORTANCE SO I CAN
 SEE WHY A PERMIT WOULD BE APPLIED FOR.
 HOWEVER, THE DRAWING PROVIDED LACKS DETAILS TO SHOW HOW
 IT WOULD MEET CODES OR BE STRUCTURALLY CONNECTED.
  
 IS THIS THE EXTERIOR STAIR AT REAR STRUCTURE?
 PLEASE PROVIDE SURVEY OR SITE PLAN TO SHOW LOCATION OF
 STAIRS IN PLAN VIEW.
  
 IF THE STAIR IS BEING REPLACED THEN PLEASE REVIEW THE
 CODE SECTIONS BELOW THAT SHOULD BE INCORPORATED INTO
 THE DESIGN.
  
 311.7.8.3 FBC[R] GRIP-SIZE. REQUIRED HANDRAILS SHALL BE
 OF ONE OF THE FOLLOWING TYPES OR PROVIDE EQUIVALENT
 GRASPABILITY.
 1. TYPE I. HANDRAILS WITH A CIRCULAR CROSS SECTION
 SHALL HAVE AN OUTSIDE DIAMETER OF NOT LESS THAN 11/ 4
 INCHES (32 MM) AND NOT GREATER THAN 2 INCHES (51 MM).
 IF THE HANDRAIL IS NOT CIRCULAR, IT SHALL HAVE A
 PERIMETER DIMENSION OF NOT LESS THAN 4 INCHES (102 MM)
 AND NOT GREATER THAN 61/4 INCHES (160 MM) WITH A CROSS
 SECTION OF DIMENSION OF NOT MORE THAN 21/4 INCHES (57
 MM). EDGES SHALL HAVE A RADIUS OF NOT LESS THAN 0.01
 INCH (0.25 MM).
 2. TYPE II. HANDRAILS WITH A PERIMETER GREATER THAN
 61/4 INCHES (160 MM) SHALL HAVE A GRASPABLE FINGER
 RECESS AREA ON BOTH SIDES OF THE PROFILE. THE FINGER
 RECESS SHALL BEGIN WITHIN A DISTANCE OF 3/4 INCH (19
 MM) MEASURED VERTICALLY FROM THE TALLEST PORTION OF THE
 PROFILE AND ACHIEVE A DEPTH OF NOT LESS THAN 5/16 INCH
 (8 MM) WITHIN 7/8 INCH (22 MM) BELOW THE WIDEST PORTION
 OF THE PROFILE. THIS REQUIRED DEPTH SHALL CONTINUE FOR
 NOT LESS THAN 3/8 INCH (10 MM) TO A LEVEL THAT IS NOT
 LESS THAN 13/4 INCHES (45 MM) BELOW THE TALLEST PORTION
 OF THE PROFILE. THE WIDTH OF THE HANDRAIL ABOVE THE
 RECESS SHALL BE NOT LESS THAN 11/4 INCHES (32 MM) AND
 NOT MORE THAN 23/4 INCHES (70 MM). EDGES SHALL HAVE A
 RADIUS OF NOT LESS THAN 0.01 INCH (0.25 MM).
  
 312.1.1 FBC[R] WHERE REQUIRED. GUARDS SHALL BE LOCATED
 ALONG OPEN-SIDED WALKING SURFACES, INCLUDING STAIRS,
 RAMPS AND LANDINGS, THAT ARE LOCATED MORE THAN 30
 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR
 GRADE BELOW AT ANY POINT WITHIN 24 INCHES (610 MM)
 HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. INSECT
 SCREENING SHALL NOT BE CONSIDERED AS A GUARD.
  
 312.1.2 FBC[R] HEIGHT. REQUIRED GUARDS AT OPEN-SIDED
 WALKING SURFACES, INCLUDING STAIRS, PORCHES, BALCONIES
 OR LANDINGS, SHALL BE NOT LESS THAN 36 INCHES (914 MM)
 IN HEIGHT AS MEASURED VERTICALLY ABOVE THE ADJACENT
 WALKING SURFACE OR THE LINE CONNECTING THE LEADING
 EDGES OF THE TREADS. EXCEPTIONS:
 1. GUARDS ON THE OPEN SIDES OF STAIRS SHALL HAVE A
 HEIGHT NOT LESS THAN 34 INCHES (864 MM) MEASURED
 VERTICALLY FROM A LINE CONNECTING THE LEADING EDGES OF
 THE TREADS.
 2. WHERE THE TOP OF THE GUARD SERVES AS A HANDRAIL ON
 THE OPEN SIDES OF STAIRS, THE TOP OF THE GUARD SHALL BE
 NOT LESS THAN 34
 INCHES (864 MM) AND NOT MORE THAN 38 INCHES (965 MM) AS
 MEASURED VERTICALLY FROM A LINE CONNECTING THE LEADING
 EDGES OF THE TREADS.
  
 312.1.3 FBC[R] OPENING LIMITATIONS. REQUIRED GUARDS
 SHALL NOT HAVE OPENINGS FROM THE WALKING SURFACE TO THE
 REQUIRED GUARD HEIGHT THAT ALLOW PASSAGE OF A SPHERE 4
 INCHES (102 MM) IN DIAMETER. EXCEPTIONS:
 1. THE TRIANGULAR OPENINGS AT THE OPEN SIDE OF STAIR,
 FORMED BY THE RISER, TREAD AND BOTTOM RAIL OF A GUARD,
 SHALL NOT ALLOW PASSAGE OF A SPHERE 6 INCHES (153 MM)
 IN DIAMETER.
 2. GUARDS ON THE OPEN SIDE OF STAIRS SHALL NOT HAVE
 OPENINGS THAT ALLOW PASSAGE OF A SPHERE 43/8 INCHES
 (111 MM) IN DIAMETER.
  
 303.8 FBC[R] EXTERIOR STAIRWAY ILLUMINATION. EXTERIOR
 STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT
 SOURCE LOCATED AT THE TOP LANDING OF THE STAIRWAY.
 EXTERIOR STAIRWAYS PROVIDING ACCESS TO A BASEMENT FROM
 THE OUTDOOR GRADE LEVEL SHALL BE PROVIDED WITH AN
 ARTIFICIAL LIGHT SOURCE LOCATED AT THE BOTTOM LANDING
 OF THE STAIRWAY.
  
 ALSO, SOME DETAILS SHOULD BE ADDED OF HOW STAIRWAY AND
 HANDRAIL ARE ATTACHED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 11:35 Rev Time 0.00
Received By dbattles Date 2019-08-23 Time 14:10 Sent To  
Notes
2019-08-23 14:10:56RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 14:34 Rev Time 0.00
Received By dbattles Date 2019-06-14 Time 07:50 Sent To  
Notes
2019-06-18 07:50:20BLDG <5K