Plan Review Details - Permit 19060677
Plan Review Stops For Permit 19060677
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-25 Cont ID  
Sent By rmcdouga Date 2019-09-25 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2019-09-25 Time 11:12 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-14 Cont ID  
Sent By rmcdouga Date 2019-08-14 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2019-08-14 Time 14:34 Sent To  
Notes
2019-08-14 14:32:272017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060677
 ADD: 4200 N. FLAGLER DR. RYBOVICH K DOCK
 CONT: BELLINGHAM MARINE
 TEL: 904-358-3362
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JULY 01/2019
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) NOT COMPLIED. THE SMALLER PLANS THAT WERE SUBMITTED
 ARE NOT TO SCALES THAT ARE SPECIFIED ON THE DRAWINGS.
 THE PLANS ARE NOT SIGNED AND SEALED AS REQUIRED BY FAC
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND
 SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MUST BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
 NOTE: ELECTRONIC OR DIGITAL SIGNATURES ARE ONLY
 ACCEPTABLE ON ELECTRONICALLY SUBMITTED PLANS.
  
 ORIGINAL COMMENT:
 THE SUBMITTED PLANS HAVE BEEN ENLARGED:
 2A) WITH THE SUBMITTED PLANS BEING ENLARGED THE SEAL IS
 OVER 3 INCHES IN DIAMETER, THE SIGNATURE IS NO LONGER
 AN ORIGINAL SIGNATURE, IT HAS BEEN COPIED. 61G15-23.002
 SEALS ACCEPTABLE TO THE BOARD.
 (2) SEALS, EMBOSSING SEALS AND DIGITALLY CREATED SEALS
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 SHALL BE OF A DESIGN SIMILAR TO THOSE SET FORTH IN
 SUBSECTIONS.
  
 2B) SHEET 1 OF 19 INDICATES AN ENGINEERING SCALE OF 1
 INCH = 50 FEET. THIS SCALE DOES NOT MEET THE
 REQUIREMENTS OF 107.2.1.3. QUALITY OF PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE. THE PLANS WERE ENLARGED TO A
 MEASUREMENT OF 51.33 FEET EQUALS 2 1/8 INCHES. IF THE
 PLANS ARE ENLARGED PLEASE CHANGE THE SCALE TO MATCH.
  
 3) NOT COMPLIED. THE SITE PLAN THAT WAS SUBMITTED IS
 SUFFICIENT. HOWEVER, IT IS REQUIRED TO BE SIGNED AND
 SEALED BY THE ENGINEER AS REQUIRED BY FAC 61G15-23.003
 PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH
 MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
 NOTE: ELECTRONIC OR DIGITAL SIGNATURES ARE ONLY
 ACCEPTABLE ON ELECTRONICALLY SUBMITTED PLANS.
  
 ORIGINAL COMMENT:
 MISSING SURVEY SHOWING THE PROPERTY LINES AND OVERALL
 DISTANCE THE DOCKS ARE GOING INTO THE INTER-COASTAL
 WATER WAY. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) NOT COMPLIED. THE SITE PLANS AND THE BELLINGHAM
 MARINE PLANS DO NOT MATCH THE PLANS THAT WERE APPROVED
 BY THE U.S. ARMY CORPS OF ENGINEERS ON AUGUST 29, 2017
 AND THE FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION.
 THE FINGER PIERS RUN NORTH TO SOUTH ON THE CORPS AND
 FDEP APPROVED PLANS AND THEY ARE SHOWN EAST TO WEST ON
 THE BELLINGHAM MARINE PLANS. THERE ARE OTHER
 DISCREPANCIES AS WELL. PROVIDE DOCUMENTATION THAT THESE
 CHANGES ARE ACCEPTABLE TO THE CORPS AND THE FDEP.
  
 ORIGINAL COMMENT.
 WEST PALM BEACH MUNI CODE ARTICLE X SECTION 94-313
 DOCKS (2) ADDITIONAL APPLICATION REQUIREMENTS, ( E )
 VALID WRITTEN APPROVAL OF THE PROPOSED DOCK BY THE
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (DEP),
 THE U.S. ARMY CORPS OF ENGINEERS (THE CORPS) AND/OR THE
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SFWMD) IS
 REQUIRED. SUCH WRITTEN APPROVAL SHALL CONTAIN THE DATE
 ON WHICH THE PROPOSED DOCK WAS APPROVED.
  
 5) NOT COMPLIED. THIS PROJECT IS EXPOSURE CATEGORY D
 AND THE PLANS SPECIFY C. PLEASE CORRECT. FBC 1609.4.3
  
 ORIGINAL COMMENT:
 SHEET 2 OF 19 WIND DESIGN IS FOR 140 MPH (DOES NOT
 STATE IF THIS IS VULT OR VASD) UNOCCUPIED.
 5A) THE 2ND ISSUE IS THE WIND DESIGN DOES NOT PROVIDE
 AT WHAT EXPOSURE THE WIND DESIGN IS TAKEN.
 5B) THE 3RD ITEM STATES THE OWNER IS RESPONSIBLE FOR
 WIND / WAVE STUDY TO VERIFY THE CONDITIONS, NOT
 PROVIDED.
 5C) 4TH ITEM ALL ELEVATIONS ARE IN NGVD. SINCE OCT.
 11/2017 THE WEST PALM BUILDING DEPARTMENT HAS CHANGED
 TO NAVD 88 FOR ALL MEASUREMENTS DEALING WITH WATER WAYS
 AND FLOOD WAYS TO COINCIDE WITH THE NEW FLOOD MAPS.
  
 5D) COMPLIED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL:(561) 805-6714
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-01 Cont ID  
Sent By jwitmer Date 2019-07-01 Time 12:59 Rev Time 0.00
Received By jwitmer Date 2019-07-01 Time 10:36 Sent To  
Notes
2019-07-01 12:59:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060677
 ADD: 4200 N. FLAGLER DR. RYBOVICH K DOCK
 CONT: BELLINGHAM MARINE
 TEL: 904-358-3362
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 01/2019
 ACTION: DENIED
  
 1) NOTICE. UNDER THE HEADING OF COMPANY NAME (DBA) IS
 LISTED AS FLORIDA FLOATS THIS IS NOT THE LISTED DBA
 WITH THE STATE. BELLINGTON MARINE IS. FLORIDA FLOATS
 HAS BEEN STRUCK.
  
 2) THE SUBMITTED PLANS HAVE BEEN ENLARGED:
 2A) WITH THE SUBMITTED PLANS BEING ENLARGED THE SEAL IS
 OVER 3 INCHES IN DIAMETER, THE SIGNATURE IS NO LONGER
 AN ORIGINAL SIGNATURE, IT HAS BEEN COPIED. 61G15-23.002
 SEALS ACCEPTABLE TO THE BOARD.
 (2) SEALS, EMBOSSING SEALS AND DIGITALLY CREATED SEALS
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER AND
 SHALL BE OF A DESIGN SIMILAR TO THOSE SET FORTH IN
 SUBSECTIONS.
  
 2B) SHEET 1 OF 19 INDICATES AN ENGINEERING SCALE OF 1
 INCH = 50 FEET. THIS SCALE DOES NOT MEET THE
 REQUIREMENTS OF 107.2.1.3. QUALITY OF PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE. THE PLANS WERE ENLARGED TO A
 MEASUREMENT OF 51.33 FEET EQUALS 2 1/8 INCHES. IF THE
 PLANS ARE ENLARGED PLEASE CHANGE THE SCALE TO MATCH.
  
 3) MISSING SURVEY SHOWING THE PROPERTY LINES AND
 OVERALL DISTANCE THE DOCKS ARE GOING INTO THE
 INTER-COASTAL WATER WAY. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) WEST PALM BEACH MUNI CODE ARTICLE X SECTION 94-313
 DOCKS (2) ADDITIONAL APPLICATION REQUIREMENTS, ( E )
 VALID WRITTEN APPROVAL OF THE PROPOSED DOCK BY THE
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (DEP),
 THE U.S. ARMY CORPS OF ENGINEERS (THE CORPS) AND/OR THE
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SFWMD) IS
 REQUIRED. SUCH WRITTEN APPROVAL SHALL CONTAIN THE DATE
 ON WHICH THE PROPOSED DOCK WAS APPROVED.
  
 5) SHEET 2 OF 19 WIND DESIGN IS FOR 140 MPH (DOES NOT
 STATE IF THIS IS VULT OR VASD) UNOCCUPIED.
 5A) THE 2ND ISSUE IS THE WIND DESIGN DOES NOT PROVIDE
 AT WHAT EXPOSURE THE WIND DESIGN IS TAKEN.
 5B) THE 3RD ITEM STATES THE OWNER IS RESPONSIBLE FOR
 WIND / WAVE STUDY TO VERIFY THE CONDITIONS, NOT
 PROVIDED.
 5C) 4TH ITEM ALL ELEVATIONS ARE IN NGVD. SINCE OCT.
 11/2017 THE WEST PALM BUILDING DEPARTMENT HAS CHANGED
 TO NAVD 88 FOR ALL MEASUREMENTS DEALING WITH WATER WAYS
 AND FLOOD WAYS TO COINCIDE WITH THE NEW FLOOD MAPS.
  
 5D) LENGTH OF PILING/ DEPTH OF REQUIRED PENETRATION.
 DETERMINED BY THE DAMES & MOORE GEOTECHNICAL REPORT. NO
 SUCH REPORT WAS SUBMITTED. ADDITIONAL INFORMATION IS
 REQUIRED. 107.2.1.2.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN REQUIRED REPORTS &
 PLANS AND REQUIRED DOCUMENTATION. WITH THE NEXT PLAN
 REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS
 BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE
 PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2019-08-09 Cont ID  
Sent By jpearson Date 2019-08-09 Time 10:11 Rev Time 0.00
Received By jpearson Date 2019-08-09 Time 07:43 Sent To  
Notes
2019-08-09 10:11:33NO ELECTRICAL SUBMITTED OR REVIEWED UNDER THIS
 APPLICATION. ELECTRICAL PLANS AND PERMIT WILL BE
 REQUIRED FOR ANY ELECTRICAL WORK ON PROJECT. WPB FBC
 107.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By jpearson Date 2019-07-12 Time 10:50 Rev Time 0.00
Received By jpearson Date 2019-07-12 Time 08:27 Sent To  
Notes
2019-07-12 10:49:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2019-10-03 Cont ID  
Sent By rrossano Date 2019-10-03 Time   Rev Time 0.00
Received By rrossano Date 2019-10-03 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2019-09-17 Cont ID  
Sent By rrossano Date 2019-09-17 Time   Rev Time 0.00
Received By rrossano Date 2019-09-17 Time   Sent To I
Notes
2019-09-17 07:16:09ORIGINAL COMMENT: PROVIDE CALCULATIONS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM &
 PEAK) AND FIRE FLOW DEMANDS FOR ADDITIONAL DOCKS.
 CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER AND PER
 FAC 64-E.008 FOR WATER.
  
 LATEST RESPONSE DATED AUGUST 28, 2019 STATES: "THE
 REVISED DEMAND CALC HAS BEEN ADDED TO THE CIVIL
 DRAWINGS."
  
 STILL UNABLE TO LOCATE WATER, SEWER AND FIRE FLOW
 DEMAND CALCULATIONS ON SUBMITTED SHEET C-1 OF
 KIMLEY-HORN CIVIL DRAWING DATED JUNE 2019.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-08-28 Cont ID  
Sent By rrossano Date 2019-08-28 Time   Rev Time 0.00
Received By rrossano Date 2019-08-28 Time   Sent To I
Notes
2019-08-28 08:50:59SITE PLAN PROVIDED WITH RESUBMITTAL DID NOT HAVE WATER
 DEMANDS SHOWN AS PER PREVIOUS COMMENT.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By rrossano Date 2019-07-10 Time   Rev Time 0.00
Received By rrossano Date 2019-07-10 Time   Sent To I
Notes
2019-07-10 14:59:32PROVIDE CALCULATIONS OF EXISTING AND PROPOSED DEMANDS
 FOR WATER & SEWER (AVERAGE, MAXIMUM & PEAK) AND FIRE
 FLOW DEMANDS FOR ADDITIONAL DOCKS. CALCULATIONS SHALL
 BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR
 WATER.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-8
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-10-01 Cont ID  
Sent By J.Walker Date 2019-10-01 Time   Rev Time 0.00
Received By jwalker Date 2019-10-01 Time   Sent To  
Notes
2019-10-01 10:28:22SENT TO B-30

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By pleduc Date 2019-07-23 Time   Rev Time 0.00
Received By pleduc Date 2019-07-23 Time 14:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-26 Cont ID  
Sent By pleduc Date 2019-06-26 Time   Rev Time 0.00
Received By pleduc Date 2019-06-26 Time 10:09 Sent To  
Notes
2019-06-26 10:42:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COVER SHEET - THERE ARE NO INDICATIONS OF COMPLAINCE
 WITH ANY FIRE CODE.
  
 AT MINIMUM THE PROPOSED SHALL COMPLY WITH NFPA 1 & 101,
 2015 EDITIONS, NFPA 303, 2011 EDITION, NFPA 70, 2014,
 AS WELL AS, ALL ASSOCIATED CODES.
  
 PLEASE REVIEW THE SUBMITTAL TO ENSURE COMPLIANCE AND
 PROVIDED A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
 1A) THERE IS NO SCOPE OF WORK PROVIDED THAT MAY HELP
 ADDRESS SOME OF THE COMMENTS BELOW. HOWEVER, PLEASE
 PROVIDE RESPONES TO THE BELOW FOR THE RECORD.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK
  
  
  
 2) SHEET 1 OF 19 - THOUGH THERE IS AN INDICATION OF 3
 NORTHERN FINGER PIERS BEING EXISTING, IT IS UNCLEAR
 WHAT WILL BE NEW.
  
 THERE ARE SOME AREAS SHADED THAT ARE ATTACHED TO
 DARKENED AREAS.
  
 PLEASE PROVIDE CLARITY ON WHAT IS EXISTING AND WHAT IS
 PROPOSED OR REPLACED.
  
  
  
 3) SHEET 3 OF 19 - THERE ARE INDICATION OF STANDPIPE
 AND FIRE EXTINGUISHER LOCATION BUT NO DETAILS,
 INCLUDING WHICH ONES ARE EXISTING VS PROPOSED.
  
 PLEASE CLARIFY AND PROVIDE DIMENSIONS IN COMPLIANCE
 WITH NFPA 303 FIRE PROTECTION STANDARD FOR MARINAS AND
 BOATYARDS 2011 EDITION
  
 6.4* FIRE STANDPIPE SYSTEMS.
 6.4.1 CLASS I STANDPIPE SYSTEMS SHALL BE PROVIDED FOR
 PIERS,
 BULKHEADS, AND BUILDINGS WHERE THE HOSE LAY DISTANCE
 FROM THE
 FIRE APPARATUS EXCEEDS 150 FT (45 M).
  
 6.4.3 STANDPIPE SYSTEMS, WHERE INSTALLED, SHALL BE IN
 ACCORDANCE
 WITH NFPA14, STANDARD FOR THE INSTALLATION OF STANDPIPE
 AND
 HOSE SYSTEMS, EXCEPT FOR THE PROVISIONS IDENTIFIED IN
 6.4.4
 THROUGH 6.4.7.
 6.4.4 HOSE RACKS, HOSES, AND STANDPIPE CABINETS SHALL
 NOT BE
 REQUIRED ON PIERS AND BULKHEADS.
 6.4.5 SUPPLY PIPING FOR STANDPIPES ON PIERS AND
 BULKHEADS
 SHALL BE SIZED FOR THE MINIMUM FLOW RATE FOR CLASS II
 SYSTEMS.
 6.4.6 MANUAL DRY STANDPIPES SHALL BE PERMITTED.
 6.4.7 FLEXIBLE CONNECTIONS SHALL BE PERMITTED ON
 FLOATING
 PIERS WHERE ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
 4) ALL STANDPIPE WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS IN COMPLIANCE WITH NFPA 303.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE
  
  
  
 5) THERE ARE NO INDICATIONS OF ELECTRICAL WORK.
  
 WILL ELECTIRCAL WORK BE DONE UNDER SEPARATE PERMIT?
  
 PLEASE CLARIFY AND PROVIDE A NOTE.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-02 Cont ID  
Sent By cpuell Date 2019-10-02 Time 17:00 Rev Time 0.00
Received By cpuell Date 2019-09-05 Time 11:54 Sent To Z
Notes
2019-09-06 11:55:07B30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-28 Cont ID  
Sent By skennedy Date 2019-08-28 Time 12:23 Rev Time 0.00
Received By skennedy Date 2019-07-19 Time 13:43 Sent To  
Notes
2019-07-22 13:43:47B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-18 Cont ID  
Sent By cpuell Date 2019-07-18 Time 14:44 Rev Time 0.00
Received By cpuell Date 2019-06-14 Time 07:48 Sent To  
Notes
2019-06-18 07:48:54B26

Review Stop Z ZONING
Rev No 4 Status P Date 2019-09-12 Cont ID  
Sent By cpuell Date 2019-10-02 Time 17:00 Rev Time 0.00
Received By jroach Date 2019-09-12 Time 15:25 Sent To  
Notes
2019-09-12 15:26:54ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.11.2019
 PERMIT NO.: 19060677
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 COMPLETION, A REVISED FDEP PERMIT APPROVAL SHALL BE
 PROVIDED (OR COMPARABLE DOCUMENTATION) SHOWING THEIR
 APPROVAL OF THE REVISED DOCK DIMENSIONS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2019-09-11 Cont ID  
Sent By jroach Date 2019-09-11 Time 16:13 Rev Time 0.00
Received By jroach Date 2019-09-11 Time 16:13 Sent To  
Notes
2019-09-11 16:19:54ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.11.2019
 PERMIT NO.: 19060677
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ PARTIALLY SATISFIED ] - PURSUANT TO RESOLUTION NO.
 185-18, PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 ANY NEW DOCK CONSTRUCTION, THE APPLICANT SHALL RECEIVE
 PERMITS FROM THE FLORIDA DEPARTMENT OF ENVIRONMENTAL
 PROTECTION (FDEP) AND THE U.S. ARMY CORPS OF ENGINEERS
 (ACOE). THE PLANS SUBMITTED DO NOT MATCH THAT WHICH WAS
 APPROVED BY THE FDEP. EITHER THE PLANS SHALL BE REVISED
 TO BE CONSISTENT WITH THE FDEP APPROVAL, OR A REVISED
 APRPOVAL SHALL BE PROVIDED. NOTE: ZONING IS AMENABLE TO
 PHASING THE WORK SUCH THAT THE FIRST PHASE WOULD ONLY
 BE FOR THAT PORTION THAT IS CONSISTENT WITH THE FDEP
 APPROVAL, AND THAT THE FINGER PIERS BE "PHASE 2", WHICH
 WOULD BE ADDED TO SCOPE OF THE PERMIT ONCE THE REVISED
 FDEP APPROVAL IS OBTAINED.
  
 1.1 [ NEW COMMENT ] - WHILE THE SCOPE OF THE WORK HAS
 BEEN REDUCED TO INCLUDE ON THE MAIN FLOATING DOCK
 (ELIMINATING THE INCONSISTENCY WITH THE FINGER PIERS),
 THE DIMENSIONS OF THE FLOATING DOCK DIFFER BETWEEN THE
 SITE PLAN PROVIDED AND THOSE PLANS PROVIDED BY
 BELLINGHAM MARINE. ADDITIONALLY, NEITHER OF THEM MATCH
 THAT WHICH WAS APPROVED BY THE FDEP.
  
 2. [ PARTIALLY SATISFIED ] - PURSUANT TO THE MARINA
 COMMERCIAL MARINE PLANNED DEVELOPMENT (CMPD) DESIGN
 GUIDELINES, EXPANSION OF THE MARINA SHALL REQUIRE
 APPROVAL OF A FORMAL SITE PLAN REVIEW (LEVEL II). THIS
 APPLICATION HAS BEEN SUBMITTED AND IS CURRENTLY UNDER
 REVIEW.
  
 2.1. [ NEW COMMENT ] - THE SITE PLAN REVIEW APPLICATION
 HAS NOT BEEN APPROVED, BUT STAFF IS WILLING TO CONSIDER
 ISSUANCE OF THE PERMIT PRIOR TO SITE PLAN APPROVAL UPON
 SATISFACTION OF ALL OTHER COMMENTS IN THIS PLAN REVIEW.
  
 3. [ PARTIALLY SATISFIED ] - THE DOCK PLANS SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING THE OVERALL CMPD,
 ALONG WITH THE NECESSARY DATA INDICATING THE TOTAL
 NUMBER OF BOAT SLIPS, COMPLIANCE WITH PARKING
 REQUIREMENTS, ETC. THE SITE PLAN PROVIDED DOES NOT
 MATCH THAT WHICH WAS SUBMITTED ON 08.20.2019 FOR THE
 SITE PLAN APPROVAL. PLEASE ENSURE THAT ALL PLANS ARE
 CONSISTENT.
  
 3.1 [ NEW COMMENT ] - THE DIMENSIONS OF THE FLOATING
 DOCK DIFFER BETWEEN THE SITE PLAN PROVIDED AND THOSE
 PLANS PROVIDED BY BELLINGHAM MARINE. ADDITIONALLY,
 NEITHER OF THEM MATCH THAT WHICH WAS APPROVED BY THE
 FDEP.
  
 4. [ NEW COMMENT ] - THE PLANS PROVIDED BY BELLINGHAM
 MARINE ARE NOT TO SCALE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-08-27 Cont ID  
Sent By jroach Date 2019-08-27 Time 13:53 Rev Time 0.00
Received By jroach Date 2019-08-15 Time 16:01 Sent To ENG
Notes
2019-08-27 13:59:24ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.27.2019
 PERMIT NO.: 19060677
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 185-18, PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR ANY NEW DOCK
 CONSTRUCTION, THE APPLICANT SHALL RECEIVE PERMITS FROM
 THE FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
 (FDEP) AND THE U.S. ARMY CORPS OF ENGINEERS (ACOE). THE
 PLANS SUBMITTED DO NOT MATCH THAT WHICH WAS APPROVED BY
 THE FDEP. EITHER THE PLANS SHALL BE REVISED TO BE
 CONSISTENT WITH THE FDEP APPROVAL, OR A REVISED
 APRPOVAL SHALL BE PROVIDED. NOTE: ZONING IS AMENABLE TO
 PHASING THE WORK SUCH THAT THE FIRST PHASE WOULD ONLY
 BE FOR THAT PORTION THAT IS CONSISTENT WITH THE FDEP
 APPROVAL, AND THAT THE FINGER PIERS BE "PHASE 2", WHICH
 WOULD BE ADDED TO SCOPE OF THE PERMIT ONCE THE REVISED
 FDEP APPROVAL IS OBTAINED.
  
 2. PURSUANT TO THE MARINA COMMERCIAL MARINE PLANNED
 DEVELOPMENT (CMPD) DESIGN GUIDELINES, EXPANSION OF THE
 MARINA SHALL REQUIRE APPROVAL OF A FORMAL SITE PLAN
 REVIEW (LEVEL II). THIS APPLICATION HAS BEEN SUBMITTED
 AND IS CURRENTLY UNDER REVIEW.
  
 3. THE DOCK PLANS SHALL BE ACCOMPANIED BY A SITE PLAN
 SHOWING THE OVERALL CMPD, ALONG WITH THE NECESSARY DATA
 INDICATING THE TOTAL NUMBER OF BOAT SLIPS, COMPLIANCE
 WITH PARKING REQUIREMENTS, ETC. THE SITE PLAN PROVIDED
 DOES NOT MATCH THAT WHICH WAS SUBMITTED ON 08.20.2019
 FOR THE SITE PLAN APPROVAL. PLEASE ENSURE THAT ALL
 PLANS ARE CONSISTENT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jroach Date 2019-07-18 Time 12:27 Rev Time 0.00
Received By jroach Date 2019-07-18 Time 11:41 Sent To  
Notes
2019-07-18 12:27:25ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.18.2019
 PERMIT NO.: 19060677
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO RESOLUTION NO. 185-18, PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR ANY NEW DOCK
 CONSTRUCTION, THE APPLICANT SHALL RECEIVE PERMITS FROM
 THE FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
 (FDEP) AND THE U.S. ARMY CORPS OF ENGINEERS (ACOE). ALL
 PLANS ASSOCIATED WITH THE FDEP AND ACOE PERMITS SHALL
 BE IN SUBSTANTIAL CONFORMANCE WITH THE PLANS APPROVED
 HEREIN. THESE PERMITS ALSO CONTAIN CONDITIONS OF
 APPROVAL SATISFYING THE APPLICANT?S NECESSARY
 COMPLIANCE WITH THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS. IN ANY EVENT WHERE THE FDEP OR ACOE
 PERMITS REQUIRE A MODIFICATION TO THE PLANS OR
 CONDITIONS OF APPROVAL, THE MODIFICATION SHALL BE
 REVIEWED BY THE CITY AND AN AMENDMENT TO THE PLANNED
 DEVELOPMENT MAY BE REQUIRED, AT THE DISCRETION OF THE
 DEVELOPMENT SERVICES DIRECTOR, OR HIS/HER DESIGNEE.
  
 2. PURSUANT TO THE MARINA COMMERCIAL MARINE PLANNED
 DEVELOPMENT (CMPD) DESIGN GUIDELINES, EXPANSION OF THE
 MARINA SHALL REQUIRE APPROVAL OF A FORMAL SITE PLAN
 REVIEW (LEVEL II). THIS APPLICATION HAS BEEN SUBMITTED
 AND IS CURRENTLY UNDER REVIEW.
  
 3. THE DOCK PLANS SHALL BE ACCOMPANIED BY A SITE PLAN
 SHOWING THE OVERALL CMPD, ALONG WITH THE NECESSARY DATA
 INDICATING THE TOTAL NUMBER OF BOAT SLIPS, COMPLIANCE
 WITH PARKING REQUIREMENTS, ETC. NOTE THAT THE DESIGN
 GUIDELINES FOR THE CMPD LIMIT THE NUMBER OF SLIPS TO
 272.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved