| 2019-06-18 12:48:10 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| | 805-6724 |
| | [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. FBC B 107.2.1, PROVIDE DRAWING DETAIL SHOWING |
| | CONSTRUCTION METHOD OF NEW SHOWER WALLS IN COMPLIANCE |
| | WITH R307.2 & R702.4.2. |
| | 2. FBC B 107.2.1, PROVIDE A CROSS SECTION DETAIL |
| | SHOWING CONSTRUCTION METHOD OF NEW SHOWER FLOOR. |
| | 3. CLARIFY IF REPLACING TILE ON BATHROOM FLOORS AND |
| | PROVIDE TEST REPORTS THAT DEMONSTRATE COMPLIANCE WITH |
| | THE SECTIONS BELOW; |
| | FBC B 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE |
| | W/FLAME SPREAD INDEX OF 200 OR LESS. |
| | FBC B 804 ? FLOORING |
| | FBC B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E |
| | FBC B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |