Plan Review Details - Permit 19060669
Plan Review Stops For Permit 19060669
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-23 Cont ID  
Sent By rmcdouga Date 2019-08-23 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2019-08-23 Time 17:53 Sent To I
Notes
2019-08-26 07:42:04APPROVED WITH EXCEPTION
 BUILDING PROVISO
  
 PROVIDE A COPY OF THE TEST REPORTS FOR THE SOUND
 INSULATION THAT WILL BE USED UNDER THE TILE FLOORING TO
 THE FIELD INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By jbrooks Date 2019-06-18 Time 12:47 Rev Time 0.00
Received By jbrooks Date 2019-06-18 Time 12:47 Sent To  
Notes
2019-06-18 12:48:10JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FBC B 107.2.1, PROVIDE DRAWING DETAIL SHOWING
 CONSTRUCTION METHOD OF NEW SHOWER WALLS IN COMPLIANCE
 WITH R307.2 & R702.4.2.
 2. FBC B 107.2.1, PROVIDE A CROSS SECTION DETAIL
 SHOWING CONSTRUCTION METHOD OF NEW SHOWER FLOOR.
 3. CLARIFY IF REPLACING TILE ON BATHROOM FLOORS AND
 PROVIDE TEST REPORTS THAT DEMONSTRATE COMPLIANCE WITH
 THE SECTIONS BELOW;
 FBC B 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED
 FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE
 W/FLAME SPREAD INDEX OF 200 OR LESS.
 FBC B 804 ? FLOORING
 FBC B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E
 FBC B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-23 Cont ID  
Sent By rmcdouga Date 2019-08-23 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2019-08-15 Time 13:44 Sent To  
Notes
2019-08-16 13:44:43RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-18 Cont ID  
Sent By jbrooks Date 2019-06-18 Time 12:48 Rev Time 0.00
Received By jbrooks Date 2019-06-14 Time 16:25 Sent To  
Notes
2019-06-17 16:25:31PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-23 Cont ID  
Sent By tklarge Date 2019-08-23 Time 15:09 Rev Time 0.00
Received By tklarge Date 2019-08-23 Time 11:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 08:48 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 08:48 Sent To  
Notes
2019-06-18 08:48:35PLUMBING 1ST REVIEW**DENIED**
  
 1) VALUE APPEARS LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT. WPB AMEND 109.3
  
 2) THIS BUILDINBG WAS BUILT IN 2007 UNDER THE FAIR
 HOUSING ACT (FHA). ALL FHA ELEMENTS SHALL REMAIN.
 PROVIDE CABINET HEIGHT DETAIL SHOWING THE NEW VANITIES
 WILL COMPLY WITH MAX BEING 34". FHA 7.52
  
 3) UNDER YOUR SCOPE OF WORK YOU REFER TO BTHROOM'S AND
 A NEW SHOWER PAN BUT ONLY 1 BATHRROM IS SHOWN ON THE
 FLOOR PLAN AND NO SHOWER. PLEASE CLARIFY. FBC 107.2.1
  
 4) PROVIDE SHOWER PAN DETAIL SHOWER WHAT MATERIAL IS
 BEING USED AND FLOORING WITH BE PRE-PITCHED 2%. FBC
 107.2.1
  
 5) PLANS SHALL BE SIGNED BY PERSON TAKING
 RESPONSIBILITY. FS 471, 481, 489
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  