| 2019-07-29 08:25:18 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19060649 |
| | ADD: 777 S. FLAGLER DR. SUITE: 950W |
| | CONT: BUTLER CONSTRUCTION CO. |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 29/2019 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES A VALUE OF $15,000 |
| | DOLLARS OF VALUE FOR THE WHOLE PROJECT. THIS SHOULD |
| | INCLUDE ALL SUB-TRADES TO BE INCLUDED IN THIS PROJECT. |
| | THE VALUE FOR THIS PERMIT SEEMS LOW FOR THE AMOUNT OF |
| | WORK TO BE COMPLETED, ESPECIALLY IN A HIGH RISE WHERE |
| | ADDITIONAL TIME IS REQUIRED FOR THE STOCKING OF |
| | MATERIAL AND THE REMOVAL OF WASTE. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 2) THE COVER SHEET LIST THE WORK TO BE COMPLETED UNDER |
| | THIS PERMIT AS A LEVEL 1 ALTERATION. |
| | |
| | 2017 EXISTING BUILDING CODE SCOPING 503.1. A LEVEL 1 |
| | ALTERATION (DEFINITION OF) INCLUDE THE REMOVAL AND |
| | REPLACEMENT OR THE COVERING OF EXISTING MATERIALS, |
| | ELEMENTS, EQUIPMENT, OR FIXTURES USING NEW MATERIALS, |
| | ELEMENTS, EQUIPMENT, OR FIXTURES THAT SERVE THE SAME |
| | PURPOSE. SHEET 005_A1.20 THE CONSTRUCTION PLAN IN THE |
| | OPEN AREA 1960 APPEARS TO BE A DOORWAY THAT IS BEING |
| | CLOSED OFF CREATING THE NEW TENANT SPACE. THERE IS A |
| | WALL TAG P3 AND 2 KEY NOTES 102 & 105. THIS IS A NEWLY |
| | CREATED ELEMENT MAKING THIS A LEVEL 2 ALTERATION. SEE |
| | SCOPING FOR LEVEL 2 ALTERATION UNDER THE: |
| | |
| | 2017 FBC-EXISTING BUILDING CODE. 504.1SCOPE. LEVEL 2 |
| | ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE |
| | ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE |
| | RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE |
| | INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| | |
| | 3) SHEET 005_A1.20 THE CONSTRUCTION PLAN SHOWING THE |
| | NEWLY CREATED WALL HAS CREATED A DEAD END CORRIDOR IN |
| | THE EXISTING TENANT SPACE, PLEASE PROVIDE A DIMENSION |
| | TO THIS CORRIDOR TO SEE IF THE DEAD END CORRIDOR |
| | CONFORMS TO 1020.4 OF THE FBC-B. |
| | |
| | 4) SHEET 004_A0.50 DETAIL # 5 SHOWS VARIOUS BASE |
| | CABINETS BUT THERE IS NO HEIGHT GIVEN FOR THESE |
| | CABINETS. PLEASE SHOW COMPLIANCE WITH: |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 902.1 .WORK |
| | SURFACES SHALL COMPLY WITH 902.3. ADVISORY 902.1 |
| | GENERAL. EXAMPLES OF WORK SURFACES INCLUDE WRITING |
| | SURFACES, STUDY CARRELS, STUDENT LABORATORY STATIONS, |
| | BABY CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL |
| | GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA |
| | SCOPING PROVISIONS, EMPLOYEE WORK STATIONS. |
| | 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| | SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |