Plan Review Details - Permit 19060644
Plan Review Stops For Permit 19060644
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 14:46 Rev Time 0.00
Received By cthroop Date 2019-08-26 Time 11:41 Sent To HIST
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 15:45 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 15:22 Sent To  
Notes
2019-07-19 15:55:38BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT IS REQUIRED.
 PERMITS 105.1 REQUIRED.
  
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 3. PROVIDE PRODUCT APPROVALS FOR ALL NEW EXT. DOORS AND
 WINDOWS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 4. ARCHITECT'S SIGNATURE AND SEAL IS PHOTO-COPIED.
 VERIFIED. CT
  
  
 5. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 6. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 7. PROVIDE SMOKE DETECTORS PER FBC R314.3.
  
 8. PROVIDE FASTENER SCHEDULE FOR ROOF SHEATHING.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By jpearson Date 2019-08-29 Time 14:51 Rev Time 0.00
Received By jpearson Date 2019-08-29 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-12 Cont ID  
Sent By ppetty Date 2019-08-12 Time 09:45 Rev Time 0.00
Received By ppetty Date 2019-08-12 Time 09:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-11 Cont ID  
Sent By jpearson Date 2019-07-11 Time 09:41 Rev Time 0.00
Received By jpearson Date 2019-07-11 Time 08:30 Sent To  
Notes
2019-07-11 09:41:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 4. LIGHT IN CLOSET IS SHOWN CLOSE TO THE CLOSET STORAGE
 SPACE. PROVIDE CODE COMPLIANT LOCATION OR FIXTURE. NEC
 410.16; FBC RE E4003.12
 5. PANEL SCHEDULE DOES NOT SHOW THE REQUIRED BRANCH
 CIRCUIT FOR BATHROOM RECEPTACLE OUTLETS. A MINIMUM OF
 ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. PROVIDE CORRECTION. NEC
 210.11(C)(3) , FBC RE E3703.4
 6. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 7. COUNTER TOP SPACE TO THE LEFT OF THE REFRIGERATOR IS
 MISSING THE REQUIRED RECEPTACLE OUTLET. PROVIDE
 CORRECTION. NEC 210.52(C)(1); FBC RE E3901
 8. PLAN SHOWS A RELOCATED ELECTRICAL SUB-PANEL THAT IS
 NOT SHOWN ON THE RISER DIAGRAM. PROVIDE ACCURATE RISER
 DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE
 E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-09-06 Cont ID  
Sent By lcrespo Date 2019-09-06 Time 16:58 Rev Time 0.00
Received By lcrespo Date 2019-09-06 Time 16:58 Sent To  
Notes
2019-09-06 16:59:1709/06/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 14:50 Rev Time 0.00
Received By cthroop Date 2019-08-26 Time 14:50 Sent To  
Notes
2019-08-26 14:51:11A SEPERATE GAS PERMIT IS REQUIRED.
 ADDRESS THE COMMENTS ON THE SECOND GAS REVIEW AND
 SUBMIT A NEW APPLICATION. CT

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-08-15 Cont ID  
Sent By jesmith Date 2019-08-15 Time 16:25 Rev Time 0.00
Received By jesmith Date 2019-08-15 Time 16:24 Sent To  
Notes
2019-08-15 16:24:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
 1) ?? SIZE FOR CSST IS NOT CORRECT. PROVIDE EHD TUBE
 SIZE(S) FOR CSST. RISER DIAGRAM IS SOMEWHAT UNCLEAR.
 DROP TO DRYER IS OBSCURING INFORMATION FOR HORIZONTAL
 RUN TO TANKLESS HEATER AND SOME DIMENSIONS ARE
 DIFFICULT TO READ. PER WPB FBC 107.2.1 PROVIDE A
 LEGIBLE RISER DIAGRAM.
 2) BTU INFO IS BARELY LEGIBLE ON RANGE SUBMITTAL.
 3) I CANNOT FIND BTU INFO ON THE DRYER SUBMITTAL.
 4) SECOND REQUEST: SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE ADDED GAS APPLIANCES. WHERE COMBUSTION AIR IS
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. 2017 FBCR G2407.9.3.
 5) PROVIDE SPEC FOR MP REGULATORS FOR APPLIANCES AND
 INCLUDE VENT LIMITER FOR INDOOR REGULATORS. OUTDOOR
 REGULATORS SHALL BE RATED FOR OUTDOOR USE.
 6) SHOW LOCATION OF GAS METER ON THE BUILDING PLANS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060644 127 WESTMINSTER RD
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By thunt Date 2019-07-08 Time 10:41 Rev Time 0.00
Received By thunt Date 2019-07-08 Time 10:38 Sent To  
Notes
2019-07-08 10:40:57GAS 1ST REVIEW**DENIED**
  
 1) A GAS PLAN AND PERMIT ARE REQUIRED. FBC 105.1
  
 2) PROVIDE STOVE MANUFACTURES INSTALLATION MANUAL. FBC
 107.2.1
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBCR
 G2407.9.3.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By fmittner Date 2019-08-26 Time 15:32 Rev Time 0.00
Received By fmittner Date 2019-08-26 Time 15:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-07-05 Cont ID  
Sent By fmittner Date 2019-07-05 Time 15:08 Rev Time 0.00
Received By fmittner Date 2019-07-05 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-10 Cont ID  
Sent By cmontell Date 2019-09-10 Time 14:39 Rev Time 0.00
Received By cmontell Date 2019-09-10 Time 14:39 Sent To  
Notes
2019-08-29 13:24:17R12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 15:37 Rev Time 0.00
Received By cthroop Date 2019-08-01 Time 12:03 Sent To  
Notes
2019-08-04 12:04:11R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 15:59 Rev Time 0.00
Received By cthroop Date 2019-06-13 Time 15:25 Sent To  
Notes
2019-06-14 15:25:59R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 14:36 Rev Time 0.00
Received By cthroop Date 2019-08-26 Time 11:41 Sent To  
Notes
2019-08-26 14:37:41MU-2019-0724-245. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 15:58 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 15:22 Sent To  
Notes
2019-07-19 15:59:03PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-09-10 Cont ID  
Sent By cmontell Date 2019-09-10 Time 14:39 Rev Time 0.00
Received By cmontell Date 2019-09-10 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-08-16 Cont ID  
Sent By cmontell Date 2019-08-16 Time 15:06 Rev Time 0.00
Received By cmontell Date 2019-08-16 Time 15:05 Sent To  
Notes
2019-08-16 15:05:47MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN PER 2017 FLORIDA BUILDING CODE
 - BUILDING, SIXTH EDITION SEC [A] 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By cmontell Date 2019-07-16 Time 11:20 Rev Time 0.00
Received By cmontell Date 2019-07-16 Time 11:17 Sent To  
Notes
2019-07-16 11:20:22MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN PER 2017 FLORIDA BUILDING CODE
 - BUILDING, SIXTH EDITION SEC [A] 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-06 Cont ID  
Sent By lcrespo Date 2019-09-06 Time 16:58 Rev Time 0.00
Received By lcrespo Date 2019-09-06 Time 16:58 Sent To  
Notes
2019-09-06 16:59:4809/06/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-15 Cont ID  
Sent By jesmith Date 2019-08-15 Time 15:50 Rev Time 0.00
Received By jesmith Date 2019-08-15 Time 15:40 Sent To  
Notes
2019-08-15 15:49:57PLUMBING COMMEMTS: APPROVED

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By thunt Date 2019-07-08 Time 10:52 Rev Time 0.00
Received By thunt Date 2019-07-08 Time 09:08 Sent To  
Notes
2019-07-08 10:52:51PLUMBING 1ST REVIEW**DENIED**
  
 1) PLUMBING ISOMETRIC SHOW DRAIN TO WASHING MACHINE AS
 2". FBC-P 709.1, 406.2 CALLS FOR MIN 3" TO THE FIXTURE
 DRAIN OR STACK.
  
 2) PROVIDE LOCATION OF WATER HEATER. ALL NEW HOT WATER
 PIPING WILL REQUIRED MIN R-3 INSULATIONS. FBC-ENERGY
 R403.5.3
  
 3) PLUMBING ISOMETRIC FOR NEW BATHROOM DOES NOT SHOW IT
 CONNECTING TO THE BUILDING DRAIN. FBC 107.3.5
  
 4) PLAN SHOWS TUB/ SHOWER VALVES AS 2 HANDLE. 2 HANDLE
 VALVES NO LONGER MEET THE CODE AND MUST BE PRESSURE
 BALANCE, THERMOSTATIC, OR A COMBO OF BOTH AND HAVE A
 STOP LIMITER MAX 120F. PROVIDE MANUFACTURE INSTALLATION
 MANUAL. FBC 107.2.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 14:45 Rev Time 0.00
Received By cthroop Date 2019-08-26 Time 11:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 15:55 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 15:22 Sent To  
Notes
2019-07-19 15:58:21BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 2. PROVIDE FASTENER SCHEDULE FOR ROOF SHEATHING.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 15:32 Rev Time 0.00
Received By fmittner Date 2019-08-26 Time 14:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-05 Cont ID  
Sent By fmittner Date 2019-07-05 Time 15:08 Rev Time 0.00
Received By fmittner Date 2019-07-05 Time 15:08 Sent To  
Notes
***NONE***