Plan Review Details - Permit 19060623
Plan Review Stops For Permit 19060623
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 17:23 Rev Time 0.00
Received By shill Date 2019-07-03 Time 17:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 10:47 Rev Time 0.00
Received By shill Date 2019-06-14 Time 10:47 Sent To  
Notes
2019-06-14 10:47:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, OPENING 1 ON THE INSTALLATION SCHEDULE IS
 NOT CONSISTENT WITH THE FLOOR PLAN AND DESIGN PRESURES,
 PLEASE CORRELATE.
  
 2. FBC R 301, FASTENER PROPOSED NOT CLEAR. SEE SHEET
 13, TABLE "EDGE DISTANCE VERSUS SPACING SCHEDULE FOR
 ANCHORING". REVISE THE INSTALLATION SCHEDULE TO SPECIFY
 ONE OF THE FOUR FASTENERS IN THE CHART. APPLY THE
 FACTOR IF REQUIRED.
  
 3. FBC 107, TWO COPIES OF ALL DOCUMENTS REQUIRED
 (INSTALLATION SCHEDULE).
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 17:23 Rev Time 0.00
Received By shill Date 2019-06-27 Time 11:43 Sent To  
Notes
2019-06-28 11:44:10RESUB ROUTED TO BLDG <5K

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 10:47 Rev Time 0.00
Received By shill Date 2019-06-13 Time 11:15 Sent To  
Notes
***NONE***