Plan Review Details - Permit 19060607
Plan Review Stops For Permit 19060607
Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-10-02 Cont ID  
Sent By lmarchan Date 2019-10-02 Time 14:17 Rev Time 0.00
Received By lmarchan Date 2019-10-02 Time 14:17 Sent To  
Notes
2019-10-02 14:17:33GAS REVIEW SHOULD BE COMPLETED UNDER MASTER PERMIT
 19060602. PLEASE ENTER YOUR RESULTS THERE.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By lcrespo Date 2019-09-10 Time 16:14 Rev Time 0.00
Received By lcrespo Date 2019-09-10 Time 16:14 Sent To  
Notes
2019-09-10 16:54:3409/10/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT ANCHORING DETAILS FOR THE LP TANK. NFPA 58-11
 SEC. 5.2.4.3.
 2. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
 3. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A
 NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
 4. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE.
 COMPLY WITH NFPA 58 SEC. 6.6.6.1.
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
 6. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 7. SHOW LISTED SHUTOFF VALVE IMMEDIATELY AHEAD OF EACH
 MP REGULATOR, LEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC FG SEC
 410.2.
 8. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2.
 9. A FULL ADDRESS OF THE PROJECT OR RESIDENCE MUST BE
 ON PLAN (CITY). WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 10. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 11. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
 12. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (DRYER
 AND GRILL) TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC.
 G2408.1.
 13. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND
 LABELED PER THE 2017 FBC FG RES. SEC. G2404.3. THE
 MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT
 ARE BEING EXHAUSTED BY THE DRYER.
 14. A GAS GRILL IS SHOWN, IS IT FOR OUTSIDE USE AND IT
 SEEMS TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER
 THE 2017 FBC RES. SEC. G2408.1.
 15. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR
 SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-10 Cont ID  
Sent By lcrespo Date 2019-09-10 Time 16:15 Rev Time 0.00
Received By lcrespo Date 2019-09-10 Time 16:15 Sent To  
Notes
2019-09-10 16:15:38GAS PERMIT RUNNING WITH MASTER 19060602