Plan Review Details - Permit 19060556
Plan Review Stops For Permit 19060556
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By cthroop Date 2019-11-20 Time 11:11 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 13:53 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:16 Sent To  
Notes
2019-07-19 14:18:17BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ARCHITECT'S SIGNATURE AND SEAL ARE PHOTO COPIES.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 3. PALM BEACH COUNTY IMPACT FEES WILL BE REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 4. PROVIDE LANDINGS AT EXTERIOR DOORS, WHERE REQUUIRED.
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
  
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-02-08 Cont ID  
Sent By equinone Date 2021-02-08 Time 09:59 Rev Time 0.00
Received By jleahy Date 2021-02-08 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-01-21 Cont ID  
Sent By jleahy Date 2021-01-21 Time 16:49 Rev Time 0.00
Received By jleahy Date 2021-01-21 Time 16:47 Sent To  
Notes
2021-01-22 10:44:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) MAINS "A" AND "B" ARE THEY GROUPED AS REQUIRED BY
 230.72
  
 230.72 GROUPING OF DISCONNECTS (A) GENERAL. THE TWO TO
 SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE
 GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED
  
 2) RISER SHOWS JUST 1 #4 TO DISCONNECT "A"
  
 3) RISER SHOWS PANEL "B" AS A MAIN BREAKER PANEL AND
 PANEL SCHEDULE SHOWS MAIN LUG ONLY IF REMOTE AND IN
 ANOTHER STRUCTURE IT HAS TO BE MAIN BREAKER TYPE.
 225.33

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-11-19 Cont ID  
Sent By equinone Date 2020-11-19 Time 09:05 Rev Time 0.00
Received By equinone Date 2020-11-18 Time 16:20 Sent To  
Notes
2020-11-19 09:34:10CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 PREVIOUS COMMENTS:
  
 1. RISER DIAGRAM SHOWS 3/0 WIRE FEEDING A 350 AMPS
 SERVICE. THIS WIRE IS NOT RATED FOR 350 AMPS SERVICE.
 PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE E3603.1
  
 NOT CORRECTED.
  
 RISER DIAGRAM SHOWS A (1) 4/0 EXISTING CONDUCTOR FOR
 THE OVERHEAD SERVICE TO FPL TRANSFORMER AND (1) 4/0
 FROM EXISTING METER TO EXISTING 350 AMPS SERVICE
 DISCONNECT. THIS IS NOT ENOUGH FOR A 350 AMPS SERVICE
 AND IT SHOULD BE AT LEAST 3 CONDUCTORS OR TWO SETS OF
 THE PROPERLY SIZED CONDUCTORS. PLEASE CORRECT.
  
  
 2. ON RISER DIAGRAM, WIRE FROM MAIN DISCONNECT TO
 INTERIOR PANELS SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6
  
 NOT CORRECTED.
  
 STILL MISSING ON NEW RISER DIAGRAM. EACH FEEDER TO
 PANEL A AND TO PANEL B SHOULD HAVE 4 CONDUCTORS, THE
 3#3/0 PLUS THE EQUIPMENT GROUNDING CONDUCTOR SIZED AS
 PER NEC 250-122; FBC RE E3704.6. PLEASE PROVIDE THE
 ACTUAL SIZE OF THE GROUNDING EQUIPMENT CONDUCTOR. A
 NOTE INDICATING TO SIZE THEM AS PER NEC 250-122 IS NOT
 ENOUGH.
  
 3. UNDER THE TITLE FOR NEW ELECTRIC ONLY, AFCI
 PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
  
 PARTIALLY CORRECTED BUT LANGUAGE INDICATING THAT SOME
 AREAS REQUIRE BOTH AFCI AND GFI IS VAGUE. ONE OPTION IS
 TO INDICATE IN PANEL SCHEDULE WHAT CIRCUITS HAVE AFCI
 OR GFCI OR BOTH.
  
 4. UNDER THE TITLE FOR NEW ELECTRIC ONLY AND NOTE 14,
 NOTE STATES THAT RECEPTACLES SHALL BE TAMPER RESISTANT
 PER NEC 406.11. THIS CODE SECTION DOES NOT APPLY TO
 TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
  
 CORRECTED.
  
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220; FBC RE E3602.2
  
 DOES THE TOTAL LOAD FOR EXISTING PANEL A INCLUDES THE
 LOAD FOR NEW PANEL B? TOTAL LOAD OF 99 AMPS SEEMS SMALL
 FOR A 350 AMPS SERVICE.
  
  
 6. IT APPEARS THIS PANEL IS LOCATED IN A SEPARATE
 STRUCTURE FROM THE BUILDING THAT HAS THE MAIN SERVICE.
 IF THIS IS THE CASE, PANEL B WILL NEED TO EITHER HAVE A
 MAIN BREAKER, OR A DISCONNECT AHEAD OF IT AT THE
 STRUCTURE. PROVIDE CORRECTION. NEC 225.31, 225.32
  
 NOT CLEAR. PANEL SCHEDULE FOR PANEL B DESCRIBES THE
 PANEL AS MAIN LUGS ONLY (MLO) BUT RISER DIAGRAM
 DESCRIBES PANEL B HAS HAVING A MAIN CIRCUIT BREAKER
 (MCB). IF PANEL B HAS A MAIN CIRCUIT BREAKER, PLEASE
 PROVIDE SIZE IN AMPS AND IF MLO PLEASE PROVIDE SIZE OF
 DISCONNECT AHEAD OF IT AT STRUCTURE AND SHOW IT ON
 RISER DIAGRAM.
  
  
 ADDITIONAL COMMENTS:
  
 7. PLEASE PROVIDE LOCATION OF MAIN SERVICE DISCONNECT,
 EXISTING PANEL A, NEW PANEL B. POWER LAYOUT SHOWS A NEW
 PANEL A LOCATED IN GARAGE, BUT RISER DIAGRAM DESCRIBES
 PANEL A AS EXISTING. PLEASE CORRECT AND CLEARLY SHOW
 LOCATION OF ALL THESE ELEMENTS.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-11-04 Cont ID  
Sent By jpearson Date 2019-11-04 Time 14:48 Rev Time 0.00
Received By jpearson Date 2019-11-04 Time 11:55 Sent To  
Notes
2019-11-04 13:11:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 3/0 WIRE FEEDING A 350 AMP
 SERVICE. THIS WIRE IS NOT RATED FOR 350 AMP SERVICE.
 PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE E3603.1
 2. ON RISER DIAGRAM, WIRE FROM MAIN DISCONNECT TO
 INTERIOR PANELS SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6
 3. UNDER THE TITLE FOR NEW ELECTRIC ONLY, AFCI
 PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 4. UNDER THE TITLE FOR NEW ELECTRIC ONLY AND NOTE 14,
 NOTE STATES THAT RECEPTACLES SHALL BE TAMPER RESISTANT
 PER NEC 406.11. THIS CODE SECTION DOES NOT APPLY TO
 TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220; FBC RE E3602.2
 6. IT APPEARS THIS PANEL IS LOCATED IN A SEPARATE
 STRUCTURE FROM THE BUILDING THAT HAS THE MAIN SERVICE.
 IF THIS IS THE CASE, PANEL B WILL NEED TO EITHER HAVE A
 MAIN BREAKER, OR A DISCONNECT AHEAD OF IT AT THE
 STRUCTURE. PROVIDE CORRECTION. NEC 225.31, 225.32
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By jleahy Date 2019-07-10 Time 13:37 Rev Time 0.00
Received By jleahy Date 2019-07-10 Time 13:37 Sent To  
Notes
2019-07-10 13:38:11FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE E-1
  
 1) PANEL SCHEDULE SHOWS #14 WIRE ON 20A BREAKERS
  
 2) RISER SHOWS NEW 150A MAIN DISCONNECT THIS NEEDS TO
 BE GROUPED WITH THE 200A MAIN.
 NOT SURE IF IT IS???
  
 3) NEED AN OUTLET AT THE FRONT OF THE BUILDING

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 10:00 Rev Time 0.00
Received By jleahy Date 2021-01-26 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-21 Cont ID  
Sent By jleahy Date 2021-01-21 Time 16:57 Rev Time 0.00
Received By jleahy Date 2021-01-14 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-19 Cont ID  
Sent By equinone Date 2020-11-19 Time 09:34 Rev Time 0.00
Received By equinone Date 2020-11-05 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-20 Cont ID  
Sent By cthroop Date 2019-11-20 Time 11:11 Rev Time 0.00
Received By cthroop Date 2019-10-16 Time 13:19 Sent To  
Notes
2019-10-17 13:19:19R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 14:19 Rev Time 0.00
Received By cthroop Date 2019-06-12 Time 15:09 Sent To  
Notes
2019-06-13 15:09:24R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2019-11-20 Cont ID  
Sent By cthroop Date 2019-11-20 Time 11:04 Rev Time 0.00
Received By cthroop Date 2019-11-20 Time 11:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 14:18 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:17 Sent To  
Notes
2019-07-19 14:19:14PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By cthroop Date 2019-11-20 Time 11:11 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-11 Cont ID  
Sent By cmontell Date 2019-07-11 Time 13:51 Rev Time 0.00
Received By cmontell Date 2019-07-11 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By jesmith Date 2019-10-24 Time 12:41 Rev Time 0.00
Received By jesmith Date 2019-10-24 Time 08:03 Sent To  
Notes
2019-10-24 12:41:43PLUMBING COMMENTS: APPROVED W/PROVISO
 1.CONCRETE TIE BEAMS OR BOND BEAMS SHALL NOT BE CUT,
 DRILLED, NOTCHED OR MODIFIED IN ANY WAY WITHOUT A
 DETAIL SIGNED AND SEALED BY A DULY LICENCED DESIGN
 PROFESSIONAL WHICH SHALL BE SUBMITTED TO THE BUILDING
 DEPARTMENT, APPROVED AND IN PLACE PRIOR TO INSPECTION.
 CONTRACTOR PROCEEDS AT THEIR OWN RISK.
 2.HORIZONTAL PIPING PASSING THROUGH WOOD FRAME STUDS
 SHALL BE INSTALLED IN ACCORDANCE WITH FBC RES R602.6
 DRILLING AND NOTCHING OF STUDS SHALL BE IN ACCORDANCE
 WITH THE FOLLOWING:
 A. NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING
 PARTITION SHALL BE PERMITTED TO BE CUT OR NOTCHED TO A
 DEPTH NOT EXCEEDING 25 PERCENT OF ITS WIDTH. STUDS IN
 NONBEARING PARTITIONS SHALL BE PERMITTED TO BE NOTCHED
 TO A DEPTH NOT TO EXCEED 40 PERCENT OF A SINGLE STUD
 WIDTH.
 B. DRILLING. ANY STUD SHALL BE PERMITTED TO BE BORED OR
 DRILLED, PROVIDED THAT THE DIAMETER OF THE RESULTING
 HOLE IS NOT MORE THAN 60 PERCENT OF THE STUD WIDTH, THE
 EDGE OF THE HOLE IS NOT MORE THAN 5/8 INCH (16 MM) TO
 THE EDGE OF THE STUD, AND THE HOLE IS NOT LOCATED IN
 THE SAME SECTION AS A CUT OR NOTCH. STUDS LOCATED IN
 EXTERIOR WALLS OR BEARING PARTITIONS DRILLED OVER 40
 PERCENT AND UP TO 60 PERCENT SHALL BE DOUBLED WITH NOT
 MORE THAN TWO SUCCESSIVE DOUBLED STUDS BORED. FOR
 CLARIFICATION, REFER TO FIGURES R602.6(1) AND R602.6(2)
 IN THE FLORIDA RESIDENTIAL CODE 2017 6TH EDITION (FBC
 RES).
 EXCEPTION: USE OF APPROVED STUD SHOES IS PERMITTED
 WHERE THEY ARE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S RECOMMENDATIONS.
 3.VERTICAL VENTS PASSING THROUGH WOOD FRAME TOP PLATES
 SHALL BE INSTALLED IN ACCORDANCE WITH FBC RES R602.6.1
 WHEN PIPING OR DUCTWORK IS PLACED IN OR PARTLY IN AN
 EXTERIOR WALL OR INTERIOR LOAD-BEARING WALL,
 NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP
 PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A
 GALVANIZED METAL TIE NOT LESS THAN 0.054 INCH THICK
 (1.37 MM) (16 GA) AND 11/2 INCHES (38 MM) WIDE SHALL BE
 FASTENED ACROSS AND TO THE PLATE AT EACH SIDE OF THE
 OPENING WITH NOT LESS THAN EIGHT 10D (0.148 INCH
 DIAMETER) NAILS HAVING A MINIMUM LENGTH OF 11/2 INCHES
 (38 MM) AT EACH SIDE OR EQUIVALENT. THE METAL TIE MUST
 EXTEND A MINIMUM OF 6 INCHES PAST THE OPENING. FOR
 CLARIFICATION, REFER TO FIGURES R602.6.1 IN THE FLORIDA
 RESIDENTIAL CODE 2017 6TH EDITION (FBC RES).
 EXCEPTION: WHEN THE ENTIRE SIDE OF THE WALL WITH THE
 NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL
 SHEATHING.
 4. PER WPB FBC 107.2.1, PROVIDE AS A DEFERRED
 SUBMITTAL, THE SUPPORTING DOCUMENT PREVIOUSLY PROVIDED
 FOR THE TANKLESS WATER HEATER AND SPECIFY ON THE
 DOCUMENT WHICH MODEL WATER HEATER IS TO BE FURNISHED.
 THE DOCUMENT SHALL BE SUBMITTED TO THE BUILDING
 DEPARTMENT WITH ARCHITECT?S STAMP, APPROVED AND ON SITE
 PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
 5. PER FBC RES P26094.4, MAINTAIN A DISTANCE BETWEEN
 THE TRENCHING FOR THE BUILDING SEWER RUNNING PARALLEL
 TO THE BUILDING FOUNDATION EDGE THAT KEEPS THE TRENCH
 OUT OF THE 45 DEGREE ANGLE OF REPOSE. SEE REDLINED
 COMMENT ON SANITARY PLAN VIEW.
 6. PER FBC RES P3105.1, THE VENT FOR THE BAR SINK SHALL
 NOT CONNECT BELOW THE TRAP WEIR AND PER FBC RES P3104.4
 SHALL CONNECT TO THE TOP OF THE TRAP CONNECTION AND
 RISE VERTICALLY TO A POINT 6? ABOVE THE FICTURE RIM OR
 TRAP BEFORE OFFSETTING HORIZONTALLY. SEE REDLINED
 COMMENT ON SANITARY RISER DIAGRAM.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-20 Cont ID  
Sent By thunt Date 2019-06-20 Time 15:10 Rev Time 0.00
Received By thunt Date 2019-06-20 Time 14:44 Sent To  
Notes
2019-06-20 15:25:51PLUMBING 1ST REVIEW**DENIED**
  
 1) PLAN SHOW ELC TANKLESS WATER HEATER OUTSIDE. PROVIDE
 COMPLETED INSTALLATION MANUAL WITH HEAT RISE CHARTS TO
 VERIFY SIZING AND APPROVED FOR OUTDOOR USE. FBC
 107.2.1, FBC P502.1
  
 2) THE WASHING MACHINE IS NOT SHOWN ON THE ISOMETRIC AS
 VENTED AND BRANCH LINE AS 2". FBC 406.2 REQUIRES THE
 BRANCH OR STACK TO BE MIN 3" AND BE VENTED FBC P901.2.1
  
 3) THE WET BAR AND WASHINE MACHINE ARE ON SEPERATE
 BUILDING DRAINS WHICH BOTH WILL REQUIRE A VENT THAT
 EXTENDS TO THE OUTDOORS. AAV IS NOT PERMITTED. FBC P
 904.1
  
 4) PROVIDE SHOWER PAN/RECESS DETAIL. SHOW MATERIAL USED
 AND THAT FLOOR WILL BE PRE-PITCHED @2%. FBC 107.2.1
  
 5) ALL SHEETS SIGNED BY SANDRA PUERTA ARC #95385 ARE
 COPIES. FS 481 REQUIRES EACH PAGE TO BE WET SIGNED.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By cthroop Date 2019-07-19 Time 14:18 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 09:59 Rev Time 0.00
Received By jleahy Date 2021-02-08 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By jleahy Date 2021-01-21 Time 16:58 Rev Time 0.00
Received By jleahy Date 2021-01-21 Time 16:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-12 Cont ID  
Sent By dbattles Date 2020-11-12 Time 15:13 Rev Time 0.00
Received By dbattles Date 2020-11-12 Time 15:13 Sent To  
Notes
2020-11-12 15:13:46ANY ADDITIONAL SHEETS WILL NEED TO BE DIGITALLY SIGNED.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-28 Cont ID  
Sent By awooten Date 2019-10-28 Time   Rev Time 0.00
Received By awooten Date 2019-10-28 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-26 Cont ID  
Sent By awooten Date 2019-06-26 Time   Rev Time  
Received By awooten Date 2019-06-26 Time   Sent To  
Notes
***NONE***