Plan Review Details - Permit 19060536
Plan Review Stops For Permit 19060536
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By jduprey Date 2019-06-18 Time 14:20 Rev Time 0.00
Received By pvalenti Date 2019-06-18 Time 14:11 Sent To  
Notes
2019-06-18 14:30:02***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE BUILDING PLAN REVIEW IS PENDING APPROVAL OF THE
 FIRE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By pleduc Date 2019-06-17 Time   Rev Time 0.00
Received By pleduc Date 2019-06-17 Time 13:29 Sent To B
Notes
2019-06-17 13:37:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE LETTER NARRATIVE INDICATES FBC REFERENCES.
  
 PER THE FLORIDA FIRE PREVENTION CODE OCCUPANCY
 CLASSIFICATION AND SEPARATION IS ADDRESSED WITHIN
 CHAPTER 6
  
 PER NFPA 101, CH 6
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 THE TABLE INDICATES A 2 HR RATING BETWEEN STORAGE/
 BUSINESS & MERCANTILE. A REDUCTION OF 1HR FOR FIRE
 SPRINKLER PROTECTION.
  
  
 BASED ON THE REVIEW TO ELIMINATE THE EXISITNG 1 HR
 RATING AND REVIEW OF THE ABOVE FFPC REFERENCES THE
 REQUEST IS NOT APPROVED.
  
  
 PLEASE REVIEW THE ABOVE AND PROVIDE ADDITIONAL
 INFORMATION AND APPLICABLE CODE REFERENCES FOR REVIEW.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-18 Cont ID  
Sent By pvalenti Date 2019-06-18 Time 14:39 Rev Time 0.00
Received By pvalenti Date 2019-06-12 Time 15:11 Sent To  
Notes
2019-06-13 15:12:01REVISION ROUTED TO FIRE INBOX