Plan Review Details - Permit 19060516
Plan Review Stops For Permit 19060516
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-21 Cont ID  
Sent By jpearson Date 2019-06-21 Time 06:58 Rev Time 0.00
Received By jpearson Date 2019-06-21 Time 06:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-18 Cont ID  
Sent By jpearson Date 2019-06-18 Time 08:29 Rev Time 0.00
Received By jpearson Date 2019-06-18 Time 08:29 Sent To I
Notes
2019-06-18 06:52:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE AND SEAL.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 (SEE SIGNATURE REVIEW FOR MORE INFORMATION.)
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NO VALUE STATED ON CONTRACT PROVIDED. MUST
 INCLUDE ALL MATERIALS, EVEN IF THEY ARE TO BE INSTALLED
 OR FURNISHED BY OTHERS.)
 3. PROVIDE SPEC SHEETS FOR CAMERAS TO CONFIRM LISTING.
 NEC 110.3 (NOT PROVIDED. REQUIRED EVEN IF INSTALLED BY
 OTHERS. IF A SUB-CONTRACTOR IS PULLING A SUB-PERMIT
 UNDER THIS PERMIT, THEY CAN SUBMIT THE SPEC SHEETS. SOW
 STATES THE CONTRACTOR OR A CONTRACTOR SECURITY VENDOR
 WILL INSTALL ALL FIELD DEVICES WHICH CONFLICTS WITH THE
 STATEMENT AT THE TOP OF THE SOW THAT STATES CONTRACTOR
 WILL NOT INSTALL FIELD DEVICES. WHICH IS IT? CLARIFY
 AND/OR CORRECT AS NECESSARY. WPB FBC 107.2.1)
  
 NEW COMMENT:
  
 4. IF THERE IS TO BE ACCESS CONTROL AS PART OF THIS
 PLAN, FIRE DEPARTMENT WILL ALSO HAVE TO REVIEW. PLEASE
 CLARIFY. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By jpearson Date 2019-06-13 Time 14:31 Rev Time 0.00
Received By jpearson Date 2019-06-13 Time 14:31 Sent To I
Notes
2019-06-13 14:30:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE AND SEAL.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 3. PROVIDE SPEC SHEETS FOR CAMERAS TO CONFIRM LISTING.
 NEC 110.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-21 Cont ID  
Sent By pleduc Date 2019-06-21 Time   Rev Time 0.00
Received By pleduc Date 2019-06-21 Time 11:01 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-19 Cont ID  
Sent By pleduc Date 2019-06-19 Time   Rev Time 0.00
Received By pleduc Date 2019-06-19 Time 16:28 Sent To  
Notes
2019-06-19 16:34:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE
 DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 COMPLYING WITH ALL OF THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM )
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM)
 OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE
 LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30
 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO
 UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH SECTION 7.9.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-21 Cont ID  
Sent By cpuell Date 2019-06-21 Time 11:59 Rev Time 0.00
Received By cpuell Date 2019-06-20 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-19 Cont ID  
Sent By lmarchan Date 2019-06-19 Time 16:49 Rev Time 0.00
Received By lmarchan Date 2019-06-14 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-12 Time 14:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-06-21 Cont ID  
Sent By jpearson Date 2019-06-21 Time 06:58 Rev Time 0.00
Received By jpearson Date 2019-06-21 Time 06:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-06-18 Cont ID  
Sent By jpearson Date 2019-06-18 Time 06:48 Rev Time 0.00
Received By jpearson Date 2019-06-18 Time 06:48 Sent To  
Notes
2019-06-18 06:48:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE AND SEAL.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 (A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. SELF-CERTIFICATION IS
 NOT ACCEPTABLE. ADDITIONALLY, THE DIGITAL SIGNATURE
 MUST INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER
 FAC 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481)
 2. PLANS WERE UPLOADED INCORRECTLY. THE PLAN SHEETS
 SHOULD BE UPLOADED TO THE DRAWINGS FOLDER. PROVIDE
 CORRECTION. WPB FBC 107.2.1 (STILL UPLOADED
 INCORRECTLY. EACH SHEET MUST BE UPLOADED SEPARATELY.
 CONTACT PERMIT LIBRARIANS FOR ASSISTANCE.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By jpearson Date 2019-06-13 Time 14:29 Rev Time 0.00
Received By jpearson Date 2019-06-13 Time 14:29 Sent To  
Notes
2019-06-13 14:29:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE AND SEAL.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. PLANS WERE UPLOADED INCORRECTLY. THE PLAN SHEETS
 SHOULD BE UPLOADED TO THE DRAWINGS FOLDER. PROVIDE
 CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  