Plan Review Details - Permit 19060508
Plan Review Stops For Permit 19060508
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By shill Date 2019-07-15 Time 10:46 Rev Time 0.00
Received By shill Date 2019-07-15 Time 10:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 09:58 Rev Time 0.00
Received By shill Date 2019-06-14 Time 09:58 Sent To  
Notes
2019-06-14 09:59:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, THE ASSEMBLY W-M-13 PROPOSED HAS A
 DESIGN PRESURE LIMITATION OF -80. SEE PAGE S0.1, DESIGN
 PRESSURE REQUIREMENTS FOR THIS ROOF ARE:
  
 ZONE 2 -65.8
 ZONE 3 -99.1
  
 SEE LIMITATION #7, ENHANCED FASTENING SHALL BE
 CALCULATED BY A QUALIFIED DESIGN PROFESSIONAL
 (ENGINEERING REQUIRED).
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-15 Cont ID  
Sent By shill Date 2019-07-15 Time 10:46 Rev Time 0.00
Received By shill Date 2019-07-11 Time 14:36 Sent To  
Notes
2019-07-12 14:36:51RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 09:59 Rev Time 0.00
Received By shill Date 2019-06-12 Time 09:11 Sent To  
Notes
2019-06-14 08:44:576/14 TO SH DESK
  
  