Plan Review Details - Permit 19060485
Plan Review Stops For Permit 19060485
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-18 Cont ID  
Sent By tklarge Date 2019-06-18 Time 09:04 Rev Time 0.00
Received By tklarge Date 2019-06-13 Time 15:36 Sent To  
Notes
2019-06-14 15:36:23RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-13 Cont ID  
Sent By tklarge Date 2019-06-13 Time 06:31 Rev Time 0.00
Received By tklarge Date 2019-06-11 Time 14:39 Sent To  
Notes
2019-06-12 14:39:14PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By tklarge Date 2019-06-18 Time 09:03 Rev Time 0.00
Received By tklarge Date 2019-06-18 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By tklarge Date 2019-06-13 Time 06:31 Rev Time 0.00
Received By tklarge Date 2019-06-13 Time 06:26 Sent To  
Notes
2019-06-13 06:31:091) SUBMIT FLOW CALCULATIONS FOR THE PREP SINK TO ENSURE
 THE GREASE INTERCEPTOR IS SIZED CORRECTLY. 2017 FBC-
 PLUMBING SEC. 1003.2.
 2) SHOW THE PREP SINK ON THE PLAN VEIEW AND THE RISER
 DIAGRAM AND SHOW THE SIZE OF THE PREP SINK DRAIN. WPB
 AMEND. TO FBC SEC. 107.2.1, 1003.3.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  