Plan Review Details - Permit 19060399
Plan Review Stops For Permit 19060399
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-14 Cont ID  
Sent By lcrespo Date 2019-06-14 Time 06:53 Rev Time 0.00
Received By lcrespo Date 2019-06-14 Time 06:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-14 Cont ID  
Sent By lcrespo Date 2019-06-14 Time 06:54 Rev Time 0.00
Received By lcrespo Date 2019-06-14 Time 06:53 Sent To  
Notes
2019-06-14 07:10:4506/15/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE
 PROPOSED BACKFLOW PREVENTION DEVICE, THIS CAN BE DONE
 BY GOING TO THE PROPERTY APPRAISER WEBSITE AND PRINT
 OUT A STRUCTURAL LAYOUT OF THE BUILDING AND HAND DRAW
 THE METER LOCATION WITH THE BACKFLOW.
  
 2.THE BACKFLOW (L7) THAT WAS SUBMITTED IS FOR UNDER
 GROUND INSTALLATION AND IT IS ALSO FURNISHED BY THE
 CITY OF WEST PALM BEACH UTILITIES DEPART, THIS DEVICE
 IS USED WHEN A POOL IS INSTALLED WITHOUT A POOL FILL.
 THE LF7R CANNOT BE USED FOR AS AN APPROVED DEVICE.
 PLEASE SPECIFY WHAT YOU ARE USING THE DEVICE FOR SO WE
 CAN DETERMINE WHICH ONE YOU NEED AND YOU MAY NEED A
 REDUCED PRESSURE ZONE
 (HTTPS://EN.WIKIPEDIA.ORG/WIKI/REDUCED_PR
 ESSURE_ZONE_DEVICE).
  
 3. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT
 OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
  
 4. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  