| 2019-06-09 09:32:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO PLAN SUBMITTED. DOCUMENTS SUPPLIED DO NOT EXPLAIN |
| | THE NATURE OF THE REPAIR. HOW LONG WILL THIS REPAIR |
| | TAKE AND WHAT DOES IT ENTAIL? PERMIT APPLICATION STATES |
| | THIS IS A REPAIR ON A 400 AMP BREAKER, BUT THE |
| | INFORMATION SUBMITTED SEEMS TO INDICATE THIS REPAIR IS |
| | ON A 4000 AMP BREAKER. CLARIFICATION NEEDED. PROVIDE |
| | MORE INFORMATION. WPB FBC 107.2.1 |
| | 2. PROVIDE METHOD OF COMPLIANCE WITH NEC 517.30(G). AN |
| | ENGINEER WILL BE REQUIRED TO VERIFY COMPLIANCE. NEC |
| | 517.30(G); FS 471.003(2)(H) |
| | 3. HOW WILL TWO SOURCES OF POWER BE MAINTAINED FOR THIS |
| | REPAIR? NEC 517.35 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |