Plan Review Details - Permit 19060241
Plan Review Stops For Permit 19060241
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-11 Cont ID  
Sent By shill Date 2019-09-11 Time 14:29 Rev Time 0.00
Received By shill Date 2019-09-08 Time 16:04 Sent To  
Notes
2019-09-11 14:29:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060241
 ADD: 477 S ROSEMARY AVE. SUITE 100
 CONT: VERTEX CONSTRUCTION INC.
 TEL: 561-619-7722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 16, 2019
 ACTION: BUILDING PROVISO
  
 1) SHEET S2.01 SHOWS VARIOUS BOLTED OR WELDED
 CONNECTIONS FOR THE NEW FRAMING MEMBERS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 FURTHER QUESTIONS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD 561-805-6666
  
 2) PRODUCT APPROVALS ARE TO BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 JAMES A. WITMER BN, PX, CBO / SENIOR COMMERCIAL
 COMBINATION PLANS EXAMINER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-13 Cont ID  
Sent By jwitmer Date 2019-08-13 Time 07:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2019-08-13 07:56:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060241
 ADD: 477 S ROSEMARY AVE. SUITE 100
 CONT: VERTEX CONSTRUCTION INC.
 TEL: 561-619-7722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 16, 2019
 ACTION: BUILDING PROVISO
  
 1) SHEET S2.01 SHOWS VARIOUS BOLTED OR WELDED
 CONNECTIONS FOR THE NEW FRAMING MEMBERS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 FURTHER QUESTIONS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD 561-805-6666
  
 2) PRODUCT APPROVALS ARE TO BE DEFERRED SUBMITTALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 JAMES A. WITMER BN, PX, CBO / SENIOR COMMERCIAL
 COMBINATION PLANS EXAMINER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By jwitmer Date 2019-07-16 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2019-07-15 Time 16:04 Sent To  
Notes
2019-07-16 15:54:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060241
 ADD: 477 S ROSEMARY AVE. SUITE 100
 CONT: VERTEX CONSTRUCTION INC.
 TEL: 561-619-7722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 16, 2019
 ACTION: DENIED
  
 1) ALS1.1- LIFE SAFETY SHEET:
  
 1A) PLEASE NOTE THE SUBMITTED PLAN INDICATES THIS
 BUILDING CONSTRUCTION TYPE AS TYPE IIA(UNSPRINKLERED).
 THE ORIGINAL BUILDING PERMIT 99081334 UNDER THE 1997
 SBC AND BUILDING TYPE WAS TYPE II FULLY SPRINKLERED.
 UNDER THE 1997 SBC AND THE 2001 FBC THERE WAS STILL A
 TYPE VI CONSTRUCTION. UNDER THE 2004 FBC THE TYPE VI
 CONSTRUCTION WAS DROPPED AND THE CONSTRUCTION TYPE FOR
 BUILDING WERE CONVERTED WITH AN EQUIVALENCY. UNDER THE
 1997 SBC TYPE II CONSTRUCTION = TYPE IB BUILDING
 CONSTRUCTION TYPE UNDER THE 2004 FBC AND STILL TODAY
 UNDER THE 2017 FBC-B. PLEASE UPDATE THE PLANS.
  
 1B) UNDER THE HEADING OF CLASSIFICATION OF WORK THE
 PLAN STATES THIS IS AN ALTERATION LEVEL II. THE LAST
 KNOWN USE FOR THIS TENANT SPACE WAS AN AMUSEMENT
 ARCADE/ BOWLING ALLEY AN A-3 ASSEMBLY OCCUPANCY. THE
 DESIGNER OF RECORD IS CLASSIFYING THE NEW OCCUPANCY
 TYPE AS BUSINESS OCCUPANCY. PLEASE REFER TO THE 2017
 EXISTING BUILDING CODE FOR CHANGE OF OCCUPANCY
 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. WHERE THE
 OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN
 EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY.
  
 1C) UNDER THE HEADING CONSTRUCTION THE PLANS INDICATE
 THE BUILDING IS UNSPRINKLERED. UNDER THE ORIGINAL
 PERMIT 99081334 AND CODE THE 1997 SBC THERE WERE 2 CODE
 SECTIONS THAT REQUIRED THE BUILDING TO BE FIRE
 SPRINKLERED.
 1997 SBC GROUP M OCCUPANCY WHERE THE 1ST FLOOR AREA
 EXCEEDS 15,000 SQ. FT. THE 2ND CODE SECTION DEALS WITH
 R2 OCCUPANCIES. AN APPROVED AUTOMATIC SPRINKLER SYSTEM
 SHALL BE PROVIDED THROUGHOUT GROUP R2 OCCUPANCIES 3
 STORIES AND HIGHER 903.7.6 1997 SBC.
  
 EXISTING BUILDING CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
  
 EXISTING BUILDING CODE 1012.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS OR
 WHERE THERE IS A CHANGE OF OCCUPANCY WITHIN A SPACE
 WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM
 THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING THAT REQUIRES AN AUTOMATIC FIRE
 SPRINKLER SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS
  
 2017 FBC-B [F] 903.2.11.3 BUILDINGS THREE STORIES OR
 MORE IN HEIGHT. ANY BUILDING WHICH IS OF THREE STORIES
 OR MORE IN HEIGHT SHALL BE EQUIPPED WITH AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION 903.1.
  
 1D) THE LIFE SAFETY SHEET INDICATES THE FLOOR PLAN
 DESIGN IS FOR A BUSINESS OCCUPANCY BUT THE PLANS DO NOT
 SHOW COMPLIANCE WITH SECTION 2902.1 & TABLE 2902.1 OF
 THE 2017 FBC-B NUMBER OF RESTROOMS, DRINKING FOUNTAINS
 (HIGH/ LOW) AND SERVICE SINK. THIS SPACE LOOKS MORE
 LIKE A SHELL SPACE WHERE THE CERTIFICATE OF OCCUPANCY
 WOULD BE REVOKED FOR THE SPACE.
  
 1E) FOR A BUSINESS OCCUPANCY PLEASE PROVIDE THE
 FURNITURE FLOOR PLANS FOR BOTH THE NORTH AND SOUTH
 TENANT SPACES. THIS WAY WE CAN CALCULATE COMMON PATH OF
 TRAVEL, TABLE 1006.2.1 FBC-B AND DEAD ENDS IF THEY
 OCCUR, SEE 1020.4 FBC-B.
  
 1F) PLEASE DECLARE THE REAR EXITS OCCUR HOW FAR IT IS
 TO THE PROPERTY LINE. PLEASE PROVIDE WHAT IS PAST THE
 PROPERTY LINE AND COMPLIANCE WITH 2017 FBC-B SECTIONS:
 1028.2 EXIT DISCHARGE WIDTH OR CAPACITY. THE MINIMUM
 WIDTH OR REQUIRED CAPACITY OF THE EXIT DISCHARGE SHALL
 BE NOT LESS THAN THE MINIMUM WIDTH OR REQUIRED CAPACITY
 OF THE EXITS BEING SERVED.
  
 1028.3 EXIT DISCHARGE COMPONENTS. EXIT DISCHARGE
 COMPONENTS SHALL BE SUFFICIENTLY OPEN TO THE EXTERIOR
 SO AS TO MINIMIZE THE ACCUMULATION OF SMOKE AND TOXIC
 GASES.
  
 2) SHEET S0.01 WALL & ROOF CHART FOR BUILDINGS < 60
 FEET IS IN VULT NOT VASD. PLEASE PROVIDE THE PRESSURES
 POSITIVE AND NEGATIVE IN VASD SINCE THE PRODUCT
 APPROVALS ARE IN VASD. 2017 FBC-B 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3) SHEET S2.01 SHOWS VARIOUS BOLTED OR WELDED
 CONNECTIONS FOR THE NEW FRAMING MEMBERS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-12 Cont ID  
Sent By jpearson Date 2019-09-12 Time 08:38 Rev Time 0.00
Received By jpearson Date 2019-09-12 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-08 Cont ID  
Sent By jpearson Date 2019-08-08 Time 11:22 Rev Time 0.00
Received By jpearson Date 2019-08-08 Time 11:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By jpearson Date 2019-07-15 Time 08:44 Rev Time 0.00
Received By jpearson Date 2019-07-15 Time 08:44 Sent To  
Notes
2019-07-15 07:54:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROPOSED RISER DIAGRAM FOR THE SOUTH WALL SHOWS A
 FEEDER FROM THE SERVICE MAIN TO A GUTTER THAT FEEDS 3
 METERS AND DISCONNECTS FOR THE UNITS. THERE IS AN
 EQUIPMENT GROUNDING CONDUCTOR CONTAINED IN THIS FEEDER,
 AND THE GROUNDING ELECTRODE IS CONNECTED AT THE MAIN.
 THERFORE, A GROUNDING ELECTRODE SHOULD NOT BE CONNECTED
 FROM THE GUTTER TO THE GROUND BAR, CREATING A PARALLEL
 PATH. THE GROUNDED CONDUCTOR IN THE METERS SHOULD BE
 ISOLATED AND THE EGC USED FOR GROUNDING PURPOSES ON THE
 LOAD SIDE OF THE MAIN DISCONNECT. PROVIDE CORRECTION.
 NEC 250.6, 250.24
 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-23 Cont ID  
Sent By pleduc Date 2019-08-23 Time   Rev Time 0.00
Received By pleduc Date 2019-08-23 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-31 Cont ID  
Sent By pleduc Date 2019-07-31 Time   Rev Time 0.00
Received By pleduc Date 2019-07-31 Time 09:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 16:57 Sent To  
Notes
2019-06-20 17:07:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY CERTIFIED
 CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY
 CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-09-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-22 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 14:40 Rev Time 0.00
Received By gjohnson Date 2019-07-30 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-24 Cont ID  
Sent By lmarchan Date 2019-07-24 Time 16:09 Rev Time 0.00
Received By lmarchan Date 2019-06-19 Time 16:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-16 Cont ID  
Sent By jwitmer Date 2019-07-16 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2019-07-16 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-09-11 Cont ID  
Sent By ccole Date 2019-09-11 Time 16:36 Rev Time 0.00
Received By ccole Date 2019-09-11 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-08 Cont ID  
Sent By pvalenti Date 2019-08-08 Time 16:26 Rev Time 0.00
Received By ccole Date 2019-08-08 Time 16:26 Sent To  
Notes
2019-08-08 16:27:402ND REVIEW MECHANICAL:
  
 APPROVED BY CHRIS COLE (REMOTELY).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By ccole Date 2019-07-16 Time 12:15 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 12:15 Sent To  
Notes
2019-07-16 12:31:051ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060241
 7/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.2: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW FCU'S IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC AND SECTION 312.1 FBC M.
  
 2) M1.2: REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 3) M1.2: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 FCU'S- SECTION 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-06 Cont ID  
Sent By rmcdouga Date 2019-09-06 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2019-09-06 Time 09:29 Sent To  
Notes
2019-09-06 09:30:24PASSED BY T HUNT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 14:35 Rev Time 0.00
Received By gjohnson Date 2019-08-19 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-07-16 Cont ID  
Sent By gjohnson Date 2019-07-16 Time 16:42 Rev Time 0.00
Received By gjohnson Date 2019-07-16 Time 16:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-09-11 Cont ID  
Sent By shill Date 2019-09-11 Time 14:34 Rev Time 0.00
Received By shill Date 2019-09-11 Time 14:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 14:40 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2019-08-19 14:37:17PLUMB SHEET OK
2019-08-08 11:22:51ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 07:06 Rev Time 0.00
Received By shill Date 2019-07-19 Time 07:05 Sent To  
Notes
2019-07-15 06:45:29ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. THE DIGITAL SIGNATURE MUST INCLUDE
 THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By eschneid Date 2019-08-29 Time 15:52 Rev Time 0.25
Received By eschneid Date 2019-08-29 Time 14:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-08-01 Cont ID  
Sent By eschneid Date 2019-08-01 Time 16:13 Rev Time 0.50
Received By eschneid Date 2019-08-01 Time 13:40 Sent To  
Notes
2019-08-01 16:13:36FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE CITYPLACE RETAIL MANAGEMENT
 APPROVAL WAS NOT PROVIDED. EITHER PROVIDE STAMPED PLANS
 OR A LETTER CITING THE PLANS THAT CITYPLACE RETAIL
 MANAGEMENT IS APPROVING. --- THE RESPONSE STATED THAT
 THE APPROVAL LETTER WAS INCLUDED WITH THE RESUBMITTAL,
 BUT STAFF WAS UNABLE TO LOCATE THE LETTER IN THE
 UPLOADED FILES.
  
 2) REPEAT COMMENT: THE ROSEMARY RETAIL CORRIDOR SUBAREA
 REQUIRES THAT THE STOREFRONTS ALONG ROSEMARY AVENUE AND
 FERN STREET HAVE A MINIMUM OF 60% TRANSPARENCY. PROVIDE
 VERIFICATION, IN ACCORDANCE WITH SECTION 94-109 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, THAT THE
 MINIMUM TRANSPARENCY IS BEING PROVIDED. --- SHEET
 A2.0.1 STATES THAT THE TRANSPARENCY ALONG ROSEMARY
 AVENUE IS 61% AND THE TRANSPARENCY ALONG FERN STREET IS
 60%. PROVIDE THE LINEAR FEET OF FRONTAGE OF THE BAY FOR
 EACH STREET FRONT AND THE DIMENSIONS AND SQUARE FOOTAGE
 OF EACH GLAZED OPENING (EXISTING AND PROPOSED) ALONG
 BOTH STREET FRONTAGES SO THAT ZONING STAFF CAN VERIFY
 YOUR GLAZING PERCENTAGES.
  
 A. THE TABLE PROVIDED FOR THE ROSEMARY AVENUE FRONTAGE
 LOOKS TO HAVE TRANSPOSED THE MEASUREMENT VALUES.
 B. THE SCOPE OF WORK INCLUDES THE ENTIRE FORMER
 REVOLUTIONS SPACE; THEREFORE THE ENTIRE ROSEMARY
 FRONTAGE MUST BE USED TO VERIFY COMPLIANCE WITH THE 60%
 GLAZING REQUIREMENT.
 C. STAFF?S ROUGH CALCULATIONS DO NOT VERIFY THAT FERN
 STREET HAS 60% GLAZING.
 D. THE TABLE PROVIDED FOR THE FERN STREET FRONTAGE
 LISTS DIFFERENT NUMBERS IN THE MEASUREMENT VALUES THAN
 IT DOES IN THE CALCULATION LINE.
  
 3) PROVIDE VERIFICATION THAT THE NEW EXTERIOR LIGHTS
 COMPLY WITH THE LIGHTING REQUIREMENTS OF SECTION
 94-113(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. --- THE NOTATION THAT WAS ADDED REGARDING
 THE LIGHTING LEVELS NEEDS TO BE INCLUDED ON THE SIGNED
 AND SEALED DRAWINGS DONE BY THE LIGHTING ENGINEER NOT
 ON THE ARCHITECTURAL PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By eshcneid Date 2019-07-24 Time 15:30 Rev Time 0.50
Received By eschneid Date 2019-07-24 Time 15:16 Sent To  
Notes
2019-07-24 15:59:40FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL WAS NOT
 PROVIDED. EITHER PROVIDE STAMPED PLANS OR A LETTER
 CITING THE PLANS THAT CITYPLACE RETAIL MANAGEMENT IS
 APPROVING.
  
 2) THE ROSEMARY RETAIL CORRIDOR SUBAREA REQUIRES THAT
 THE STOREFRONTS ALONG ROSEMARY AVENUE AND FERN STREET
 HAVE A MINIMUM OF 60% TRANSPARENCY. PROVIDE
 VERIFICATION, IN ACCORDANCE WITH SECTION 94-109 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, THAT THE
 MINIMUM TRANSPARENCY IS BEING PROVIDED.
  
 3) PROVIDE VERIFICATION THAT THE NEW EXTERIOR LIGHTS
 COMPLY WITH THE LIGHTING REQUIREMENTS OF SECTION
 94-113(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]