Plan Review Details - Permit 19060211
Plan Review Stops For Permit 19060211
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-06 Cont ID  
Sent By tklarge Date 2019-06-06 Time 08:10 Rev Time 0.00
Received By tklarge Date 2019-06-06 Time 08:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By tklarge Date 2019-06-06 Time 08:10 Rev Time 0.00
Received By tklarge Date 2019-06-06 Time 07:42 Sent To  
Notes
2019-06-06 07:42:431) SUBMIT A ROOF PLAN SHOWING THE LOCATION OF THE ROOF
 DRAINS AND THE TERMINATION POINTS OF THE STORM DRAIN
 PIPING. WPB AMEND. TO FBC SEC. 107.2.1.
 2) CLEANOUTS ARE REQUIRED IN THE STORM RISERS PER 2017
 FBC-PLUMBING SEC.1101.8.
 3) WHAT PROVISIONS ARE BEING MADE FOR SECONDARY
 (EMERGENCY OVERFLOW) PROVISIONS? INDICATE ON THE
 PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 4) ROOF DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT
 AWAY FROM THE STRUCTURE SIDEWALL PER 2017 FBC-BUILDING
 SEC.1503.7.
 5) SUBMIT CALCULATIONS FOR THE ROOF DRAIN SIZING.
 COMPLY WITH 2017 FBC-PLUMBING SEC. 1105.2. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE TYPE OF ROOF
 DRAINS BEING INSTALLED.
 6) INDICATE ON THE PLANS THE TYPE OF MATERIAL BEING
 INSTALLED FOR THE STORM DRAIN PIPING ABOVEGROUND.2017
 FBC-PLUMBING TABLE 702.1.
 7) INDICATE ON THE PLANS WHERE AND HOW THE ABOVEGROUND
 PIPING IS CONNECTING TO ANY UNDERGROUND PIPING. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW