Plan Review Details - Permit 19060192
Plan Review Stops For Permit 19060192
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-26 Cont ID  
Sent By shill Date 2019-08-26 Time 17:01 Rev Time 0.00
Received By skennedy Date 2019-08-26 Time 17:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-27 Cont ID  
Sent By jpearson Date 2019-08-27 Time 07:59 Rev Time 0.00
Received By jpearson Date 2019-08-27 Time 07:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-23 Cont ID  
Sent By J.Walker Date 2019-08-23 Time   Rev Time 0.00
Received By jwalker Date 2019-08-23 Time   Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-05 Cont ID  
Sent By lmarchan Date 2019-09-05 Time 11:26 Rev Time 0.00
Received By lmarchan Date 2019-08-30 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-27 Cont ID  
Sent By lmarchan Date 2019-08-27 Time 10:32 Rev Time 0.00
Received By lmarchan Date 2019-08-22 Time 13:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By tklarge Date 2019-09-05 Time 10:49 Rev Time 0.00
Received By tklarge Date 2019-09-05 Time 10:19 Sent To  
Notes
2019-09-05 10:43:51WATER RISER DIAGRAM TO BE SUBMITTED ON TENANT BUILDOUT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-27 Cont ID  
Sent By gjohnson Date 2019-08-27 Time 10:26 Rev Time 0.00
Received By tklarge Date 2019-08-26 Time 17:29 Sent To  
Notes
2019-08-27 10:25:531) SUBMIT A SANITARY RISER AND CORRESPONDING WATER
 RISER DIAGRAM FOR REVIEW. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 2) THE PLAN VIEW OF THE UNDERGROUND PLUMBING APPEARS TO
 SHOW FLAT, DRY VENTS. VENTS SHALL CONNECT TO A
 HORIZONTAL DRAIN ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAIN PIPE. 2017 FBC-PLUMBING SEC.905.3.
 3) THE PLAN VIEW SHOWS A SINK AND ICEMAKER DISCHARGING
 INTO A HORIZONTAL WET VENT. ONLY FIXTURES IN A BATHROOM
 GROUP SHALL DISCHARGE INTO THE WET VENT. 2017
 FBC-PLUMBING SEC.912.1.
 4) NOT MORE THAN ONE WET VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION. 2017 FBC-PLUMBING SEC.912.2.1.
 5) THE NUMBER OF THE TYPE OF FIXTURES PERMITTED TO BE
 WET VENTED HAS BEEN EXCEEDED. REFER TO THE DEFINITION
 OF "BATHROOM GROUP" IN CHAPTER 2 OF THE 2017
 FBC-PLUMBING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By tklarge Date 2019-09-09 Time 10:27 Rev Time 0.00
Received By tklarge Date 2019-09-05 Time 10:50 Sent To  
Notes
2019-09-05 10:50:44SIGNATURE ON PLUMBING SHEET OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-08-26 Cont ID  
Sent By skennedy Date 2019-08-26 Time 17:01 Rev Time 0.00
Received By skennedy Date 2019-08-26 Time 17:01 Sent To  
Notes
***NONE***