Plan Review Details - Permit 19060160
Plan Review Stops For Permit 19060160
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By jbrooks Date 2019-06-25 Time 11:21 Rev Time 0.00
Received By jbrooks Date 2019-06-25 Time 11:21 Sent To  
Notes
2019-06-25 11:22:17JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 RESULTS: DENIED
 1. FBC B 107.1 SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.
 2. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
 3. FBC B 1803.5.2. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED. PROVIDE TWO SETS.
 4. FBC B 107.2.1. PROVIDE A LEGIBLE PLAN TO PROVIDE THE
 FOLLOWING INFORMATION: TOTAL NUMBER OF PARKING SPACES;
 NUMBER OF ACCESSIBLE SPACES; LOCATION OF ACCESSIBLE
 ENTRANCES; SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY;
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE.
 5. FBC A 502.3. WHERE THE ACCESSIBLE ROUTE MUST CROSS
 VEHICULAR TRAFFIC LANES, MARKED CROSSINGS ENHANCE
 PEDESTRIAN SAFETY; PLEASE INDICATE LOCATION ON PLAN.
 6. FBC A 208.2.1. THE FOLLOWING USES HAVE ADDITIONAL
 PARKING REQUIREMENTS: HOSPITAL OUTPATIENT FACILITIES;
 REHABILITATION FACILITIES; OUTPATIENT PHYSICAL THERAPY
 FACILITIES. PLAN IS TO EITHER SHOW LOCATION OF TENANTS
 WITH ANY OF THE ABOVE USES OR PLAN IS TO INCLUDE A
 STATEMENT WHICH STATES THAT NONE OF THE ABOVE USES
 (HOSPITAL OUTPATIENT FACILITIES, REHABILITATION
 FACILITIES, OUTPATIENT PHYSICAL THERAPY FACILITIES) ARE
 AT THIS LOCATION.
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-06-12 Cont ID  
Sent By rrossano Date 2019-06-12 Time   Rev Time  
Received By rrossano Date 2019-06-12 Time   Sent To B
Notes
2019-06-12 07:38:44PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 SHOW HOW ADDITIONAL DRAINAGE WILL BE ACCOMMODATED. FOR
 ANY RECONSTRUCTION OF A PARKING LOT, THE OWNER SHOULD
 INSTALL A DRAINAGE SYSTEM TO PROVIDE WATER QUALITY
 TREATMENT OF THE STORMWATER RUNOFF, WHETHER IT BE
 PERVIOUS PAVERS, AN EXFILTRATION TRENCH, OR BIOSWALE.
  
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, SECTION
 94-35, SITE PLAN REVIEW
  
 (C) SITE DESIGN QUALITATIVE DEVELOPMENT STANDARDS.
 (11) STORMWATER CONTROL. APPROPRIATE MEASURES SHALL BE
 TAKEN TO ENSURE THAT REMOVAL OF STORMWATER WILL NOT
 ADVERSELY AFFECT NEIGHBORING PROPERTIES OR THE PUBLIC
 STORM DRAINAGE SYSTEM. PROVISIONS SHALL BE MADE FOR THE
 CONSTRUCTION OF FACILITIES, INCLUDING GRADING, GUTTERS,
 PIPING AND THE TREATMENT OF TURF, TO ACCOMMODATE
 STORMWATER AND TO PREVENT EROSION AND THE FORMATION OF
 SILT.
  
 WATER QUALITY CRITERIA RETENTION/DETENTION REQUIREMENTS
 VOLUME IS CALCULATED AS: WET DETENTION VOLUME SHALL BE
 PROVIDED FOR THE FIRST INCH OF RUNOFF FROM THE
 DEVELOPED PROJECT, OR THE TOTAL RUNOFF OF 2.5-INCHES
 TIMES THE PERCENTAGE OF IMPERVIOUSNESS, WHICHEVER IS
 GREATER,
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By jbrooks Date 2019-06-25 Time 11:23 Rev Time 0.00
Received By jbrooks Date 2019-06-05 Time 15:14 Sent To  
Notes
2019-06-06 15:14:22ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-11 Cont ID  
Sent By ajones Date 2019-06-11 Time 09:36 Rev Time 0.00
Received By ajones Date 2019-06-11 Time 09:36 Sent To ENG
Notes
***NONE***