Plan Review Details - Permit 19060132
Plan Review Stops For Permit 19060132
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-06 Cont ID  
Sent By shill Date 2019-08-06 Time 07:20 Rev Time 0.00
Received By dbattles Date 2019-08-02 Time 15:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-18 Cont ID  
Sent By jpearson Date 2019-12-18 Time 07:55 Rev Time 0.00
Received By jpearson Date 2019-12-18 Time 06:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By jpearson Date 2019-07-24 Time 15:20 Rev Time 0.00
Received By jpearson Date 2019-07-24 Time 15:20 Sent To  
Notes
2019-07-24 15:20:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-508 SHOWS PANEL L8N2 WITH A LOAD OF 114
 AMPS. THIS PANEL IS FED FROM A 100 AMP BREAKER AND A
 100 AMP FEEDER. PROVIDE CORRECTION. NEC 215.2, 240.4,
 310.15(B)(16)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By pleduc Date 2019-07-19 Time   Rev Time 0.00
Received By pleduc Date 2019-07-19 Time 10:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By gjohnson Date 2019-12-19 Time 15:54 Rev Time 0.00
Received By gjohnson Date 2019-12-19 Time 15:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By gjohnson Date 2019-07-18 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2019-07-18 Time 14:22 Sent To  
Notes
2019-07-18 14:39:241ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. THE 1" SECTION OF PIPE FEEDING THE KITCHEN AND
 LAUNDRY ON GROUND FLOOR WITH A CFH 1131 IS UNDERSIZED
 AT 300' DEVELOPED LENGTH IT SHALL BE 11/4" PER FBC FG
 TABLE 402.4(5)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-21 Cont ID  
Sent By shill Date 2020-03-21 Time 10:07 Rev Time 0.00
Received By shill Date 2020-02-07 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-31 Cont ID  
Sent By cpuell Date 2019-12-31 Time 13:18 Rev Time 0.00
Received By cpuell Date 2019-11-21 Time 07:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-07 Cont ID  
Sent By lmarchan Date 2019-08-07 Time 10:59 Rev Time 0.00
Received By lmarchan Date 2019-07-01 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-12 Cont ID  
Sent By ccole Date 2019-12-12 Time 12:02 Rev Time 0.00
Received By ccole Date 2019-12-11 Time 15:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-02 Cont ID  
Sent By ccole Date 2019-08-02 Time 15:40 Rev Time 0.00
Received By ccole Date 2019-08-02 Time 16:40 Sent To  
Notes
2019-08-02 15:40:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT#19060132
 8/2/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED SHEETS M102 & M103 THAT ARE LISTED IN THE
 REVISION NARRATIVE WERE NOT UPLOADED FOR REVIEW. PLEASE
 PROVIDE THE PLAN SHEETS- SECTION 107.2.1 WPB.
  
 2) M105: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF AIR HANDLERS HAVING A CAPACITY
 GREATER THAN 2000 CFMS- SECTION 606.2.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-02-21 Cont ID  
Sent By gjohnson Date 2020-02-21 Time 11:34 Rev Time 0.00
Received By gjohnson Date 2020-02-21 Time 11:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By gjohnson Date 2019-12-19 Time 15:54 Rev Time 0.00
Received By gjohnson Date 2019-12-19 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By gjohnson Date 2019-07-18 Time 14:39 Rev Time 0.00
Received By gjohnson Date 2019-07-16 Time 10:40 Sent To  
Notes
2019-07-18 14:56:381ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE TRENCH DRAIN AND THE SAND/OIL INTERCEPTOR SHALL
 BE VENTED. PER FBC PL 901.2.1
  
 2. PROVIDE SIZING CALCULATION FOR SAND/OIL INTERCEPTOR
 PER FBC PL 1003.4.2.2
  
 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION
 GUIDE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-02-27 Cont ID  
Sent By shill Date 2020-02-27 Time 17:54 Rev Time 0.00
Received By shill Date 2020-02-27 Time 17:54 Sent To  
Notes
2020-02-07 14:50:17APPLICANT UPLOADED SHEET P903 FOR SIGNATURES - P103 WAS
 NOT SUBMITTED AS PART OF THIS REVISION. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-01-06 Cont ID  
Sent By shill Date 2020-01-06 Time 11:39 Rev Time 0.00
Received By shill Date 2020-01-06 Time 11:35 Sent To  
Notes
2020-01-06 11:35:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
 P103 IS NOT DIGITALLY SIGNED. WHEN RESUBMITTING,
 PROVIDE A DIGITALLY SIGNED DOCUMENT, FS471.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-02 Cont ID  
Sent By shill Date 2019-08-02 Time 16:12 Rev Time 0.00
Received By shill Date 2019-08-02 Time 16:12 Sent To  
Notes
2019-08-02 16:13:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DIGITAL SIGNATURES OK; NEW PAGES SUBMITTED NEXT CYCLE
 REQUIRE REVIEW
  
  
2019-07-24 13:36:06ELECTRICAL SHEETS OK.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-03-17 Cont ID  
Sent By aaponte Date 2020-03-17 Time 12:20 Rev Time 0.00
Received By aaponte Date 2020-03-17 Time 12:20 Sent To  
Notes
2020-03-17 12:21:26PROVISO:
 1. TRANSFORMER ON BANYAN SHALL BE SCREENED WITH A
 DECORATIVE PANEL AS TALL AS EQUIPMENT.
 2. ROOF TOP EQUIPMENT SHALL BE SCREENED WITH A SCREEN
 AS TALL AS EQUIPMENT.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-12-31 Cont ID  
Sent By aaponte Date 2019-12-31 Time 12:44 Rev Time 0.00
Received By aaponte Date 2019-12-31 Time 12:44 Sent To  
Notes
2019-12-31 12:48:111. PROPOSED GATE FOR TRANSFORMER ALONG BANYAN BOULEVARD
 IS NOT COMPLEMENTARY TO THE GROUND FLOOR DESIGN. GATE
 SHALL BE AN AESTHETICALLY PLEASING DESIGN THAT
 MINIMIZES THE NEGATIVE IMPACT OF NOT PROVIDING AN
 ACTIVE USE AT THAT LOCATION. ORIGINAL SITE PLAN
 APPROVAL HAD AN ACTIVE USE AND A STOREFRONT. PLEASE
 PROVIDE SOME ALTERNATIVES FOR THE DESIGN. PLEASE
 SCHEDULE A SEPARATE MEETING WITH STAFF TO DISCUSS
 ALTERNATIVES.
 2. PLEASE REMEMBER PROPOSED GREEN WALL ALONG THE EAST
 ELEVATION CANNOT BE ARTIFICIAL PLANT MATERIAL.
 FOR ADDITIONAL INFORMATION PELASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By aaponte Date 2019-08-05 Time 16:52 Rev Time 0.00
Received By aaponte Date 2019-08-05 Time 16:52 Sent To  
Notes
2019-08-05 17:04:441. STEPS INDICATED ON THE EAST SIDE OF BUILDING DO NOT
 PROVIDE MINIMUM SIDEWALK CLEARANCE. A MINIMUM OF 8 FEET
 CLEARANCE SHALL BE PROVIDED.
 2. PLEASE PROVIDE PROPOSED LANDSCAPE AND HARDSAPCE
 DRAWINGS OF THE AREA TO INDICATE HOW ALL THE ELEMENTS
 INTERACT AND CONFIRM CLEARANCE IS PROVIDED.
 3. PLEASE PROVIDE INFORMATION ON THE DIFFERENCE BETWEEN
 THE CEMENTITIOUS PANEL WOOD GRAIN AND THE EXTERIOR
 INSULATED FINISH SYSTEM PROPOSED NOW. PROVIDE SAMPLE OF
 BOTH MATERIALS. SITE PLAN APPROVAL MATERIAL WAS
 SIMULATED WOOD PANEL.
 4. PLEASE PROVIDE DETAILS ON THE PROPOSED DOOR FOR THE
 TRANSFORMER ROOM FACNG BANYAN BOULEVARD.
 5. PLEASE SHOW THE SETBACK LINE AND PROPOSED CURB LINE
 ON NARCISSUS AVENUE, AS WELL AS PROPOSED LANDSCAPE TO
 IDENTIFY ANY POSSIBLE CONFLICTS WITH THE RESTAURANT
 EXIT STAIRS.
 6 A MINOR SITE PLAN AMENDMENT SHALL BE SUBMITTED TO THE
 PLANNING OFFICE FOR THE ENTIRE PROJECT TO REFLECT ALL
 CHANGES SINCE SITE PLAN APPROVAL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.