Plan Review Details - Permit 19060112
Plan Review Stops For Permit 19060112
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-10 Cont ID  
Sent By bwoods Date 2019-06-10 Time 00:00 Rev Time  
Received By bwoods Date 2019-06-10 Time 00:00 Sent To M
Notes
2019-06-10 10:16:50THESE PROVISO AND COMMENTS WILL BE VERIFIED AND
 CONFIRMED AT THE TIME OF FIRE INSPECTION. FAILURE TO
 FOLLOW THESE PROVISO WILL RESULT IN A FAILED
 INSPECTION.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO
 RELOCATED DROPS MAY NOT BE ISOLATED; HOWEVER, THE FLOOR
 AREA MAY BE TESTED AT 200PSI FOR 2 HOURS.
 IF NOT:
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
 USE FIRE PUMP PRESSURE FOR WORKING PRESSURE
 CALCULATIONS
  
 3.3.23 SYSTEM WORKING PRESSURE. THE MAXIMUM ANTICIPATED
 STATIC (NONFLOWING) OR FLOWING PRESSURE APPLIED TO
 SPRINKLER
 SYSTEM COMPONENTS EXCLUSIVE OF SURGE PRESSURES AND
 EXCLUSIVE
 OF PRESSURE FROM THE FIRE DEPARTMENT CONNECTION.
  
 25.2 ACCEPTANCE REQUIREMENTS.
 25.2.1* HYDROSTATIC TESTS.
 25.2.1.1 UNLESS PERMITTED BY 25.2.1.2 THROUGH 25.2.1.8,
 ALL
 PIPING AND ATTACHED APPURTENANCES SUBJECTED TO SYSTEM
 WORKING
 PRESSURE SHALL BE HYDROSTATICALLY TESTED AT 200 PSI
 (13.8 BAR)
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2
 HOURS.
 25.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM
 WORKING PRESSURES IN EXCESS OF 150 PSI (10.4 BAR) SHALL
 BE
 TESTED AS DESCRIBED IN 25.2.1.1, AT A PRESSURE OF 50
 PSI (3.5 BAR)
 IN EXCESS OF SYSTEM WORKING PRESSURE.
 25.2.1.3 WHERE COLD WEATHER WILL NOT PERMIT TESTING
 WITH WATER,
 AN INTERIM AIR TEST SHALL BE PERMITTED TO BE CONDUCTED
 AS
 DESCRIBED IN 25.2.2. THIS PROVISION SHALL NOT REMOVE OR
 REPLACE
 THE REQUIREMENT FOR CONDUCTING THE HYDROSTATIC TEST AS
 DESCRIBED
 IN 25.2.1.1.
 25.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL
 NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
 25.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING
 SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW
 PORTION
 SHALL BE ISOLATED AND TESTED AT NOT LESS THAN 200 PSI
 (13.8 BAR)
 FOR 2 HOURS.
 25.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED
 DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM
 WORKING
 PRESSURE.
 25.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE
 PRESSURE
 OR VISUAL LEAKAGE.
 25.2.1.8* THE TEST PRESSURE SHALL BE READ FROM A GAUGE
 LOCATED
 AT THE LOW ELEVATION POINT OF THE SYSTEM OR PORTION
 BEING
 TESTED. THE PRESSURES IN PIPING AT HIGHER ELEVATIONS
 SHALL BE
 PERMITTED TO BE LESS THAN 200 PSI (13.8 BAR) WHEN
 ACCOUNTING
 FOR ELEVATION LOSSES. SYSTEMS OR PORTIONS OF SYSTEMS
 THAT CAN BE
 ISOLATED SHALL BE PERMITTED TO BE TESTED SEPARATELY.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-10 Cont ID  
Sent By lmarchan Date 2019-06-10 Time 13:03 Rev Time 0.00
Received By lmarchan Date 2019-06-04 Time 14:09 Sent To  
Notes
2019-06-05 14:09:22ROUTED TO FIRE INBOX