Plan Review Details - Permit 19060088
Plan Review Stops For Permit 19060088
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-01 Cont ID  
Sent By shill Date 2019-08-01 Time 14:29 Rev Time 0.00
Received By shill Date 2019-08-01 Time 14:29 Sent To  
Notes
2019-08-01 14:29:10ACTION: BUILDING PROVISO
  
 1) THE BASE REQUIRED FOR TILE WALLS IN SHOWERS SHALL
 COMPLY WITH THE 2017 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURE'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
  
 TABLE 2509.2 / BACKERBOARD MATERIALS
  
 MATERIAL-----------------------------------------------
 ------------ STANDARD
  
 GLASS MAT GYPSUM BACKING PANEL
 ---------------------------ASTM C1178
  
 NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM
 C1288 OR ISO 8336,
 CATEGORY C
  
 NONASBESTOS FIBER-MAT REINFORCED
 ------------------------ASTM 1325
 CEMENTITIOUS BACKER UNIT
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 06:49 Rev Time 0.00
Received By shill Date 2019-07-19 Time 06:49 Sent To  
Notes
2019-07-19 06:49:36ACTION: BUILDING PROVISO
  
 1) THE BASE REQUIRED FOR TILE WALLS IN SHOWERS SHALL
 COMPLY WITH THE 2017 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURE'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
  
 TABLE 2509.2 / BACKERBOARD MATERIALS
  
 MATERIAL-----------------------------------------------
 ------------ STANDARD
  
 GLASS MAT GYPSUM BACKING PANEL
 ---------------------------ASTM C1178
  
 NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM
 C1288 OR ISO 8336,
 CATEGORY C
  
 NONASBESTOS FIBER-MAT REINFORCED
 ------------------------ASTM 1325
 CEMENTITIOUS BACKER UNIT
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-06-17 Cont ID  
Sent By jwitmer Date 2019-06-17 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2019-06-17 Time 09:40 Sent To  
Notes
2019-06-17 12:46:562017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060088
 ADD: 2450 PRESIDENTIAL WAY SUITE: 1906
 CONT: A. C. E. & M CONSTRUCTION GROUP
 TEL: 561-716-3563
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 17/2019
 ACTION: BUILDING PROVISO
  
 1) THE BASE REQUIRED FOR TILE WALLS IN SHOWERS SHALL
 COMPLY WITH THE 2017 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURE'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
  
 TABLE 2509.2 / BACKERBOARD MATERIALS
  
 MATERIAL-----------------------------------------------
 ------------ STANDARD
  
 GLASS MAT GYPSUM BACKING PANEL
 ---------------------------ASTM C1178
  
 NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM
 C1288 OR ISO 8336,
 CATEGORY C
  
 NONASBESTOS FIBER-MAT REINFORCED
 ------------------------ASTM 1325
 CEMENTITIOUS BACKER UNIT
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-31 Cont ID  
Sent By jleahy Date 2019-07-31 Time 09:06 Rev Time 0.00
Received By jleahy Date 2019-07-31 Time 09:06 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-07-25 Cont ID  
Sent By jleahy Date 2019-07-25 Time 12:39 Rev Time 0.00
Received By jleahy Date 2019-07-25 Time 12:39 Sent To P
Notes
2019-07-25 12:40:08ONLY ONE SET SUBMITTED JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-19 Cont ID  
Sent By jleahy Date 2019-07-19 Time 12:45 Rev Time 0.00
Received By jleahy Date 2019-07-19 Time 12:45 Sent To  
Notes
2019-07-19 12:46:18FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONLY ONE SET OF PLANS TO REVIEW
  
 NO ELECTRIC SHOWN FOR TUB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-24 Cont ID  
Sent By jleahy Date 2019-06-24 Time 11:14 Rev Time 0.00
Received By jleahy Date 2019-06-24 Time 11:14 Sent To  
Notes
2019-06-24 11:15:38FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW ELECTRICAL WORK INVOLVED ON PLAN.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-08 Cont ID  
Sent By pleduc Date 2019-07-08 Time   Rev Time 0.00
Received By pleduc Date 2019-07-08 Time 14:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-07 Cont ID  
Sent By pleduc Date 2019-06-07 Time   Rev Time 0.00
Received By pleduc Date 2019-06-07 Time 14:11 Sent To  
Notes
2019-06-07 14:18:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE INFORMATION SUBMITTED ON THE PLAN SHEETS IS
 INSUFFICIENT TO REVIEW FOR FIRE CODE COMPLIANCE
 PURPOSES.
  
  
 1) THERE IS NO SCOPE OF WORK SUBMITTED FOR THIS
 PROJECT.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION,
 CONSTRUCTION DOCUMENTS AND SHOP DRAWINGS SHALL BE
 SUBMITTED, REVIEWED, AND A
 PPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN
 SECTION 1.14.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK INCLUDING WHAT
 IS TO BE DEMOED AND NEW.
  
  
  
  
 2) THERE ARE NO INDICATIONS OF ANY FIRE ALARM OR FIRE
 SPRINKLER PROTECTION INDICATED OR AFFECTED.
  
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
 (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION DOCUMENTS ON SITE.
  
  
 PLEASE PROVIDE DETAILS OF ANY EXISTING SYSTEMS AND AN
 APPLICABLE NOTE THAT ANY WORK ON THE FA OR FS SYSTEMS
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-04 Cont ID  
Sent By cpuell Date 2019-08-04 Time 08:42 Rev Time 0.00
Received By cpuell Date 2019-07-26 Time 14:09 Sent To  
Notes
2019-08-01 14:31:56TO TL DESK
  
2019-07-30 14:09:15RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-26 Cont ID  
Sent By gjohnson Date 2019-07-26 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2019-07-23 Time 13:38 Sent To  
Notes
2019-07-24 13:38:35RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-19 Cont ID  
Sent By jleahy Date 2019-07-19 Time 13:36 Rev Time 0.00
Received By jleahy Date 2019-07-01 Time 13:18 Sent To  
Notes
2019-07-02 13:18:11B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-24 Cont ID  
Sent By jleahy Date 2019-06-24 Time 11:15 Rev Time 0.00
Received By jleahy Date 2019-06-04 Time 15:58 Sent To  
Notes
2019-06-05 15:58:52B06

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-08-03 Cont ID  
Sent By abelisle Date 2019-08-03 Time 08:57 Rev Time 0.00
Received By abelisle Date 2019-08-03 Time 08:57 Sent To I
Notes
2019-08-03 08:58:048/3/19 REVIEW COMPLETE SENT TO PROCESSING A.B

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-07-26 Cont ID  
Sent By gjohnson Date 2019-07-26 Time 08:40 Rev Time 0.00
Received By gjohnson Date 2019-07-26 Time 08:40 Sent To  
Notes
2019-07-26 08:45:053RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE TWO COMPLETE PLAN SETS ONLY ONE WAS
 SUBMITTED THIS IS THE SECOND REQUEST. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By gjohnson Date 2019-07-17 Time 11:07 Rev Time 0.00
Received By gjohnson Date 2019-07-17 Time 10:41 Sent To  
Notes
2019-07-17 11:14:452ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
  
 1) PROVIDE 2 COPIES WITH NARRATIVE OF THE SCOPE OF WORK
 BEING DONE. YOU PLAN IS TOO BASIC AND THE FIELD
 INSPECTOR'S MAY NOT BE CLEAR ON THE SCOPE OF WORK. TO
 BE CLEAR THE ONLY WORK IS THE GUEST BATH TUB TO SHOWER,
 NEW MASTER TUB, AND KITCHEN ISLAND. NO OTHER FIXTURES
 OR TILE IS BEING REPLACED? FBC 107.3.5
 THERE WAS ONLY 1 SET OF OF PLANS WITH THE SCOPE OF WORK
 PLEASE SUBMIT SECOND COPY. PER WPB AMEND TO FBC 107.1
  
 2) PROVIDE SHOWER PAN DETAIL TO INCLUDE THE TOTAL
 OFFSET OF THE DRAIN, PAN MATERIAL BEING USED,
 PRE-PITCHING OF FLOOR @ 2%MIN, AND A COMPLETE FIRE
 STOPPING DETAIL. FBC 107.3.5
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 14:40 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 14:25 Sent To  
Notes
2019-06-18 14:41:07PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) PROVIDE 2 COPIES WITH NARRATIVE OF THE SCOPE OF WORK
 BEING DONE. YOU PLAN IS TOO BASIC AND THE FIELD
 INSPECTOR'S MAY NOT BE CLEAR ON THE SCOPE OF WORK. TO
 BE CLEAR THE ONLY WORK IS THE GUEST BATH TUB TO SHOWER,
 NEW MASTER TUB, AND KITCHEN ISLAND. NO OTHER FIXTURES
 OR TILE IS BEING REPLACED? FBC 107.3.5
  
 2) PROVIDE SHOWER PAN DETAIL TO INCLUDE THE TOTAL
 OFFSET OF THE DRAIN, PAN MATERIAL BEING USED,
 PRE-PITCHING OF FLOOR @ 2%MIN, AND A COMPLETE FIRE
 STOPPING DETAIL. FBC 107.3.5
  
 3) PROVIDE INSTALLATION MANUAL FOR THE NEW MASTER
 BATHROOM TUB. FBC 107.2.1
  
 4) SUB PLUMBING PERMIT WILL BE REQUIRED. FBC 105.1 BY
 LICENSED PLUMBING CONTRACTOR. FS 489
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]