| Plan Review Stops For Permit 19060088 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-01 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-01 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2019-08-01 14:29:10 | ACTION: BUILDING PROVISO | | | | | | 1) THE BASE REQUIRED FOR TILE WALLS IN SHOWERS SHALL | | | COMPLY WITH THE 2017 FBC-B SECTION: | | | | | | 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL | | | TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING | | | PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN | | | TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURE'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM | | | BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER | | | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE | | | WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S | | | RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED | | | UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING | | | AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM | | | C840. | | | | | | TABLE 2509.2 / BACKERBOARD MATERIALS | | | | | | MATERIAL----------------------------------------------- | | | ------------ STANDARD | | | | | | GLASS MAT GYPSUM BACKING PANEL | | | ---------------------------ASTM C1178 | | | | | | NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM | | | C1288 OR ISO 8336, | | | CATEGORY C | | | | | | NONASBESTOS FIBER-MAT REINFORCED | | | ------------------------ASTM 1325 | | | CEMENTITIOUS BACKER UNIT | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-19 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-19 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2019-07-19 06:49:36 | ACTION: BUILDING PROVISO | | | | | | 1) THE BASE REQUIRED FOR TILE WALLS IN SHOWERS SHALL | | | COMPLY WITH THE 2017 FBC-B SECTION: | | | | | | 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL | | | TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING | | | PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN | | | TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURE'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM | | | BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER | | | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE | | | WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S | | | RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED | | | UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING | | | AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM | | | C840. | | | | | | TABLE 2509.2 / BACKERBOARD MATERIALS | | | | | | MATERIAL----------------------------------------------- | | | ------------ STANDARD | | | | | | GLASS MAT GYPSUM BACKING PANEL | | | ---------------------------ASTM C1178 | | | | | | NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM | | | C1288 OR ISO 8336, | | | CATEGORY C | | | | | | NONASBESTOS FIBER-MAT REINFORCED | | | ------------------------ASTM 1325 | | | CEMENTITIOUS BACKER UNIT | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-06-17 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-06-17 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2019-06-17 12:46:56 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19060088 | | | ADD: 2450 PRESIDENTIAL WAY SUITE: 1906 | | | CONT: A. C. E. & M CONSTRUCTION GROUP | | | TEL: 561-716-3563 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. JUNE 17/2019 | | | ACTION: BUILDING PROVISO | | | | | | 1) THE BASE REQUIRED FOR TILE WALLS IN SHOWERS SHALL | | | COMPLY WITH THE 2017 FBC-B SECTION: | | | | | | 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL | | | TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING | | | PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN | | | TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURE'S RECOMMENDATIONS. WATER-RESISTANT GYPSUM | | | BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER | | | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE | | | WITH GA-216 OR ASTM C840 AND THE MANUFACTURER'S | | | RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED | | | UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING | | | AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM | | | C840. | | | | | | TABLE 2509.2 / BACKERBOARD MATERIALS | | | | | | MATERIAL----------------------------------------------- | | | ------------ STANDARD | | | | | | GLASS MAT GYPSUM BACKING PANEL | | | ---------------------------ASTM C1178 | | | | | | NONASBESTOS FIBER-CEMENT BACKER BOARD---------ASTM | | | C1288 OR ISO 8336, | | | CATEGORY C | | | | | | NONASBESTOS FIBER-MAT REINFORCED | | | ------------------------ASTM 1325 | | | CEMENTITIOUS BACKER UNIT | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-07-31 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-31 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-31 |
Time |
09:06 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-07-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-25 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-25 |
Time |
12:39 |
Sent To |
P |
|
| Notes |
| 2019-07-25 12:40:08 | ONLY ONE SET SUBMITTED JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-19 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-19 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2019-07-19 12:46:18 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ONLY ONE SET OF PLANS TO REVIEW | | | | | | NO ELECTRIC SHOWN FOR TUB |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-06-24 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-06-24 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2019-06-24 11:15:38 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SHOW ELECTRICAL WORK INVOLVED ON PLAN. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-07-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-07-08 |
Time |
14:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-06-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-07 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2019-06-07 14:18:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE INFORMATION SUBMITTED ON THE PLAN SHEETS IS | | | INSUFFICIENT TO REVIEW FOR FIRE CODE COMPLIANCE | | | PURPOSES. | | | | | | | | | 1) THERE IS NO SCOPE OF WORK SUBMITTED FOR THIS | | | PROJECT. | | | | | | PER NFPA 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND | | | SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE | | | CODES AND | | | STANDARDS. | | | | | | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, | | | MODIFICATION, OR REHABILITATION, | | | CONSTRUCTION DOCUMENTS AND SHOP DRAWINGS SHALL BE | | | SUBMITTED, REVIEWED, AND A | | | PPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN | | | SECTION 1.14. | | | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK INCLUDING WHAT | | | IS TO BE DEMOED AND NEW. | | | | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF ANY FIRE ALARM OR FIRE | | | SPRINKLER PROTECTION INDICATED OR AFFECTED. | | | | | | 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE | | | THAT THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE | | | PROTECTION REQUIREMENTS. | | | (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE | | | WITH THE APPLICABLE CODES AND STANDARDS. | | | (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF | | | CONSTRUCTION DOCUMENTS ON SITE. | | | | | | | | | PLEASE PROVIDE DETAILS OF ANY EXISTING SYSTEMS AND AN | | | APPLICABLE NOTE THAT ANY WORK ON THE FA OR FS SYSTEMS | | | SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-08-04 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-08-04 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-07-26 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2019-08-01 14:31:56 | TO TL DESK | | | | | 2019-07-30 14:09:15 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-07-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-26 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-23 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2019-07-24 13:38:35 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-19 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-01 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-06-24 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-06-04 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-08-03 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2019-08-03 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2019-08-03 |
Time |
08:57 |
Sent To |
I |
|
| Notes |
| 2019-08-03 08:58:04 | 8/3/19 REVIEW COMPLETE SENT TO PROCESSING A.B |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-07-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-26 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-26 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2019-07-26 08:45:05 | 3RD REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE TWO COMPLETE PLAN SETS ONLY ONE WAS | | | SUBMITTED THIS IS THE SECOND REQUEST. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-17 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-17 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2019-07-17 11:14:45 | 2ND REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | | | | | | 1) PROVIDE 2 COPIES WITH NARRATIVE OF THE SCOPE OF WORK | | | BEING DONE. YOU PLAN IS TOO BASIC AND THE FIELD | | | INSPECTOR'S MAY NOT BE CLEAR ON THE SCOPE OF WORK. TO | | | BE CLEAR THE ONLY WORK IS THE GUEST BATH TUB TO SHOWER, | | | NEW MASTER TUB, AND KITCHEN ISLAND. NO OTHER FIXTURES | | | OR TILE IS BEING REPLACED? FBC 107.3.5 | | | THERE WAS ONLY 1 SET OF OF PLANS WITH THE SCOPE OF WORK | | | PLEASE SUBMIT SECOND COPY. PER WPB AMEND TO FBC 107.1 | | | | | | 2) PROVIDE SHOWER PAN DETAIL TO INCLUDE THE TOTAL | | | OFFSET OF THE DRAIN, PAN MATERIAL BEING USED, | | | PRE-PITCHING OF FLOOR @ 2%MIN, AND A COMPLETE FIRE | | | STOPPING DETAIL. FBC 107.3.5 | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-06-18 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-06-18 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-06-18 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2019-06-18 14:41:07 | PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE | | | REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL | | | PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE | | | RE-REVIEW OF SUBMITTED CORRECTIONS | | | | | | 1) PROVIDE 2 COPIES WITH NARRATIVE OF THE SCOPE OF WORK | | | BEING DONE. YOU PLAN IS TOO BASIC AND THE FIELD | | | INSPECTOR'S MAY NOT BE CLEAR ON THE SCOPE OF WORK. TO | | | BE CLEAR THE ONLY WORK IS THE GUEST BATH TUB TO SHOWER, | | | NEW MASTER TUB, AND KITCHEN ISLAND. NO OTHER FIXTURES | | | OR TILE IS BEING REPLACED? FBC 107.3.5 | | | | | | 2) PROVIDE SHOWER PAN DETAIL TO INCLUDE THE TOTAL | | | OFFSET OF THE DRAIN, PAN MATERIAL BEING USED, | | | PRE-PITCHING OF FLOOR @ 2%MIN, AND A COMPLETE FIRE | | | STOPPING DETAIL. FBC 107.3.5 | | | | | | 3) PROVIDE INSTALLATION MANUAL FOR THE NEW MASTER | | | BATHROOM TUB. FBC 107.2.1 | | | | | | 4) SUB PLUMBING PERMIT WILL BE REQUIRED. FBC 105.1 BY | | | LICENSED PLUMBING CONTRACTOR. FS 489 | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|
|