Plan Review Details - Permit 19060057
Plan Review Stops For Permit 19060057
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By rmcdouga Date 2019-07-19 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2019-07-19 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By rmcdouga Date 2019-06-25 Time 19:12 Rev Time 0.00
Received By rmcdouga Date 2019-06-25 Time 16:32 Sent To  
Notes
2019-06-25 18:46:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS ARE REQUIRED TO BE APPROVED BY CITY PLACE
 RETAIL LLC. THE PLANS CAN BE STAMPED BY THEM OR A
 LETTER OF APPROVAL FROM THEM IS REQUIRED. SEE ZONING
 COMMENTS.
  
 2) SUBMIT A COPY OF THE PALM BEACH COUNTY HEALTH
 DEPARTMENT FORMS THAT ARE REQUIRED FOR CONSTRUCTION OF
 THE INTERACTIVE WATER FEATURE. FAC 64E-9.005
  
 3) THE DIGITAL SIGNATURE OF THE PROFESSIONAL ENGINEER
 CAN NOT BE SELF CERTIFIED PER THE BOARD OF FLORIDA
 ENGINEER'S.
  
 4) THE CONTRACTOR IS REQUIRED TO PROVIDE PROTECTION TO
 PEDESTRIANS DURING CONSTRUCTION IN ACCORDANCE WITH FBC
 3306.1.
  
 5) SHOP DRAWING SUBMITTALS, AS NOTED IN THE
 SPECIFICATION BOOK, ARE REQUIRED TO BE REVIEWED BY THE
 DESIGNER OF RECORD OF THE PROJECT AND MARKED WITH THEIR
 SHOP DRAWING REVIEW STAMP PRIOR TO SUBMITTAL TO THE
 BUILDING DEPARTMENT FOR REVIEW. FBC 107.3.4.1 DEFERRED
 SUBMITTALS.
  
 6) IN ORDER TO EXPEDITE PLAN REVIEW IT IS HELPFUL TO
 SUBMIT A RESPONSE LETTER STATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By jpearson Date 2019-07-19 Time 15:24 Rev Time 0.00
Received By jpearson Date 2019-07-19 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By jpearson Date 2019-06-25 Time 07:41 Rev Time 0.00
Received By jpearson Date 2019-06-25 Time 07:41 Sent To  
Notes
2019-06-25 07:41:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS STATE THEY ARE NOT FOR CONSTRUCTION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT INCLUDING AMPERAGE RATING, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GROUNDING DETAIL. NEC 215.5, 230, 250, 408.30
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 5. PROVIDE ENCLOSURES THAT ARE RATED FOR CORROSIVE
 ENVIRONMENTS FOR ELECTRICAL EQUIPMENT IN MECHANICAL
 ROOM. NEC 110.28
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-29 Cont ID  
Sent By hmoser Date 2019-07-29 Time 13:56 Rev Time 0.00
Received By hmoser Date 2019-07-19 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-05 Cont ID  
Sent By cpuell Date 2019-07-05 Time 16:23 Rev Time 0.00
Received By cpuell Date 2019-06-10 Time 08:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-29 Cont ID  
Sent By hmoser Date 2019-07-29 Time 13:56 Rev Time 0.00
Received By hmoser Date 2019-07-29 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By ccole Date 2019-07-03 Time 16:09 Rev Time 0.00
Received By ccole Date 2019-07-03 Time 16:09 Sent To  
Notes
2019-07-03 16:46:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060057
 7/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET XM100: VENTILATION REQUIREMENTS FOR THE
 CHEMICAL ROOM AND FILTRATION FEATURE ROOM ARE LISTED
 UNDER UTILITY DATA, HOWEVER NO SYSTEMS OR DETAILS ARE
 PROVIDED ON THE PLANS- SEE SECTION 107.2.1 WPB AND
 PROVIDE DRAWINGS AND SPECIFICATIONS.
  
 2) REFER TO SECTION 414.1.3 FBC B- INFORMATION
 REQUIRED:
 "A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY."
 PLEASE PROVIDE THE REQUIRED INFORMATION ON THE PLAN IN
 THE FORM OF A SCHEDULE LISTING EACH MATERIAL, THE
 QUANTITY OF THE MATERIAL, AND WHERE THE MATERIAL IS TO
 BE USED OR STORED. SUBMIT MSDS SHEETS FOR ALL
 MATERIALS.
  
 3) PLEASE NOTE THAT ROOMS AND SPACES ENCLOSING
 HAZARDOUS MATERIALS SHALL BE IDENTIFIED AS CONTROL
 AREAS AND ARE REQUIRED TO BE SEPARATED FROM OTHER ROOMS
 OR CONTROL AREAS BY FIRE BARRIERS AND HORIZONTAL
 ASSEMBLIES- SEE SECTIONS 414.2.1 & 414.2.2 FBC B AND
 REVISE THE PLANS ACCORDINGLY.
  
 4) HAZARDOUS EXHAUST SYSTEMS SHALL COMPLY WITH SECTIONS
 510.2- 510.10 FBC M. THE CURRENT PLANS DO NOT PROVIDE
 ANY EXHAUST VENTILATION DETAILS. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-24 Cont ID  
Sent By lcrespo Date 2019-07-24 Time 13:53 Rev Time 0.00
Received By lcrespo Date 2019-07-22 Time 13:41 Sent To  
Notes
2019-07-24 13:54:1707/24/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By tklarge Date 2019-07-05 Time 13:58 Rev Time 0.00
Received By tklarge Date 2019-07-03 Time 12:31 Sent To  
Notes
2019-07-03 11:19:53INTERACTIVE WATER FEATURE REVIEW
  
 1) THE SPECIFIC ADDRESS OF THE WATER FEATURE SHALL BE
 PLACED ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUCTION
 DRAIN COVERS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. XF 102 REFERS TO A CIVIL SHEET FOR THE LOCATION
 OF THE WASTE LINE. THERE IS NO CIVIL DRAWING IN THIS
 SUBMITTAL. CLARIFY. SUBMIT A CIVIL DRAWING SHOWING THE
 TERMINATION LOCATION OF THE WASTE LINE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) THE PLANS ARE REQUIRED TO BE APPROVED BY CITY PLACE
 RETAIL LLC. THE PLANS CAN BE STAMPED BY THEM OR A
 LETTER OF APPROVAL FROM THEM IS REQUIRED. SEE ZONING
 COMMENTS.
 SUBMIT A COPY OF THE PALM BEACH COUNTY HEALTH
 DEPARTMENT FORM DH 4159 THAT IS REQUIRED FOR
 CONSTRUCTION OF THE INTERACTIVE WATER FEATURE. FL.
 STATUTE 514.025.
 5) THE DIGITAL SIGNATURE OF THE PROFESSIONAL ENGINEER
 CAN NOT BE SELF CERTIFIED PER THE BOARD OF FLORIDA
 ENGINEER'S.
 6) SHOP DRAWING SUBMITTALS, AS NOTED IN THE
 SPECIFICATION BOOK, ARE REQUIRED TO BE REVIEWED BY THE
 DESIGNER OF RECORD OF THE PROJECT AND MARKED WITH THEIR
 SHOP DRAWING REVIEW STAMP PRIOR TO SUBMITTAL TO THE
 BUILDING DEPARTMENT FOR REVIEW. FBC 107.3.4.1 DEFERRED
 SUBMITTALS.
 7) THE DISCHARGE LOCATION/TERMINATION OF THE WASTE LINE
 SHALL RECEIVE APPROVAL FROM THE CITY OF WEST PALM BEACH
 ENGINEERING DEPT. CONTACT MANNY GONZALEZ AT
 561-494-1085.
 8) THE MINIMUM SIZE OF THE COLLECTOR TANK SHALL BE
 EQUAL TO THE VOLUME OF 3 MINUTES OF THE COMBINED FLOW
 OF ALL FEATURE PUMPS AND THE FILTER PUMP PER 2017
 FBC-BUILDING SEC. 454.1.9.8. SUBMIT VERIFICATION OF
 COMPLIANT DESIGN CAPACITY OF THE COLLECTOR TANK.
 9) THE FLOW RATE THROUGH THE FEATURE NOZZLES OF THE
 WATER FEATURES SHALL BE SUCH AS NOT TO HARM THE PATRONS
 AND SHALL NOT EXCEED 20 FEET PER SECOND UNLESS
 JUSTIFIED BY THE DESIGN ENGINEER AND BY THE FOUNTAIN
 MANUFACTURER PERR 2017 FBC SEC. 454.1.9.8.6.4. SUBMIT
 VERIFICATION.
 10) ADEQUATE ACCESS SHALL BE PROVIDED TO THE COLLECTOR
 TANK. 2017 FBC SEC. 454.1.9.8.
 11) A MEANS OF VACUUMING AND COMPLETELY DRAINING THE
 COLLECTOR TANK SHALL BE PROVIDED PER 2017 FBC
 SEC.454.1.9.8.6.7.
 12) SHT.XM 140 - KEYNOTE 10.404 IS SHOWN IN THE SUCTION
 LINE FROM THE RESERVOIR TO THE FILTER TANKS BUT IS NOT
 LISTED IN THE KEYNOTE SCHEDULE. CLARIFY & IDENTIFY THE
 PART. WPB AMEND. TO FBC. SEC. 107.2.1.
 13) SHT. XM 140 - CLARIFY THE LETTERS W/AR ON THE
 OVERFLOW LINE & P/AR ON THE POTABLE WATER LINE. PB
 AMEND. TO FBC SEC. 107.2.1.
 14) SHT. XD 100 - PROVIDE THE SCHEDULE KEYNOTE FOR ITEM
 13.054 ON DETAIL 6.
 15) SUBMIT MSDS DOCUMENTS FOR THE CHEMICALS TO BE USED/
 STORED ON SITE AND THE QUANTITIES OF EACH.WPB AMEND. TO
 FBC SEC. 107.2.1.
 16) SUBMIT MANUF. SPECIFICATIONS ON THE DRENCH SHOWER.
 17) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DECK
 SHOWER. THE DECK SHOW SHALL COMPLY WITH THE 2017
 FBC-ACCESSIBILITY SECS.305 (CLEAR FLOOR SPACE), 402.1
 (ACCESSIBLE ROUTE), 308 (REACH RANGES) & 309 (OPERABLE
 PARTS).
 18) SHT. XD 101 - DETAIL #1 - SHOW THE LOCATION OF THE
 STORAGE PIT ON THE DRAWINGS. WPB AMEND. TO FBC SEC.
 107.2.1.
 19) ALL PIPING SHALL BE TESTED AT 35 PSI.
 20) SUBMIT SPECIFICATIONS AND SHOW THE LOCATION OF THE
 DRENCH SHOWER AS REFERENCED IN THE JOB SPECIFICATIONS.
 21)THE MAXIMUM ALLOWABLE QUANTITIES OF THE CHLORINE AND
 MURIATIC ACID SHALL COMPLY WITH 2017 FBC SEC.307.1 AND
 TABLES 307.1 (1) AND 307.1 (2).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By rmcdouga Date 2019-07-19 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2019-07-19 Time 14:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By rmcdouga Date 2019-06-25 Time 19:13 Rev Time 0.00
Received By rmcdouga Date 2019-06-25 Time 19:13 Sent To  
Notes
2019-07-05 14:10:29SIGNATURE COULD NOT BE VERIFIED ON ANY SHEETS. T.LARGE.
2019-06-25 07:31:36FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE
 FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED
 AND SEALED" AS PER FAC 61G15-23.004. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By eschneid Date 2019-07-23 Time 10:53 Rev Time 0.25
Received By eschneid Date 2019-07-23 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By eschneid Date 2019-06-25 Time 16:40 Rev Time 0.50
Received By eschneid Date 2019-06-25 Time 16:40 Sent To  
Notes
2019-06-25 16:42:49FAILED
  
 CITYPLACE RETAIL LLC APPROVAL IS REQUIRED IN ONE OF TWO
 WAYS:
  
 1) STAMPED ON PLANS
 2) SEPARATE APPROVAL LETTER
  
 PLANS COMPLY WITH ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]