| Plan Review Stops For Permit 19060025 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-12-10 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-12-10 |
Time |
09:13 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-06-26 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-06-26 |
Time |
18:08 |
Sent To |
FIRE |
|
| Notes |
| 2019-06-26 18:15:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF A SITE PLAN THAT CLEARLY SHOWS | | | THE LOCATION OF THE GENERATOR IN RELATION TO BUILDINGS | | | AND PROPERTY LINES. FBC 107.2.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2020-04-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-04-17 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-04-17 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2020-04-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-04-14 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-04-14 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2020-04-14 16:46:21 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE OF $45,000 NOT A INDUSTRY STANDARD VALUE | | | MARSHAL SWIFTS HAS A STANDARD VALUE OF $76,000 FOR | | | GENERATOR AND INSTALL PLUS $15,000 FOR THE TRANSFER | | | SWITCH. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-24 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-24 |
Time |
14:16 |
Sent To |
P |
|
| Notes |
| 2020-03-24 14:15:54 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEETS E-1 AND E-3 APPEAR TO BE IDENTICAL. WHY ARE | | | THERE TWO IDENTICAL SHEETS IN THE SET? PROVIDE | | | CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1 | | | 2. LOAD CALCULATION SHOWS THE LOAD ON A PHASE AND C | | | PHASE TO BE GREATER THAN 300 AMPS. THE GENERATOR IS | | | SHOWN WITH A 300 AMP BREAKER. HOW WILL THIS HANDLE THE | | | LOAD? PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC | | | 110.3, 702.4(B)(2) | | | 3. TOTAL COMPUTED LOAD FOR EACH PHASE IS NOT ACCURATE. | | | FOR PHASES A AND C, THE LOAD WOULD BE DIVIDED BY 120 | | | VOLTS. FOR B PHASE, THE LOAD WOULD BE DIVIDED BY 208 | | | VOLTS. PROVIDE ACCURATE LOAD CALCULATION. NEC 220; WPB | | | FBC 107.2.1 | | | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 5. PROVIDE NOTES FOR REQUIRED MARKING OF HIGH LEG. NEC | | | 110.15, 230.56, 408.3(E) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2020-01-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-01-27 |
Time |
05:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-23 |
Time |
15:33 |
Sent To |
G |
|
| Notes |
| 2020-01-23 15:34:07 | SAME COMMENT FROM THE LAST REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-10 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-10 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2019-12-10 10:31:43 | VALUE OF GENERATOR AND TRANSFER SWITCH TO BE INCLUDED | | | WITH VALUE OF PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-06-06 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-06-06 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2019-06-06 15:49:25 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE FOR THE GENERATOR , TRANSFER SWITCH, AND WIRE | | | SHALL BE INCLUDED IN THE VALUE FOR THE WORK TO BE DONE. | | | NOTE!!!!!! PERMIT 17080950 WAS FOR LIGHTING ONLY. | | | | | | GENERATORS ARE ALWAYS A SEPARATE PERMIT AND VALUE. | | | | | | YOU WILL ALSO HAVE TO REVISE THE DRAWINGS FOR THE | | | MASTER PERMIT TO REFLECT RISER THE WAY IT IS SHOWN ON | | | THESE PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2020-04-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-04-13 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-11-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-11-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-11-22 |
Time |
14:03 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-27 |
Time |
13:15 |
Sent To |
I |
|
| Notes |
| 2019-06-27 13:27:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) IT APPEARS THAT THE FUEL SUPPY IS NATURAL GAS. | | | | | | THERE ARE NO NATURAL GAS LINS INDICATED. A SEPARATE | | | PERMIT IS REQUIRED FOR THE NATURAL GAS LINES INCULDING | | | EQUIPEMT SPECIFICATIONS. | | | | | | PLEASE SHOW THE PROPOSED NATURAL GAS LINES ON THE SITE | | | PLAN AND PROVIDE A NOTE STATING UNDER SEPARATE PERMIT. | | | | | | | | | | | | 2) THERE IS SITE PLAN SHOWING THE SPECIFIC LOCATION OF | | | THE GENERATOR INCLUDING ALL DIMENSIONS TO AREA | | | BUILDINGS, INCLUDING NEIGHBORING PROPERTIES, AND WINDOW | | | AND DOOR AND OTHER OPENINGS. | | | | | | PER NFPA 110 | | | | | | 7.2.2 OUTDOOR EPS INSTALLATIONS. | | | 7.2.2.1 THE EPS SHALL BE INSTALLED IN A SUITABLE | | | ENCLOSURE LOCATED | | | OUTSIDE THE BUILDING AND CAPABLE OF RESISTING THE | | | ENTRANCE | | | OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY AS REQUIRED | | | BY LOCAL BUILDING CODES. | | | | | | PLEASE PROVIDE SPECIFIC SITE PLAN DETAILS. | | | | | | | | | | | | 3) THERE IS NO INDICATION OF GENERATOR CLASSIFICATION | | | NOR TYPE PER NFPA 110 | | | | | | PER NFPA 110 | | | | | | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY | | | SYSTEMS (EPSSS) | | | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF | | | ELECTRICAL | | | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO | | | LOADS FOR | | | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND | | | WITHIN A SPECIFIED | | | TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER | | | SUPPLY | | | AS SPECIFIED IN TABLE 4.1(B). | | | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN | | | HOURS, FOR | | | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD | | | WITHOUT | | | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] | | | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN | | | SECONDS, | | | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE | | | TRANSFER | | | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE | | | 4.1(B) | | | PROVIDES THE TYPES DEFINED BY THIS STANDARD. | | | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF | | | EQUIPMENT | | | INSTALLATION, PERFORMANCE, AND MAINTENANCE. | | | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | | OF THE | | | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE | | | OR | | | SERIOUS INJURIES. | | | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | | OF THE | | | EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND | | | SAFETY. | | | 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. | | | 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT | | | ALL LOADS | | | SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER | | | THAT | | | MEETS ALL THE FOLLOWING CRITERIA: | | | (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE | | | LOAD | | | (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED | | | IN TABLE | | | 4.1(A) | | | (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED | | | IN TABLE | | | 4.1(B) | | | | | | PLEASE PROVIDE DETAILS AS THIS IS HOW IT WILL INSPECTED | | | AND THE ACCEPTANCE TESTING. | | | | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-04-15 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-04-15 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2020-04-15 10:12:54 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS WITH TWO | | | DIFFERENT PIPE SIZES SHOWN. SUBMIT ONE GAS DRAWING FOR | | | REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2020-03-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-03-26 |
Time |
06:22 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-03-26 |
Time |
05:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-01-27 |
Time |
05:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-01-27 |
Time |
05:34 |
Sent To |
|
|
| Notes |
| 2020-01-27 05:54:40 | 1) 3RD REQUEST - THE PLANS INDICATE AN EXISTING GAS | | | METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR | | | THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM | | | MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO | | | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF | | | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3. | | | NOTE:I PUT A COPY OF THE ORIGINAL GAS PLAN IN THE | | | PERMIT APPLICATION PACKAGE AFTER THE LAST REVIEW TO BE | | | GIVEN TO THE CONTRACTOR TO USE AS A REFERENCE FOR THE | | | EXISTING GAS LOAD. PLEASE USE THIS DRAWING TO COMPLY | | | WITH THE PLAN REVIEW COMMENTS. | | | 2)THE ORIGINAL GAS PLAN ON FILE IN CITY RECORDS SHOW A | | | DEVELOPED LENGTH OF 158 FEET BUT THE SUBMITTED PLAN | | | SHOWS A DEVELOPED LENGTH OF 20 FEET. CLARIFY. THE 158 | | | SHALL BE USED TO SIZE THIS SYSTEM. 2017 FBC-FUEL GAS | | | SEC. 402.4. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-12-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-12-11 |
Time |
05:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-12-11 |
Time |
04:59 |
Sent To |
|
|
| Notes |
| 2019-12-11 05:25:42 | 1) INDICATE ON THE PLAN THE TYPE OF PIPING TO BE USED | | | ABOVEGROUND AND SHOW THE REQUIRED LISTED GAS SHUTOFF | | | VALVE FOR THE GENERATOR.. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) A UNION IS REWUIRED WITHIN ONE FOOT UPSTREAM OR | | | DOWNSTREAM OF THE REGULATOR. 2017 FBC-FUEL GAS SEC. | | | 410.2 (7) . | | | 3) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | | OF THE REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. | | | 4) - -2ND REQUEST - THE PLANS INDICATE AN EXISTING GAS | | | METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR | | | THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM | | | MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO | | | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF | | | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | | 402.2, 402.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-06-06 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-06-06 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-06-06 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2019-06-06 14:36:15 | GAS 1ST REVIEW**DENIED** | | | | | | 1) VALUE IS TOO LOW. COST MUST INCLUDED GENERATOR EVERN | | | WHEN FURNISHED BY OWNER. PERMIT # 17080950 CALLED OUT | | | FOR A FURTURE 50KW THIS UNIT IS 100KW. PROVIDE BONA | | | FIDE SIGN CONTRACT TO INCLUDE THE COST OF THE GENERATOR | | | AND GAS PIPING THAT WILL NEED TO BE DONE TO FUEL THE | | | UNIT. WPB AMEND 109.3 | | | | | | 2) PROVIDE A COMPLETE GAS PLAN. CITY RECORDS DO NOT | | | SHOW ANY GAS SYSTEM ON SITE. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2020-04-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-17 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-09 |
Time |
12:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-03-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-03-26 |
Time |
06:22 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-03-18 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2020-03-18 15:33:30 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-01-27 |
Time |
05:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-01-17 |
Time |
14:34 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-12-11 |
Time |
05:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-11-18 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2019-11-19 14:34:56 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-06-27 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-06-03 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2019-06-04 15:09:10 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-04-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-10 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-10 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2020-04-10 12:28:20 | PAPER ORIGINALS SUBMITTED | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-04-13 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-04-13 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-13 16:59:59 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 04/13/2020 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PROVIDE A SURVEY OF THE SUBJECT SITE. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1442 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-06-05 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-06-05 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|