Plan Review Details - Permit 19060025
Plan Review Stops For Permit 19060025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By rmcdouga Date 2019-12-10 Time 09:13 Rev Time 0.00
Received By rmcdouga Date 2019-12-10 Time 09:13 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-26 Cont ID  
Sent By rmcdouga Date 2019-06-26 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2019-06-26 Time 18:08 Sent To FIRE
Notes
2019-06-26 18:15:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A SITE PLAN THAT CLEARLY SHOWS
 THE LOCATION OF THE GENERATOR IN RELATION TO BUILDINGS
 AND PROPERTY LINES. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2020-04-17 Cont ID  
Sent By jleahy Date 2020-04-17 Time 15:56 Rev Time 0.00
Received By jleahy Date 2020-04-17 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2020-04-14 Cont ID  
Sent By jleahy Date 2020-04-14 Time 16:23 Rev Time 0.00
Received By jleahy Date 2020-04-14 Time 16:23 Sent To  
Notes
2020-04-14 16:46:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF $45,000 NOT A INDUSTRY STANDARD VALUE
 MARSHAL SWIFTS HAS A STANDARD VALUE OF $76,000 FOR
 GENERATOR AND INSTALL PLUS $15,000 FOR THE TRANSFER
 SWITCH.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 14:16 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 14:16 Sent To P
Notes
2020-03-24 14:15:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEETS E-1 AND E-3 APPEAR TO BE IDENTICAL. WHY ARE
 THERE TWO IDENTICAL SHEETS IN THE SET? PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1
 2. LOAD CALCULATION SHOWS THE LOAD ON A PHASE AND C
 PHASE TO BE GREATER THAN 300 AMPS. THE GENERATOR IS
 SHOWN WITH A 300 AMP BREAKER. HOW WILL THIS HANDLE THE
 LOAD? PROVIDE CLARIFICATION AND/OR CORRECTIONS. NEC
 110.3, 702.4(B)(2)
 3. TOTAL COMPUTED LOAD FOR EACH PHASE IS NOT ACCURATE.
 FOR PHASES A AND C, THE LOAD WOULD BE DIVIDED BY 120
 VOLTS. FOR B PHASE, THE LOAD WOULD BE DIVIDED BY 208
 VOLTS. PROVIDE ACCURATE LOAD CALCULATION. NEC 220; WPB
 FBC 107.2.1
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE NOTES FOR REQUIRED MARKING OF HIGH LEG. NEC
 110.15, 230.56, 408.3(E)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-01-23 Cont ID  
Sent By tklarge Date 2020-01-27 Time 05:56 Rev Time 0.00
Received By jleahy Date 2020-01-23 Time 15:33 Sent To G
Notes
2020-01-23 15:34:07SAME COMMENT FROM THE LAST REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By jleahy Date 2019-12-10 Time 10:30 Rev Time 0.00
Received By jleahy Date 2019-12-10 Time 10:30 Sent To  
Notes
2019-12-10 10:31:43VALUE OF GENERATOR AND TRANSFER SWITCH TO BE INCLUDED
 WITH VALUE OF PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By jleahy Date 2019-06-06 Time 15:41 Rev Time 0.00
Received By jleahy Date 2019-06-06 Time 15:41 Sent To  
Notes
2019-06-06 15:49:25FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR THE GENERATOR , TRANSFER SWITCH, AND WIRE
 SHALL BE INCLUDED IN THE VALUE FOR THE WORK TO BE DONE.
 NOTE!!!!!! PERMIT 17080950 WAS FOR LIGHTING ONLY.
  
 GENERATORS ARE ALWAYS A SEPARATE PERMIT AND VALUE.
  
 YOU WILL ALSO HAVE TO REVISE THE DRAWINGS FOR THE
 MASTER PERMIT TO REFLECT RISER THE WAY IT IS SHOWN ON
 THESE PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-04-13 Cont ID  
Sent By pleduc Date 2020-04-13 Time   Rev Time 0.00
Received By pleduc Date 2020-04-13 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-22 Cont ID  
Sent By pleduc Date 2019-11-22 Time   Rev Time 0.00
Received By pleduc Date 2019-11-22 Time 14:03 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-27 Cont ID  
Sent By pleduc Date 2019-06-27 Time   Rev Time 0.00
Received By pleduc Date 2019-06-27 Time 13:15 Sent To I
Notes
2019-06-27 13:27:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT APPEARS THAT THE FUEL SUPPY IS NATURAL GAS.
  
 THERE ARE NO NATURAL GAS LINS INDICATED. A SEPARATE
 PERMIT IS REQUIRED FOR THE NATURAL GAS LINES INCULDING
 EQUIPEMT SPECIFICATIONS.
  
 PLEASE SHOW THE PROPOSED NATURAL GAS LINES ON THE SITE
 PLAN AND PROVIDE A NOTE STATING UNDER SEPARATE PERMIT.
  
  
  
 2) THERE IS SITE PLAN SHOWING THE SPECIFIC LOCATION OF
 THE GENERATOR INCLUDING ALL DIMENSIONS TO AREA
 BUILDINGS, INCLUDING NEIGHBORING PROPERTIES, AND WINDOW
 AND DOOR AND OTHER OPENINGS.
  
 PER NFPA 110
  
 7.2.2 OUTDOOR EPS INSTALLATIONS.
 7.2.2.1 THE EPS SHALL BE INSTALLED IN A SUITABLE
 ENCLOSURE LOCATED
 OUTSIDE THE BUILDING AND CAPABLE OF RESISTING THE
 ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY AS REQUIRED
 BY LOCAL BUILDING CODES.
  
 PLEASE PROVIDE SPECIFIC SITE PLAN DETAILS.
  
  
  
 3) THERE IS NO INDICATION OF GENERATOR CLASSIFICATION
 NOR TYPE PER NFPA 110
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECIFIED
 TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER
 SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
 PLEASE PROVIDE DETAILS AS THIS IS HOW IT WILL INSPECTED
 AND THE ACCEPTANCE TESTING.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2020-04-15 Cont ID  
Sent By tklarge Date 2020-04-15 Time 10:11 Rev Time 0.00
Received By tklarge Date 2020-04-15 Time 09:36 Sent To  
Notes
2020-04-15 10:12:541) THERE ARE TWO DIFFERENT GAS DRAWINGS WITH TWO
 DIFFERENT PIPE SIZES SHOWN. SUBMIT ONE GAS DRAWING FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-03-26 Cont ID  
Sent By tklarge Date 2020-03-26 Time 06:22 Rev Time 0.00
Received By tklarge Date 2020-03-26 Time 05:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-01-27 Cont ID  
Sent By tklarge Date 2020-01-27 Time 05:56 Rev Time 0.00
Received By tklarge Date 2020-01-27 Time 05:34 Sent To  
Notes
2020-01-27 05:54:401) 3RD REQUEST - THE PLANS INDICATE AN EXISTING GAS
 METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR
 THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3.
 NOTE:I PUT A COPY OF THE ORIGINAL GAS PLAN IN THE
 PERMIT APPLICATION PACKAGE AFTER THE LAST REVIEW TO BE
 GIVEN TO THE CONTRACTOR TO USE AS A REFERENCE FOR THE
 EXISTING GAS LOAD. PLEASE USE THIS DRAWING TO COMPLY
 WITH THE PLAN REVIEW COMMENTS.
 2)THE ORIGINAL GAS PLAN ON FILE IN CITY RECORDS SHOW A
 DEVELOPED LENGTH OF 158 FEET BUT THE SUBMITTED PLAN
 SHOWS A DEVELOPED LENGTH OF 20 FEET. CLARIFY. THE 158
 SHALL BE USED TO SIZE THIS SYSTEM. 2017 FBC-FUEL GAS
 SEC. 402.4.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-12-11 Cont ID  
Sent By tklarge Date 2019-12-11 Time 05:33 Rev Time 0.00
Received By tklarge Date 2019-12-11 Time 04:59 Sent To  
Notes
2019-12-11 05:25:421) INDICATE ON THE PLAN THE TYPE OF PIPING TO BE USED
 ABOVEGROUND AND SHOW THE REQUIRED LISTED GAS SHUTOFF
 VALVE FOR THE GENERATOR.. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) A UNION IS REWUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF THE REGULATOR. 2017 FBC-FUEL GAS SEC.
 410.2 (7) .
 3) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 4) - -2ND REQUEST - THE PLANS INDICATE AN EXISTING GAS
 METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR
 THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By thunt Date 2019-06-06 Time 14:32 Rev Time 0.00
Received By thunt Date 2019-06-06 Time 14:32 Sent To  
Notes
2019-06-06 14:36:15GAS 1ST REVIEW**DENIED**
  
 1) VALUE IS TOO LOW. COST MUST INCLUDED GENERATOR EVERN
 WHEN FURNISHED BY OWNER. PERMIT # 17080950 CALLED OUT
 FOR A FURTURE 50KW THIS UNIT IS 100KW. PROVIDE BONA
 FIDE SIGN CONTRACT TO INCLUDE THE COST OF THE GENERATOR
 AND GAS PIPING THAT WILL NEED TO BE DONE TO FUEL THE
 UNIT. WPB AMEND 109.3
  
 2) PROVIDE A COMPLETE GAS PLAN. CITY RECORDS DO NOT
 SHOW ANY GAS SYSTEM ON SITE. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-04-17 Cont ID  
Sent By shill Date 2020-04-17 Time 08:40 Rev Time 0.00
Received By shill Date 2020-04-09 Time 12:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-26 Cont ID  
Sent By tklarge Date 2020-03-26 Time 06:22 Rev Time 0.00
Received By tklarge Date 2020-03-18 Time 15:33 Sent To  
Notes
2020-03-18 15:33:30RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-27 Cont ID  
Sent By tklarge Date 2020-01-27 Time 05:56 Rev Time 0.00
Received By tklarge Date 2020-01-17 Time 14:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-11 Cont ID  
Sent By tklarge Date 2019-12-11 Time 05:33 Rev Time 0.00
Received By tklarge Date 2019-11-18 Time 14:34 Sent To  
Notes
2019-11-19 14:34:56RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-27 Cont ID  
Sent By cpuell Date 2019-06-27 Time 13:57 Rev Time 0.00
Received By cpuell Date 2019-06-03 Time 15:08 Sent To  
Notes
2019-06-04 15:09:10ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-10 Cont ID  
Sent By shill Date 2020-04-10 Time 12:28 Rev Time 0.00
Received By shill Date 2020-04-10 Time 12:28 Sent To  
Notes
2020-04-10 12:28:20PAPER ORIGINALS SUBMITTED
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By rfalcone Date 2020-04-13 Time 16:59 Rev Time 0.00
Received By rfalcone Date   Time   Sent To  
Notes
2020-04-13 16:59:59ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 04/13/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A SURVEY OF THE SUBJECT SITE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-05 Cont ID  
Sent By mcruz Date 2019-06-05 Time 14:10 Rev Time 0.00
Received By mcruz Date 2019-06-05 Time 14:02 Sent To  
Notes
***NONE***