Plan Review Details - Permit 19060010
Plan Review Stops For Permit 19060010
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-05 Cont ID  
Sent By jwitmer Date 2019-08-05 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2019-08-05 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-15 Cont ID  
Sent By shill Date 2019-07-15 Time 17:03 Rev Time 0.00
Received By shill Date 2019-07-15 Time 16:55 Sent To  
Notes
2019-07-15 17:05:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2017
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. CLARIFY WHY IMPERIUM CONSTRUCTION, LLC, CRC, IS
 INCLUDED IN THE TITLE BLOCK AND ON THE RESUBMITTAL
 FORM. A CRC CANNOT HAVE A CONTRACT TO PERFORM THIS
 SCOPE OF WORK, FS489.
  
 2. THE CONTRACT INDICATES THAT ITEMS ARE PROVIDED BY
 OWNER; PROVIDE VALUE FBC 109. NO SQUARE FOOT AREAS WERE
 PROVIDED.
  
 3. THE OWNER'S SIGNATURE IS REQUIRED ON THE PERMIT
 APPLICATION, FBC 107, OR A COPY OF THE SIGNED CONTRACT
 IS TO BE PROVIDED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By jwitmer Date 2019-06-17 Time 10:22 Rev Time 0.00
Received By jwitmer Date 2019-06-17 Time 07:00 Sent To  
Notes
2019-06-17 10:23:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060010
 ADD: 801 S. OLIVE AVE. SUITE: 1407
 CONT:WS HOME IMPROVEMENTS LLC
 TEL: 772-888-1177
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 17/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE COPIES OF COPYRIGHTED PLANS.
 EVEN THOUGH THE CONTRACTOR HAS APPLIED THEIR NAME ON
 THE LEFT SIDE OF THE PLANS, THE RIGHT SIDE OF THE PLANS
 THE TITLE BLOCK INDICATES THEY WERE DRAWN BY O?BRIEN
 HARRIS. THE OTHER ISSUE IS THE PLANS WERE DRAWN TO A ?
 INCH SCALE AND SHRUNK TO THE CURRENT SIZE.
 W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.
  
 2) THE SUBMITTED PLANS ALSO REFER TO THE REMOVAL OF
 BATHROOM FLOORING, BUT THERE IS NO MENTION AS TO THE
 NEW TYPE OF FLOORING TO BE INSTALLED NOR SOUND
 UNDERLAYMENT TYPE OF INSTALLATION.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-31 Cont ID  
Sent By jpearson Date 2019-07-31 Time 08:45 Rev Time 0.00
Received By jpearson Date 2019-07-31 Time 08:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 09:20 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 09:20 Sent To  
Notes
2019-07-14 09:16:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN PROVIDED DOES NOT SHOW ANY ELECTRICAL WORK.
 ELECTRICAL NOTE 1 STATES THAT AN ELECTRICAL CONTRACTOR
 IS RESPONSIBLE FOR FBC COMPLIANCE, HOWEVER, THIS
 STATEMENT DOES NOT ALLEVIATE THE RESPONSIBILITY OF
 SHOWING ELECTRICAL ON THE PLAN. PROVIDE ELECTRICAL PLAN
 FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR SIGNED BY THE ELECTRICAL CONTRACTOR
 QUALIFIER. SHOW EXISTING AND PROPOSED RECEPTACLE AND
 LIGHTING OUTLETS. FS 471.003(2)(H); 471.025; WPB FBC
 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. CONTRACT PROVIDED STATES THAT ELECTRICAL IS NOT
 INCLUDED. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR
 SO THIS VALUE CAN BE ADDED TO THE TOTAL PERMIT VALUE.
 WPB FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-24 Cont ID  
Sent By jleahy Date 2019-06-24 Time 11:16 Rev Time 0.00
Received By jleahy Date 2019-06-24 Time 11:16 Sent To  
Notes
2019-06-24 11:16:51FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW ELECTRICAL WORK INVOLVED ON PLAN.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-10 Cont ID  
Sent By pleduc Date 2019-07-10 Time   Rev Time 0.00
Received By pleduc Date 2019-07-10 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-05 Cont ID  
Sent By pleduc Date 2019-06-05 Time   Rev Time 0.00
Received By pleduc Date 2019-06-05 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 13:38 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 13:38 Sent To  
Notes
2019-07-30 14:30:28B05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-15 Cont ID  
Sent By shill Date 2019-07-15 Time 17:06 Rev Time 0.00
Received By shill Date 2019-07-02 Time 13:51 Sent To  
Notes
2019-07-03 13:51:13B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-24 Cont ID  
Sent By jleahy Date 2019-06-24 Time 11:16 Rev Time 0.00
Received By jleahy Date 2019-06-03 Time 15:41 Sent To  
Notes
2019-06-04 15:41:43B04

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 13:35 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 13:34 Sent To  
Notes
2019-08-13 13:35:04PLUMBING COMMEMTS: APPROVED
 PLUMBING PROVISO
 1. PER WPB FBC 107.2.1 AND AS ALLOWED BY WPB FBC
 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL THE
 MANUFACTURER?S SPECIFICATION SHEET FOR THE KOHLER
 WALK-IN BATH, TUB VALVE AND WATER TEMPERATURE LIMITING
 DEVICE CONFORMING TO ASSE 1070 AS REQUIRED BY FBC PL
 607.1.2. IF TUB IS A WHIRLPOOL BATH, THEN THE
 PROVISIONS OF FBC PL 421 SHALL BE COMPLIED WITH.
 SPECIFICATIONS SHALL BE SUBMITTED, APPROVED AND IN
 PLACE PRIOR TO FIRST INSPECTION.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL 3. ALL WORK PER CITY CODES SUBJECT TO FIELD
 INSPECTOR?S APPROVAL
 3. WASHING MACHINE SHUT OFF VALVES SHALL BE ACCESSIBLE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-07-14 Cont ID  
Sent By abelisle Date 2019-07-14 Time 03:55 Rev Time 0.00
Received By abelisle Date 2019-07-14 Time 04:27 Sent To  
Notes
2019-07-14 04:54:427/14/2019 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1 )WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC
 R2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 2) TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE
 COST OF ALL PLUMBING . PROVIDE BONA FIDE SIGNED
 CONTRACT PER WPB AMENDMENTS TO THE FBC 109.3 BUILDING
 PERMIT VALUATIONS.
  
 3) MASTER TUB VALVE MUST PROVIDE PROVISIONS FOR
 TEMPERED WATER REQUIRED AND DETAILS OF A TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 FBC P
 607.1.2 TEMPERED WATER TEMPERATURE CONTROL.
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 14:21 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 13:42 Sent To  
Notes
2019-06-18 14:18:31PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) BUILDING WAS BUILT IN 2006 UNDER THE FAIR HOUSING
 ACT (FHA) ALL ELEMENTS OF FHA ARE TO REMAIN. YOUR
 BATHROOM CABINET DETAIL SHOW HEIGHT @ 35 3/4". MAX
 PERMITTED IS 34". PLEASE REVIEW THE FAIR HOUSING DESIGN
 MANUAL. SECTION 7.52. ADD NOTE TO PLAN THAT ALL
 INSTALLATIONS SHALL REMAIN AND COMPLY WITH FHA
  
 2) PLANS SHALL BE SIGNED AND SEAL BY DESIGN
 PROFESSIONAL.FS 471, 481. PLANS SHALL BE DIMENSIONAL
 AND HAVE SUFFICIENT CLARITY AND SHOW DETAIL. SEE
 BUILDING REVIEW COMMENTS. FBC 107.2.1
  
 3) PROVIDE KITCHEN CABINET DETAIL. NOTE MAX PERMITTED
 IS 36"
  
 4) PROVIDE SHOWER PAN DETAIL SHOWING WHAT MATERIAL IS
 BEING USED AND FLOOR WILL BE PRE-PITCH @ 2%. FBC
 107.3.5
  
 5) VALUE APPEARS TOO LOW. PROVIDE A SIGN BONA FIDE
 CONTRACT. WPB AMEND 109.3
  
 6) A SUB PLUMBING PERMIT BY A LICENSE PLUMBING
 CONTRACTOR IS REQUIRED. FS 489
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  