Plan Review Details - Permit 19051600
Plan Review Stops For Permit 19051600
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-09-19 Cont ID  
Sent By pleduc Date 2019-09-19 Time   Rev Time 0.00
Received By pleduc Date 2019-09-19 Time 12:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By pleduc Date 2019-07-19 Time   Rev Time 0.00
Received By pleduc Date 2019-07-19 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-05 Cont ID  
Sent By J.Walker Date 2019-06-05 Time   Rev Time  
Received By   Date 2019-06-05 Time   Sent To M
Notes
2019-06-05 16:11:48NFPA 96 REQUIREMENTS WILL APPLY AT TIME OF TESTING AND
 INSPECTION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-20 Cont ID  
Sent By shill Date 2019-09-20 Time 06:33 Rev Time 0.00
Received By shill Date 2019-09-18 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-30 Cont ID  
Sent By pvalenti Date 2019-07-30 Time 12:50 Rev Time 0.00
Received By pvalenti Date 2019-07-18 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-13 Cont ID  
Sent By hmoser Date 2019-06-13 Time 10:21 Rev Time 0.00
Received By hmoser Date 2019-05-31 Time 14:52 Sent To  
Notes
2019-06-03 14:52:38ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-09-19 Cont ID  
Sent By pvalenti Date 2019-09-19 Time 09:28 Rev Time 0.00
Received By pvalenti Date 2019-09-19 Time 08:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-30 Cont ID  
Sent By pvalenti Date 2019-07-30 Time 11:06 Rev Time 0.00
Received By pvalenti Date 2019-07-30 Time 11:05 Sent To  
Notes
2019-07-30 11:21:19***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND MECHANICAL REVIEW DENIED:
  
 1. FBC M 503.2 AND FBC M 506.3 PROVIDE SEPERATE PLANS
 SPECIFIC TO HOODS WITH GREASE/EXHAUST AND MAKE-UP AIR
 DUCT DETAILS. THE GREASE DUCT DETAILS NEED TO INCLUDE
 THE IN-LINE EXHAUST FAN (IF USED) FIRE RATED ENCLOSURE
 /FIRE WRAP/ACCESS DOOR INFORMATION.
 2. FBC B 107.2.1 ALL INFORMATION ON CONSTRUCTION
 DOCUMENTS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By hmoser Date 2019-06-13 Time 10:21 Rev Time 0.00
Received By hmoser Date 2019-06-13 Time 09:41 Sent To I
Notes
2019-06-13 10:21:07PLAN DENIED
 1) PROVIDE EXHAUST DUCT AND MAKEUP AIR DUCT ON PLAN.
 PER SECTION 506 COMMERCIAL KITCHEN HOOD VENTILATION
 SYSTEM DUCTS AND EXHAUST EQUIPMENT.
 2017 FBC (M)
 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION DRAWINGS SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. 2017
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-19 Cont ID  
Sent By pvalenti Date 2019-09-19 Time 09:28 Rev Time 0.00
Received By pvalenti Date 2019-09-19 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-07-25 Cont ID  
Sent By shill Date 2019-07-25 Time 08:25 Rev Time 0.00
Received By shill Date 2019-07-25 Time 08:25 Sent To  
Notes
***NONE***